GRUNDFOS ALLDOS DME Series User manual

GRUNDFOS ALLDOS INSTRUCTIONS
DME with PROFIBUS
Installation and operating instructions

2

Table of contents
3
DME with PROFIBUS
English (GB)
Installation and operating instructions....................................................................................................................... 4
Norsk (NO)
Installasjons- og driftsinstruksjon............................................................................................................................ 13

English (GB)
4
English (GB) Installation and operating instructions
CONTENTS
Page
1. Introduction
This document describes the functional profile for
Grundfos Alldos DME dosing pumps:
• DME (2-48 l/h)
• DME (60-940 l/h).
For identification of DME model, see section 3.
2. Connections
The DME pump is supplied with an IP 65 RS-485 M12 connector.
Fig. 1 M12 connector, IP 65
3. Identification of DME model
The DME model is identified by the first letter in the model
number.
Fig. 2 Model identification
4. Device identification
The ID number is accessible by sending a diagnostic request
telegram from the master.
ID numbers of DME dosing pumps:
5. Addressing
The address is factory-set to a standard value (126).
The PROFIBUS address of each DME pump in the bus system
must have a unique written value for the network communication
to work. This can be done via the bus if the units are connected
one at a time.
The PROFIBUS address can also be changed via the DME pump
display. From the menu, select "SETUP" and then "NUMBER".
6. Slave diagnosis services
Via the diagnosis, the slave informs the master of its current
mode. It consists at least of the information specified in the
standard, in the first 6 octets, such as the status of the state
machine. The user can supplement this information (user
diagnosis) with process-specific information (for example wire
break).
On the slave's initiative, the diagnosis can be transmitted as error
message and as status message. In addition to 3 defined bits, the
user also influences the application-specific diagnostic data.
However, any master (not only the assigned master) can poll the
current diagnostic information.
6.1 Application-specific diagnostic data
The DME dosing pump has device-related diagnostics
(see IEC 50170 vol. 2 for protocol-specific information).
The diagnostics consist of 3 bytes of user-specific diagnostics in
the following format:
The user diagnostic byte Status has the following format:
Fig. 3 Overview of the user diagnostic byte Status
1. Introduction 4
2. Connections 4
3. Identification of DME model 4
4. Device identification 4
5. Addressing 4
6. Slave diagnosis services 4
6.1 Application-specific diagnostic data 4
6.2 Watchdog 5
7. References 5
8. Mode control and status 5
9. Modes of the DME 5
10. DME inputs 5
11. DME display unit 5
12. Anti-cavitation 6
13. Status of pump LEDs 6
14. Alarm status 6
15. Dosing control 7
16. Commands (output) 7
16.1 PROFIBUS commands available 8
17. Data item overview (inputs) 9
18. Software overview 12
18.1 GSD file (DME model C) 12
18.2 GSD file (DME model A) 12
18.3 GSD file (DME model B) 12
19. Disposal 12
Prior to installation, read these installation and
operating instructions. Installation and operation
must comply with local regulations and accepted
codes of good practice.
TM03 2640 4705
M12 connector 9-pin D-sub connector
Pin Pin
1VP 6
2 RxD/TxD-N 8
3DGND 5
4RxD/T-P 3
5Screen 1
TM03 2487 4405
Pump Model ID number
Hex value
DME 2-18
DME (2-48 l/h) C 0970
DME 8-10
DME 12-6
DME 19-6
DME 48-3
DME 60-10
DME (60-940 l/h) A 0971
DME 150-4
DME 375-10
DME 940-4
Status DME SW. ver. Profi SW. ver.
TM02 1728 2001
Made in France
Type
Model
UP
max
Q
H
Imax
f
VHz A
IP 65
W
l/h
Bar
~
96441587
N2042
A96462494P101320001

English (GB)
5
The other two user diagnostic bytes indicate the software
versions of both the DME dosing pump and the PROFIBUS add-
on module.
6.2 Watchdog
The dosing pump can be configured so that it stops pumping if
communication fails.
The configuration must be done in two steps:
1. Enable the communication watchdog with the commissioning
tool or PLC.
2. Send the command 26 comm_watch_e to the dosing pump,
otherwise the pump will not react to a communication
watchdog timeout. The configuration is stored in non-volatile
memory, e.g. EEPROM.
To disable this feature, send the command 27 comm_watch_d
to the dosing pump or disable the communication watchdog
with the commissioning tool or PLC.
7. References
8. Mode control and status
A DME pump has the mode scheme shown below.
By means of the commands - also shown below - a DME pump
can be set to operate as required. This corresponds to operating
it via the buttons on the front panel.
9. Modes of the DME
The tables below show the data items holding information about
the actual operating mode of the DME pump.
act_mode1 (I,54) – actual mode status no. 1
+Only DME (60-940 l/h)
act_mode2 (I,55) – actual mode status no. 2
act_mode3 (I,56) – actual mode status no. 3
This byte is not influenced by the setup status. It contains
information about modes for which no setup exists. These modes
are typically generated by the system itself.
10. DME inputs
The tables below show the data items holding information about
how the inputs of the DME pump are configured.
input_setup1 (I,62) – mode of configurable inputs
* Only DME (2-48 l/h)
input_setup2 (I,65)+– mode of configurable inputs
+ Only DME (60-940 l/h)
11. DME display unit
The table below shows the data items holding information about
how the DME pump is configured to show units in the display.
scaling_setup (I,63) – display mode
Reference Document title Document file
/1/ PROFIBUS Protocol Specification EN 50170 vol. 2
System
modes Normal Alarm
Standby
Operating
modes Start Stop
Control
modes Manual Analog Pulse Timer Batch
Bit no. Description
2-0
Operating modes (user modes):
000: Start
001: Stop
010: –
011: Max.
5-3
Control modes:
000: Manual
001: Pulse
010: Analog
011: Timer
100: Batch
6Anti-cavitation:
0: Disabled
1: Enabled
7+Auto restart after alarm:
0: Disabled
1: Enabled
Bit no. Description
6Communication watchdog:
0: Disabled
1: Enabled
Bit no. Description
2-0
System modes:
000: Normal
011: Survive
100: Alarm Standby
3Pending alarm:
0: No alarm
1: Alarm
5Calibration mode:
0: Disabled
1: Enabled
6Bleeding:
0: Disabled
1: Enabled
Bit no. Description
1-0 External stop:
01: Normally open
10: Normally closed
3-2
Level modes:
00: Monitor function*
01: Normally open
10: Normally closed
6-4
Analog modes:
000: 4-20 mA
001: 20-4 mA
010: 0-20 mA
011: 20-0 mA
7-
Bit no. Description
0Diaphragm input:
0: Normally open
1: Normally closed
1Monitor input:
0: Disabled
1: Enabled
Bit no. Description
1-0 Unit in display:
00: Metric (litre)
01: US (gallon)

English (GB)
6
12. Anti-cavitation
The table below shows the data items holding information about
how much the max. capacity is reduced to avoid cavitation.
Note:
• Only DME (60-940 l/h).
• Remember to enable anti-cavitation, see section 9. Modes of
the DME for further information.
13. Status of pump LEDs
The status of the pump LEDs can be requested via the data item
led_contr defined below.
Note that the relay status follows the ON condition of the red
LED.
Using 'NC' terminal at the relay means that active equals an open
relay.
Using 'NO' terminal means that active equals a closed relay.
led_contr (I,44) – LED indication
*Add-on feature, not available on DME 2-48 pumps with
PROFIBUS
Interpretation of LEDs and status of the alarm relay.
Note that the relay status follows the ON condition of the red
LED.
Using 'NC' terminal at the relay means that active equals an open
relay.
Using 'NO' terminal means that active equals a closed relay.
14. Alarm status
alarm_code (I,59)
Alarms are recorded in alarm_code. All alarms result in the DME
entering the Alarm Standby mode.
In this mode, the green LED on the pump is switched off and the
red LED is switched on. The value of alarm_code is kept and not
updated (cleared) until restarting is attempted. An automatic
restart will occur if the cause of the alarm disappears.
The alarm_code will then be cleared and the green LED will be
switched on again.
The table below shows supported alarms:
+Only DME (60-940 l/h)
* Not configurable in DME (2-48 l/h), but always set to "Yes"
** Generated by PROFIBUS module
•act_mode3, bits 0-2, (see section 9.) holds information about
the pump being in Alarm Standby or not and
•act_mode3, bit 3, holds information about the presence of an
unacknowledged (pending) alarm.
reset_alarm will acknowledge (clear) the alarms that can be
cleared.
alarm_code_disp (I,57)
This data item is identical to alarm_code.
warning_code (I,58)
Warnings are recorded in warning_code. A warning does not lead
to any action of the DME pump, but both red and green LEDs are
switched on. When the cause of the warning disappears, the
code is cleared.
The table below shows supported warnings:
+Only DME (60-940 l/h)
Bit no. Description
2-0
Capacity reduction:
000: Max. capacity reduced to 75 %
001: Max. capacity reduced to 50 %
010: Max. capacity reduced to 25 %
Bit no. Description
1-0
00: LED 1 (green) off
01: LED 1 (green) on
10: LED 1 (green) flashing
11: –
3-2
00: LED 2 (red) off
01: LED 2 (red) on
10: LED 2 (red) flashing
11: –
Green
LED Red
LED Cause Alarm
relay*
Off Off Power off or fault in mains connection –
On Off System mode Normal,
operating mode Start –
Flashing Off System mode Normal,
operating mode Stop –
On On System mode Survive,
operating mode Start
(pump keeps dosing despite warning) Active
Flashing On System mode Survive,
operating mode Stop Active
Off On System mode Alarm Standby Active
Code Alarm cause Automatic
restarting Description/action
19+Diaphragm break No The alarm must always be acknowledged by a reset_alarm command which
also clears pending alarm bit.
48+Overload (maximum
pressure exceeded)
57 Dry running (low liquid level) Configurable* Can be configured to "Enabled" or "Disabled" in DME (60-940 l/h).
64 Overtemperature
76** Internal communication fault Yes The PROFIBUS module always clears the alarm when communication is
restored with the DME. reset_alarm command clears pending alarm bit.
83 Parameter area verification
error (EEPROM) Pump stopped The alarm cannot be cleared. DME must be re-powered.
88 Sensor fault (analog input) Yes The alarm is always cleared by the DME auto restart function.
reset_alarm command clears pending alarm bit.
154+Display communication fault
174+Origo sensor fault Pump stopped The alarm cannot be cleared. DME must be re-powered.
173+Hall sensor fault
Code Warning cause
17 Max. flow (exceeds max. capacity in pulse mode)
48+Overload (maximum pressure exceeded)
57 Low liquid level
59 No flow

English (GB)
7
15. Dosing control
Figure 4 shows the data items used in the five control modes.
For all control modes, the data item max_dosing_flow will limit the
actual capacity to this value.
For the control mode Manual, it is not possible to select a value
higher than this limit.
Fig. 4 The five control modes and the data items used for
generating the actual capacity
16. Commands (output)
Via the module definition "Commands Buffer" in the GSD file, it is
possible to use the 8 defined output bytes of the module to send
commands to the DME dosing pump.
The "Commands Buffer" module is mandatory and the first
module when configuring a DME PROFIBUS slave on the
network.
The first byte is used to indicate the command, and the following
3 bytes are for future use ("don't care" at the moment). The next
4 bytes are used to represent the data item which can be from
8 bits to 32 bits. Some commands do not have a data item, and
the value of the 4 data bytes is "don't care".
Example 1
To start, the DME dosing pump must receive command number
3 (0x03).
The 8 outputs will look like this to start the pump:
Example 2
The pulse dosing volume is to be set to
0.975 ml/p ⇒975 000 nl/p.
The data format for pulse dosing volume is a 32-bit data item,
hence 975,000 is 00 0E E0 98 in hexadecimal.
The command for setting the pulse dosing volume is number
17 (0x11).
The 8 outputs will look like this to set the pulse dosing volume to
0.975 ml/p:
Example 3
The timer dosing period is to be set to 1 day, 2 hours and
45 minutes.
The data format for the timer dosing period is a 16-bit data item,
hence 1 day, 2 hours and 45 minutes are 1605 minutes and
00 00 06 45 in hexadecimal.
The command for setting the timer dosing period is number
20 (0x14).
The 8 outputs will look like this to set the timer dosing period to
1 day, 2 hours and 45 minutes:
For acknowledge purpose indicating that the command is
executed in the DME dosing pump, the command is returned from
the DME dosing pump to the PROFIBUS master via the
"Command Ack" module which defines 1 input byte in the GSD
file.
If the command is executed successfully, the value of the
command is returned in command_ack.
If, for some reason, the command is not executed (e.g. a pump
fault), the value 0xFF is returned in command_ack. The master
must then send the idle command (0x00) or another command
before sending the failed command again.
Note: To get this acknowledge feature, it is important to add the
module in the parameterization, the "Command Ack" module
must be added, when configuring the DME PROFIBUS slave on
the network.
Example 1 without error
To stop, the DME dosing pump must receive command number
4 (0x04).
The 8 outputs will look like this to stop the pump:
The Data_Exchange cycles will look like this for the first output
and the command_ack:
Example 2 with error
To stop, the DME dosing pump must receive command number
4 (0x04).
The 8 outputs will look like this to stop the pump:
The Data_Exchange cycles will look like this for the first output
and the command_ack:
TM02 1726 2001
0x03 0x00 0x00 0x00 0x00 0x00 0x00 0x00
0x11 0x00 0x00 0x00 0x00 0x0E 0xE0 0x98
Capacity
0x14 0x00 0x00 0x00 0x06 0x45 0x00 0x00
0x04 0x00 0x00 0x00 0x00 0x00 0x00 0x00
Cycle no. Command output 0 Command_ack (I,0)
10x00 0x00
20x04 0x00
30x04 0x04
0x04 0x00 0x00 0x00 0x00 0x00 0x00 0x00
Cycle no. Command output 0 Command_ack (I,0)
10x00 0x00
20x04 0x00
3 0x04 0xFF
4 0x00 0xFF
50x00 0x00
60x04 0x00
70x04 0x04

English (GB)
8
16.1 PROFIBUS commands available
+ Only DME (60-940 l/h)
Identifier Command Data item Description
RESET_ALARM 1 Don't care Clears a possible pending alarm.
FACT_BOOT 2 Don't care All configuration parameters are returned to the factory setting.
START 3 Don't care Starts the pump (operating mode Start).
Updates the act_mode1, bits 0-2, accordingly.
STOP 4 Don't care Stops the pump (operating mode Stop).
Updates the act_mode1, bits 0-2, accordingly.
MANUAL 5 Don't care
Sets the pump to control mode Manual dosing.
The dosing setpoint man_dosing_flow can now be controlled via
the + and – buttons and from the PROFIBUS via bus_dosing_flow.
Updates the act_mode1, bits 3-5, accordingly.
PULSE 6 Don't care
Sets the pump to control mode Pulse dosing.
The pump will dose pulse_dosing_volume for each external electrical
pulse input.
Updates the act_mode1, bits 3-5, accordingly.
ANALOG 7 Don't care
Sets the pump to control mode Analog dosing.
The dosing setpoint (flow) can now be controlled from the analog input
(4-20 mA).
Updates the act_mode1, bits 3-5, accordingly.
TIMER 8 Don't care Sets the pump to control mode Timer dosing.
The pump will dose timer_dosing_volume for every timer_dosing_period.
Updates the act_mode1, bits 3-5, accordingly.
BATCH 9 Don't care
Sets the pump to control mode Batch dosing.
The pump will dose batch_dosing_volume with maximum capacity for
each external electrical pulse input.
Updates the act_mode1, bits 3-5, accordingly.
ANTI_CAVITATE_E 10 Don't care Enables the DME anti-cavitation mechanism (prolonged suction).
ANTI_CAVITATE_D 11 Don't care Disables the DME anti-cavitation mechanism.
DOSE_BATCH 12 Don't care The pump doses a batch in control mode Batch dosing.
START_BLEED 13 Don't care The pump starts bleeding (pressing 100 % button).
STOP_BLEED 14 Don't care The pump stops bleeding (releasing 100 % button).
LOCK_KEYS 15 Don't care Locks the + and – buttons on the pump.
UNLOCK_KEYS 16 Don't care Unlocks the + and – buttons on the pump.
PULSE_DOSING_VOLUME 17 hi, lo1, lo2, lo3 Sets the dosing volume to be used in control mode Pulse dosing.
BATCH_DOSING_VOLUME 18 hi, lo1, lo2, lo3 Sets the dosing volume to be used in control mode Batch dosing.
TIMER_DOSING_VOLUME 19 hi, lo1, lo2, lo3 Sets the dosing volume to be used in control mode Timer dosing.
TIMER_DOSING_PERIOD 20 hi, lo Sets the period of time between dosing in control mode Timer dosing.
TIMER_DOSING_START 21 hi, lo Sets the start time of first dosing in control mode Timer dosing.
MAX_DOSING_FLOW 22 hi, lo1, lo2, lo3 Sets the pump's maximum allowed flow.
CALIBRATION_VOLUME 23 hi, lo1, lo2, lo3 Sets the calibration value of the pump.
LANGUAGE 24 hi Sets the language to be used in menus.
BUS_DOSING_FLOW 25 hi, lo1, lo2, lo3 Sets the dosing capacity to be used in control mode Manual dosing.
COMM_WATCH_E 26 Don't care Enables the communication watchdog which will stop the pump
if communication fails.
COMM_WATCH_D 27 Don't care Disables the communication watchdog.
AUTO_RESTART_E+28 Don't care Enables auto restart after alarm.
AUTO_RESTART_D+29 Don't care Disables auto restart after alarm.
INPUT_SETUP1+30 hi Set up of inputs 1, see section 10.
SCALING_SETUP+31 hi Set up of unit, see section 11.
ANTI_CAVI_SETUP+32 hi Set up of anti-cavitation function, see section 12.
INPUT_SETUP2+33 hi Set up of inputs 2, see section 10.

English (GB)
9
17. Data item overview (inputs)
Abbreviations used:
The table below shows all possible inputs (parameters) in bytes
from the DME pump.
Each parameter is defined as a module in the GSD file. The
modules contain 1 to 4 bytes of input depending on the actual
parameter size. Each module also contains a definition of up to 4
user parameters, which are the actual input number according to
the table below. It is thus possible to add the modules in random
order.
The benefit from defining each parameter as a module in the
GSD file is that the PROFIBUS network only has to read the
number of inputs defined by the modules added by the network
designer. For instance, it is not necessary to read
timer_dosing_volume, which occupies 4 bytes of input, if the
pump is only used in manual control mode.
Example
The module "Pulse Dosing Volume" defines 4 bytes of input
containing:
• pulse_dosing_volume_hi
• pulse_dosing_volume_lo1
•pulse_dosing_volume_lo2
•pulse_dosing_volume_lo3
where pulse_dosing_volume_hi is the most significant byte and
pulse_dosing_volume_lo3 is the least significant byte.
unsca.: The data item is unscaled (e.g. a number, a counter,
etc.).
lo: This is the low-order byte to a 16/32-bit value.
Scaling follows high order.
bits: The data item is bit-interpreted. The bit
interpretation is explained in the next sections.
<unit>: The data item has this unit (with a possible prefix
and factor) as its fixed scaling.
No. Parameter
name Byte
weight Parameter description Scaling Factory setting Range Changes
during
operation
Con-
version
index
Data
type
0 Command Ack Command to pump is
returned as an acknowledge Yes 0 5
1Pulse Dosing
Volume
Hi Dosing volume to be used in
control mode "Pulse" dosing 1 nl/P Yes 0 7
2Lo1
3Lo2
4Lo3
5Batch Dosing
Volume
Hi Dosing volume to be used in
control mode "Batch" dosing 0.1 ml Yes –3 7
6Lo1
7Lo2
8Lo3
9Timer Dosing
Volume
Hi Dosing volume to be used in
control mode "Timer" dosing 0.1 ml Yes –3 7
10 Lo1
11 Lo2
12 Lo3
13 Timer Dosing
Period Hi Dosing period to be used in
control mode "Timer" dosing 1 minute Yes 0 6
14 Lo
15 Timer Dosing
Start
Hi Dosing start time to be used
in control mode "Timer"
dosing 1 minute Yes 0 6
16 Lo
17 Max. Dosing
Flow
Hi Maximum allowed dosing
flow 0.1 ml/h Yes –3 7
18 Lo1
19 Lo2
20 Lo3
21 Calibration
Volume
Hi Value used when calibrating
the pump 0.1 ml See
table
below Yes –3 7
22 Lo1
23 Lo2
24 Lo3
25 Language
Code for pump display:
0: English 0-13 Yes 0 5
0: English
1: German
2: French
3: Dutch
4: Spanish
5: Italian
6: Portuguese
7: Danish
8: Swedish
9: Finnish
10: Czech
11: Slovak
12: Polish
13: Russian

English (GB)
10
26 Bus Dosing
Flow
Hi Dosing setpoint from
PROFIBUS 0.1 ml/h See
table
below Yes –3 7
27 Lo1
28 Lo2
29 Lo3
30 Hours Hi Two-hour counter 2 hours 0-65535 Yes 0 6
31 Lo
32 Temperature Temperature in motor/pump 1°C 0-90 Yes 0 2
33 Manual
Dosing Flow
Hi Dosing flow used in control
mode "Manual" dosing 0.1 ml/h Yes –3 7
34 Lo1
35 Lo2
36 Lo3
37 Actual Dosing
Flow
Hi Actual dosing flow,
regardless of control mode 0.1 ml/h Yes –3 7
38 Lo1
39 Lo2
40 Lo3
41 Max. Pump
Flow Hi Maximum pump flow 0.5 l/h
DME 2-18: 5
Fixed No 0 6
DME 4-15: 8
DME 8-10: 15
DME 12-6: 24
DME 19-6: 37
DME 48-3: 96
DME 60-10: 120
DME 150-4: 300
DME 375-10: 752
DME 940-4: 1280
42 Lo
43 Max. Pump
Pressure Maximum pump pressure
(head) 0.1 bar
DME 2-18: 180
Fixed No –1 5
DME 4-15: 150
DME 8-10: 100
DME 12-6: 60
DME 19-6: 62
DME 48-3: 26
DME 60-10: 100
DME 150-4: 40
DME 375-10: 100
DME 940-4: 40
44 LED Control Status of green and red
LEDs
If no alarm:
Bits 1-0: Green LED
10: Flashing
Bits 3-2: Red LED
00: Off
8 bits Yes 0 5
45 Power On
Counter Hi Number of times the pump
has been powered on 1 0-65535 Yes 0 6
46
Stroke
Counter
Lo
Pump stroke counter 1 0-
999.999.
999 Yes 0 7
47 Hi
48 Lo1
49 Lo2
50 Lo3
51 Analog Input Hi Value from the analog input
0-20 mA:
4.9 uA If no input signal, the bit
will read 0 0-4095 Yes 0 6
52 Lo 4-20 mA:
3.9 uA
53 Digital Inputs
Logical value of the digital
level inputs:
Bit 0: Level alarm input
Bit 1: Level warning input
Bit 2: External stop input+
Bit 3: Monitor input+
Bit 4: Leakage/diaphragm
input+
Bit 5: Pulse input+
If no input signal, the bit
will read 0 8 bits Yes 0 5
No. Parameter
name Byte
weight Parameter description Scaling Factory setting Range Changes
during
operation
Con-
version
index
Data
type

English (GB)
11
* Only DME (0-48 l/h)
+Only DME (60-940 l/h)
54 Actual Mode 1 Actual mode status no. 1
Bits 2-0: Operating mode:
001: Stop
Bits 5-3: Control mode:
000: Manual dosing
Bit 6: Anti-cavitation:
0: Disabled
Bit 7: Auto restart after
alarm:
0: Disabled
8 bits Yes 0 5
55 Actual Mode 2 Actual mode status no. 2
Bit 5: Button status:
0: Unlocked
Bit 6: Communication
watchdog:
0: Disabled
8 bits Yes 0 5
56 Actual Mode 3 Actual mode status no. 3
If no alarm:
Bits 2-0: System mode:
000: Normal
Bit 3: Pending alarm:
0: No alarm
Bit 5: Calibration mode:
0: Disabled
Bit 6: Bleeding
0: Disabled
8 bits Yes 0 5
57 Alarm Code
Disp Identical to alarm code If no alarm:
00-255 Yes 0 5
58 Warning Code Actual warning code If no warning:
00-255 Yes 0 5
59 Alarm Code Actual alarm code If no alarm:
00-255 Yes 0 5
60 DME SW
Version DME software version 160 0-255 No –2 5
61 PROFIBUS
SW Version PROFIBUS software
version 140 0-255 No –2 5
62 Input Setup1* Setup of inputs
Bits 1-0: External stop:
01: Normally open
Bits 3-2: Level mode:
01: Normally open
Bits 6-4: Analog mode:
000: 4-20 mA
8 bits Yes 0 5
63 Scaling Setup* Unit to appear in DME
display Bits 1-0: Unit in display:
00: Metric (litre) 8 bits Yes 0 5
64 Anti Cavitation
Setup+Setup of anti-cavitation
function
Bits 2-0: Capacity
reduction:
000: 0 (max. capacity
reduced to 75%)
8 bits Yes 0 5
65 Input Setup2+Setup of inputs
Bit 0: Diaphragm input:
0: Normally open
Bit 1: Monitor input:
0: Disabled
8 bits Yes 0 5
No. Parameter
name Byte
weight Parameter description Scaling Factory setting Range Changes
during
operation
Con-
version
index
Data
type

English (GB)
12
18. Software overview
The GSD files mentioned below can be downloaded from the
Grundfos Alldos Website www.grundfosalldos.com in the
Download section.
18.1 GSD file (DME model C)
GSD file name: GRUN0970.GSD
Grundfos Alldos DME pumps with flow rates from 2.5 l/h to 48 l/h,
model C with software version 1.60.
The model can be identified by the first letter in the model number
"C"96xxxxxxxxxxxxxxxx. See fig. 2.
18.2 GSD file (DME model A)
GSD file name: GRUN0971.GSD
Grundfos Alldos DME pumps with flow rates from 60 l/h to 940 l/h,
model A after week 23 year 2005.
The model and the production week appear from the model
number. See fig. 2.
"A"96xxxxxxP1"0523"xxxx.
18.3 GSD file (DME model B)
GSD file name: DME_05B0.GSD*
Grundfos Alldos DME pumps with flow rates from 2.5 l/h to 48 l/h,
model B.
The model can be identified by the first letter in the model number
"B"96xxxxxxxxxxxxxxxx. See fig. 2.
*For this product, please use the Profibus documentation
supplied with the product.
19. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use appropriate waste collection services.
2. If this is not possible, contact the nearest Grundfos or
Grundfos Alldos company or service workshop.
Calibration volume Bus dosing flow
Metric (litre) Bus dosing flow
US (gallon)
Pump Scaling Min. Max. Cavitati
on Profile
no. Scaling Min. Max. Scaling Min. Max.
DME 2-18 0.1 ml 116 578 Off n/a 0.1 ml/h 25 25000 0.01 mgal/h 66 66000
On n/a 0.1 ml/h 25 18000 0.01 mgal/h 66 47400
DME 8-10 0.1 ml 347 1388 Off n/a 0.1 ml/h 75 75000 0.01 mgal/h 198 198000
On n/a 0.1 ml/h 75 56000 0.01 mgal/h 198 147000
DME 12-6 0.1 ml 556 2222 Off n/a 0.1 ml/h 120 120000 0.01 mgal/h 316 316000
On n/a 0.1 ml/h 120 90000 0.01 mgal/h 316 236000
DME 19-6 0.1 ml 1019 4633 Off n/a 0.1 ml/h 185 185000 0.01 mgal/h 488 488000
On n/a 0.1 ml/h 185 145000 0.01 mgal/h 488 382000
DME 48-3 0.1 ml 2639 9999 Off n/a 0.1 ml/h 480 480000 0.01 mgal/h 1260 1260000
On n/a 0.1 ml/h 480 370000 0.01 mgal/h 1260 975000
DME 60-10 0.1 ml 3130 12500
Off n/a 0.1 ml/h 750 600000 0.1 mgal/h 198 158000
On 0 0.1 ml/h 750 450000 0.1 mgal/h 198 118000
On 1 0.1 ml/h 750 334000 0.1 mgal/h 198 88000
On 2 0.1 ml/h 750 161000 0.1 mgal/h 198 42400
DME 150-4 0.1 ml 7810 31250
Off n/a 0.1 ml/h 2000 1500000 0.1 mgal/h 525 396000
On 0 0.1 ml/h 2000 1120000 0.1 mgal/h 525 294000
On 1 0.1 ml/h 2000 835000 0.1 mgal/h 525 220000
On 2 0.1 ml/h 2000 404000 0.1 mgal/h 525 106000
DME 375-10 0.1 ml 19580 78330
Off n/a 0.1 ml/h 5000 3760000 0.1 mgal/h 1320 990000
On 0 0.1 ml/h 5000 2820000 0.1 mgal/h 1320 740000
On 1 0.1 ml/h 5000 2100000 0.1 mgal/h 1320 550000
On 2 0.1 ml/h 5000 1010000 0.1 mgal/h 1320 266000
DME 940-4 0.1 ml 48960 195830
Off n/a 0.1 ml/h 12000 9400000 0.1 mgal/h 3160 2480000
On 0 0.1 ml/h 12000 7050000 0.1 mgal/h 3160 1860000
On 1 0.1 ml/h 12000 5250000 0.1 mgal/h 3160 1380000
On 2 0.1 ml/h 12000 2520000 0.1 mgal/h 3160 665000
Conversion index Conversion factor
74 0.1
2100
110
01
–1 0.1
–2 0.01
–3 0.001
–4 0.0001
Data type Description
2 Integer 8
3 Integer 16
4 Integer 32
5 Unsigned 8
6 Unsigned 16
7 Unsigned 32
9Textstring
Subject to alterations.

Norsk (NO)
13
Norsk (NO) Installasjons- og driftsinstruksjon
INNHOLD
Side
1. Innledning
Dette dokumentet beskriver funksjonen for Grundfos Alldos DME
doseringspumper:
• DME (2-48 l/h)
• DME (60-940 l/h).
For å indentifisere DME modellbetegnelse, se kapittel 3.
2. Tilslutninger
DME pumpen har en IP 65 RS-485 M12 kontakt.
Fig. 1 M12 kontakt, IP 65
3. Identifisere DME modellbetegnelse
DME modellbetegnelse identifiseres av den første bokstaven i
modellnummeret.
Fig. 2 Modellidentifisering
4. Apparat identifisering
ID nummeret fåes ved å sende en diagnoserings forespørsel fra
masteren.
ID nummer til DME doseringspumper:
5. Adressering
Adressen er fabrikksinnstilt til en standardverdi (126). PROFIBUS
adressen til hver enkelt DME pumpe på bussystemet må være
unik for at kommunikasjonen i nettverket skal fungere. Dette kan
gjøres via bussen hvis enhetene kobles til en og en om gangen.
PROFIBUS adressen kan også forandres via displayet på DME
pumpen. Fra menyen, velg "SETUP" og videre "NUMBER".
6. Slave diagnose verktøy
Slaven informerer masteren om sin nåværende status via slave
diagnose verktøyet. Informasjonen består minimum av den infor-
masjonen som er beskevet i standarden i de første 6 oktetter, slik
som f.eks status på apparatet. Brukeren kan legge til ekstra infor-
masjon (bruker informasjon) med informasjon spesielt om appli-
kasjonen (f.eks ledningsbrudd).
På slavens initiativ kan informasjonen overføres som en feilmel-
ding eller statusmelding. I tillegg til 3 forhåndsdefinerte bits kan
brukeren også påvirke applikasjonsspesifikk informasjon. Enhver
master (ikke bare den tildelte) kan hente denne informasjonen.
6.1 Applikasjonsspesifikk informasjon
DME doseringspumpene har tilleggsinformsjon som er knyttet
opp mot pumpemodellen (se IEC 50170 vol. 2 for prtokoll spesi-
fikk informasjon). informasjonen inneholder 3 bytes med bruker-
definert informasjon med følgende format:
Det brukerdefinertet bytet Status har følgende format:
Fig. 3 Oversikt over det brukerdefinertet bytet Status
De andre to brukerdefinerte bytene forteller om software versjo-
nene til både DME doseringspumpen og PROFIBUS tilleggs
modulen.
1. Innledning 13
2. Tilslutninger 13
3. Identifisere DME modellbetegnelse 13
4. Apparat identifisering 13
5. Adressering 13
6. Slave diagnose verktøy 13
6.1 Applikasjonsspesifikk informasjon 13
6.2 Watchdog 14
7. Referanser 14
8. Kontrollmodus og status 14
9. Driftsmodus for DME 14
10. DME innganger 14
11. DME enhetsvisning 14
12. Anti-kavitasjon 15
13. Status på pumpenes lysdioder. 15
14. Alarm status 15
15. Doseringsstyring 16
16. Kommandoer (utganger) 16
16.1 Oversikt over PROFIBUS kommandoer 17
17. Oversikt over dataelementer (innsignaler) 18
18. Software oversikt 21
18.1 GSD fil (DME modell C) 21
18.2 GSD fil (DME modell A) 21
18.3 GSD fil (DME modell B) 21
19. Avhending 21
Advarsel
Les denne installasjons- og driftsinstruksjonen
før montering. Følg lokale forskrifter og allmen
god praksis ved installasjon og drift.
TM03 2640 4705
M12 kontakt 9-pin D-sub kontakt
Stift Stift
1VP 6
2 RxD/TxD-N 8
3DGND 5
4RxD/T-P 3
5Skjerm 1
TM03 2487 4405
Pumpe Modell ID nummer
Hex verdi
DME 2-18
DME (2-48 l/h) C 0970
DME 8-10
DME 12-6
DME 19-6
DME 48-3
DME 60-10
DME (60-940 l/h) A 0971
DME 150-4
DME 375-10
DME 940-4
Status DME SW. ver. Profi SW. ver.
TM02 1728 2001
Made in France
Type
Model
UP
max
Q
H
Imax
f
VHz A
IP 65
W
l/h
Bar
~
96441587
N2042
A96462494P101320001

Norsk (NO)
14
6.2 Watchdog
Doseringspumpen kan settes opp slik at den stopper å pumpe
dersom kommunikasjonen feiler.
Oppsettet må gjøres i to steg:
1. Aktivere watchdog funksjonen med oppstartsverktøyet eller
PLS'en.
2. Send kommandoen 26 comm_watch_e til doseringspumpen.
Hvis ikke vil ikke pumpen reagere dersom det går for lang tid
mellom to signaler. Konfigurasjonen lagres i et minne som ikke
er strømavhengig, f.eks EEPROM.
For å deaktivere denne funksjonen, send kommandoen 27
comm_watch_d til doseringspumpen eller deaktiver innstillin-
gen watchdog fra oppstartsverktøyet eller PLS'en.
7. Referanser
8. Kontrollmodus og status
En DME pumpe kan styres som vist nedenfor.
Ved bruk av kommandoer - også vist nedenfor - kan en DME
pumpe stilles inn til å fungere som ønsket. Dette tilsvarer å styre
pumpen med tastene på pumpens styrepanel.
9. Driftsmodus for DME
Tabellene nedenfor angir hvor informasjon om hvor de forskjellige
driftsmodus lagres.
act_mode1 (I,54) – aktuelle driftsmodus 1
+Kun DME (60-940 l/h)
act_mode2 (I,55) – aktuelle driftsmodus 2
act_mode3 (I,56) – aktuelle driftsmodus 3
Dette bytet påvirkes ikke av oppsettet. Det inneholder informa-
sjon for modus som ikke kan forandres. Disse modusene endres
automatisk av systemet.
10. DME innganger
Tabellene nedenfor angir hvor informasjon om data til oppsettet
for inngangene til DME pumpene lagres.
input_setup1 (I,62) – modus for innganger som kan forandres
* Kun DME (2-48 l/h)
input_setup2 (I,65)+– modus for innganger som kan
forandres
+ Kun DME (60-940 l/h)
11. DME enhetsvisning
Tabellene nedenfor angir hvor informasjon om data til oppsettet
for hvordan visning av enheter til DME pumpene lagres.
scaling_setup (I,63) – visningsmodus
Referanse Dokument tittel Dokument fil
/1/ PROFIBUS Protokoll Spesifika-
sjon EN 50170 vol. 2
System
modus Normal Alarm
Standby
Drifts
modus Start Stopp
Styre modus Manuell Analog Puls Timer Batch
Bit nr. Beskrivelse
2-0
Driftsmodus (brukermodus)
000: Start
001: Stopp
010: –
011: Maks
5-3
Kontrollmodus:
000: Manuell
001: Puls
010: Analog
011: Timer
100: Batch
6Anti-kavitasjon:
0: Deaktivert
1: Aktivert
7+Auto restart etter alarm
0: Deaktivert
1: Aktivert
Bit nr. Beskrivelse
6Watchdog funksjonen:
0: Deaktivert
1: Aktivert
Bit nr. Beskrivelse
2-0
System modus:
000: Normal
011: Bestå
100: Alarm Standby
3Aktiv alarm:
0: Ingen alarm
1: Alarm
5Kalibrerings modus:
0: Deaktivert
1: Aktivert
6Utlufting:
0: Deaktivert
1: Aktivert
Bit nr. Beskrivelse
1-0 Ekstern stopp:
01: Normalt åpen
10: Normalt lukket
3-2
Nivå modus:
00: Overvåkingsfunksjon*
01: Normalt åpen
10: Normalt lukket
6-4
Analoge modus:
000: 4-20 mA
001: 20-4 mA
010: 0-20 mA
011: 20-0 mA
7-
Bit nr. Beskrivelse
0Membran inngang:
0: Normalt åpen
1: Normalt lukket
1Overvåkingsinngang:
0: Deaktivert
1: Aktivert
Bit nr. Beskrivelse
1-0 Enhet i displayet:
00: Metrisk (liter)
01: Amerikansk (gallon)

Norsk (NO)
15
12. Anti-kavitasjon
Tabellene nedenfor angir hvor informasjon om data for hastig-
hetsreduksjon for a unngå kavitasjon lagres.
Viktig:
• Kun DME (60-940 l/h).
• Husk å aktivere anti-kavitasjon, see kapittel 9. Driftsmodus for
DME for mer informasjon.
13. Status på pumpenes lysdioder.
Med led_contr som beskrevet nedenfor kan man forespørre på
status på pumpens lysdioder.
Bemerk at relestatusen følger diodens PÅ status.
Ved å bruke 'NC' kobling på releet betyr det at aktiv tilsvarer et
åpent rele.
Ved å bruke 'NO' kobling på releet betyr det at aktiv tilsvarer et
lukket rele.
led_conrt (I,44) - lysdiodevisning
* Tilleggsfunksjon, ikke tilgjengelig på DME2-48 pumper med
PROFIBUS
Tolking av lysdioder og status på alarmreleet.
Bemerk at relestatusen følger diodens PÅ status.
Ved å bruke 'NC' kobling på releet betyr det at aktiv tilsvarer et
åpent rele.
Ved å bruke 'NO' kobling på releet betyr det at aktiv tilsvarer et
lukket rele.
14. Alarm status
alarm_code (I,59)
Alarmer er lagret i alarm_code. Alle alarmer setter DME pumpen i
Alarm Standby modus.
I dette moduset slukkes den grønne lysdioden og den røde lys-
dioden tennes. Verdien på alarm_code ligger inne og oppdateres
ikke (slettes) før en omstart forsøkes gjennomført. Pumpen fore-
tar en automatisk omstart hvis årsaken til alarmen blir borte. Den
aktuelle alarm_code vil da slettes og den grønne lysdioden ten-
nes igjen.
Tabellen nedenfor viser hvilke alarmer som støttes:
+Kun DME (60-940 l/h)
*Ikke konfigurerbar på DME (2-48 l/h), satt fast til "Ja"
**Generert av PROFIBUS modulen
•act_mode3, bit 0-2, (se kapittel 9.) inneholder informasjon om
pumpen er i Alarm Standby eller ikke og
•act_mode3, bit 3 inneholder informasjon om det er aktive alar-
mer som ikke er kvittert ut.
reset_alarm vil kvittere ut (fjerne) alle alarmer som kan slettes.
alarm_code_disp (I,57)
Disse dataene er identiske med alarm_code.
warning_code (I,58)
Advarseler lagres i warning_code. En advarsel fører ikke til for-
andring i driften til DME pumpen, men både den røde og grønne
lysdioden tennes. Når årsaken til advarselen fjernes, slettes
koden som indikerer advarsel.
Tabellen nedenfor viser advarsler som støttes:
+Kun DME (60-940 l/h)
Bit nr. Beskrivelse
2-0
Kapasitetsreduksjon:
000: Maks kapasitet redusert til 75 %
001: Maks kapasitet redusert til 50 %
010: Maks kapasitet redusert til 25 %
Bit nr. Beskrivelse
1-0
00: Lysdiode 1 (grønn) av
01: Lysdiode 1 (grønn) på
10: Lysdiode 1 (grønn) blinker
11: –
3-2
00: Lysdiode 2 (rød) av
01: Lysdiode 2 (rød) på
10: Lysdiode 2 (rød) blinker
11: –
Grønn
lysdiode Rød
lysdiode Årsak Alarm
rele*
Av Av Strømforsyning slåttt av eller
feil i strømforsyning –
På Av System modus Normal,
driftsmodus Start –
Blinker Av System modus Normal,
driftsmodus Stopp –
På På
Systemmodus Bestå,
driftsmodus Start
(pumpen fortsetter å dosere til
tross for advarslen)
Aktiv
Blinker På Systemmodus Bestå,
driftsmodus Stopp Aktiv
Av På Systemmodus Alarm Standby Aktiv
Kode Alarmårsak Automatisk omstart Beskrivelse/handling
19+Membranlekkasje Nei Alarmen må alltid kvitteres ut med en reset_alarm kommando som i til-
legg nullstiller bitet som gir alarmen.
48+Overlast (maksimalt trykk
overskredet)
57 Tørrkjøring (lavt væskenivå) Konfigurerbar* Kan konfigureres til "Enabled" (aktiv) eller "Disabled" (inaktiv) på
DME (60-940 l/h).
64 For høy temperatur
76** Intern kommunikasjonsfeil Ja PROFIBUS modulen sletter alltid alarmen når kommunikasjonen er
gjenopprettet med DME pumpen. Reset-alarm kommandoen nullstiller
aktuelle alarm bits.
83 Feil i godkjennelse av para-
meterområdet (EEPROM) Pumpe stoppet Alarmen kan ikke fjernes. DME pumpen må slåes av og på igjen.
88 Sensor feil (analog inngang) Ja Alarmen slettes alltid av DMEpumpens automatiske restartsfunksjon.
Reset-alarm kommandoen nullstiller aktuelle alarm bits.
154+Feil på displayet
174+Origosensor feil Pumpe stoppet Alarmen kan ikke fjernes. DME pumpen må slåes av og på igjen.
173+Hallsensor feil
Kode Årsak til advarsel
17 Maks mengde
(overskredet maks kapasitet i pulsmodus)
48+Overlast (maksimalt trykk overskredet)
57 Lavt væskenivå
59 Ingen væskestrøm

Norsk (NO)
16
15. Doseringsstyring
Figur 4 viser parametrene som brukes i de fem forskjellige styre-
metodene. For alle styremetoder vil parameter max_dosing_flow
begrense den faktiske verdien til denne verdien.
For styremodus Manuell er det ikke mulig å velge en høyere verdi
enn denne begrensningen.
Fig. 4 De fem styremodusene og parametrene som brukes til
å angi den aktuelle kapasiteten.
16. Kommandoer (utganger)
Med modulen som heter "Commands Buffer" i GSD filen er det
mulig å bruke 8 definerte utgangsbytes i modulen til å sende
kommandoer til DME doseringspumpen.
Kommandoen "Commands Buffer" er obligatorisk og den første
modulen man setter opp når man konfigurerer en DME PROFI-
BUS slave på nettverket.
Det første bytet brukes til å anngi kommandoen og de 3 neste
bytene er til fremtidig bruk ("likegyldige" foreløpig). De neste
4 bytene brukesfor å representere data som kan være fra 8 til
32 bits. Noen kommandorer har ingen data og verdien på de
4 databytene er "likegyldige".
Eksempel 1
For å starte må DME doseringspumpen motta kommandoen
3 (0x03).
De 8 utgangskommandoene vil se slik ut for å starte pumpen:
Eksempel 2
Volum som doseres pr puls skal settes til
0,975 ml/p 975 000 nl/p.
Dataformatet for volum som doseres pr puls er i et 32 bit datafor-
mat, dvs 975 000 er 00 0E 98 skrevet som et heksadesimalt tall.
Kommandoen for å sette volumet pr puls ved pulsdosering er
kommando nummer 17 (0x11).
De 8 utgangskommandoene vill se slik ut for å sette volumet pr
puls til 0,975 ml/p:
Eksempel 3
Timer dosering perioden skal settes til 1 dag, 2 timer og 45 minut-
ter.
Dataformatet for perioden på timer dosering er i et 16 bits datafor-
mat, dvs 1 dag, 2 timer og 45 minutter er 1605 minutter eller
00 00 06 45 skrevet som et hekasdesimalt tall.
Kommandoen for å sette perioden for timer dosering er kom-
mando nummer 20 (0x14).
De 8 utgangskommandoene vil se slik ut for å sette timer dose-
ringsperioden til 1 dag, 2 timer og 45 minutter:
For å bekrefte at kommandoen er utført av DME doseringspum-
pen returneres kommandoen fra DME doseringspumpen til PRO-
FIBUS masteren med kommandoen "Command _Ack" funksjonen
som defineres med 1 bytesom mottas av pumpen i GSD filen.
Hvis kommandoen utføres uten feil blir koden til kommandoen
returnert i command_ack.
Hvis kommandoen av en eller annen grunn ikke kan utføres (f.eks
feil ved pumpen) returneres verdien 0xFF i command_ack. Mas-
teren må da sende en blank kommando (0x00) eller en annen
komando før den sender kommandoen som feilet på nytt.
Viktig: For å få tilgang til denne kvitteringsfunksjonen må man
legge til "Command Ack" modulen i parameteroppsettet når man
konfigurerer DME PROFIBUS som slave på nettverket.
Eksempel 1 uten feil
For å stoppe må DME doseringspumpen motta kommandoen
4 (0x04).
De 8 utgangskommandoene vil se slik ut for å stoppe pumpen:
Data_Exchange flyten vil se slik utfor den første pakken og
command_ack:
Eksempel 2 med feil
For å stoppe må DME doseringspumpen motta kommandoen 4
(0x04).
De 8 pakkene vil se slik ut for å stoppe pumpen:
Data_Exchange flyten vil se slik ut for den første utgangskom-
mandoen og command_ack:
TM02 1726 2001
0x03 0x00 0x00 0x00 0x00 0x00 0x00 0x00
0x11 0x00 0x00 0x00 0x00 0x0E 0xE0 0x98
0x14 0x00 0x00 0x00 0x06 0x45 0x00 0x00
Kapasitet
0x04 0x00 0x00 0x00 0x00 0x00 0x00 0x00
Syklus nr. Utgangskommando 0 Command_ack (I,0)
10x00 0x00
20x04 0x00
30x04 0x04
0x04 0x00 0x00 0x00 0x00 0x00 0x00 0x00
Syklus nr. Kommando pakke 0 Command_ack (I,0)
10x00 0x00
20x04 0x00
3 0x04 0xFF
4 0x00 0xFF
50x00 0x00
60x04 0x00
70x04 0x04

Norsk (NO)
17
16.1 Oversikt over PROFIBUS kommandoer
* Kun DME (60-940 l/h)
Identifikasjonsnavn Kom-
mando Dataelement Beskrivelse
RESET_ALARM 1 Uvesentlig Nullstiller en mulig aktuell alarm.
FACT_BOOT 2 Uvesentlig Alle oppsettsparametre tilbakestilles til fabrikksinnstillingene.
START 3 Uvesentlig Starter pumpen (driftsmodus Start).
Oppdaterer act_mode1 bit 0-2 i henhold.
STOP 4 Uvesentlig Stopper pumpen (driftsmodus Stopp).
Oppdaterer act_mode1 bit 0-2 i henhold.
MANUAL 5 Uvesentlig
Setter pumpen til driftsmodus Manuell dosering.
Doseringssettpunktet man_dosing-flow kan nå justeres med
+ og - knappene og fra PROFIBUS med bus_dosing_flow.
Oppdaterer act_mode1 bit 3-5 i henhold.
PULSE 6 Uvesentlig
Setter pumpen til driftsmodus Puls dosering.
Pumpen vil dosere pulse_dosing_volume for hvert elektriske pulssignal den
mottar.
Oppdaterer act_mode1 bit 3-5 i henhold.
ANALOG 7 Uvesentlig
Setter pumpen til driftsmodus Analog dosering.
Doseringssettpunktet (mengden) kan nå justeres via den analoge inngangen.
(4-20 mA).
Oppdaterer act_mode1 bit 3-5 i henhold.
TIMER 8 Uvesentlig Setter pumpen til driftsmodus Timer dosering.
Pumpen vil dosere timer_dosing-volume hver timer_dosing_period.
Oppdaterer act_mode1 bit 3-5 i henhold.
BATCH 9 Uvesentlig
Setter pumpen til driftsmodus Batch dosering.
Pumpen vil dosere batch_dosing_volume med maks kapasitet for hvert elek-
triske pulssignal den mottar.
Oppdaterer act_mode1 bit 3-5 i henhold.
ANTI_CAVITATE_E 10 Uvesentlig Aktiverer DME pumpens anti-kavitasjon funksjon (forlenget sugeslag).
ANTI_CAVITATE_D 11 Uvesentlig Deaktiverer DME pumpens anti-kavitasjon funksjon.
DOSE_BATCH 12 Uvesentlig Pumpen doserer en batch i driftsmodus Batch dosering.
START_BLEED 13 Uvesentlig Pumpen starter lufting (tilsvarer å trykke 100 % knappen).
STOP_BLEED 14 Uvesentlig Pumpen stopper lufting (tilsvarer å slippe 100 % knappen).
LOCK_KEYS 15 Uvesentlig Låser + og - knappene på pumpen.
UNLOCK_KEYS 16 Uvesentlig Låser opp + og - knappene på pumpen.
PULSE_DOSING_VOLUME 17 hi, lo1, lo2,
lo3 Setter volumet som doseres i driftsmodus Puls dosering.
BATCH_DOSING_VOLUME 18 hi, lo1, lo2,
lo3 Setter volumet som doseres i driftsmodus Batch dosering.
TIMER_DOSING_VOLUME 19 hi, lo1, lo2,
lo3 Setter volumet som doseres i driftsmodus Timer dosering.
TIMER_DOSING_PERIOD 20 hi, lo Setter tidsintervallet mellom dosering i driftsmodus Timer dosering.
TIMER_DOSING_START 21 hi, lo Setter startstidspunktet for den første doseringen i driftsmodus Timer dose-
ring.
MAX_DOSING_FLOW 22 hi, lo1, lo2,
lo3 Setter pumpens maksimale tillatte mengde.
CALIBRATION_VOLUME 23 hi, lo1, lo2,
lo3 Setter kalibreringsvolumet til pumpen.
LANGUAGE 24 hi Setter språket som brukes i menyene.
BUS_DOSING_FLOW 25 hi, lo1, lo2,
lo3 Setter mengden som doseres i driftsmodus Manuell dosering.
COMM_WATCH_E 26 Uvesentlig Aktiverer communication watchdog som stopper pumpen hvis kommunika-
sjonen feiler.
COMM_WATCH_D 27 Uvesentlig Deaktiverer communication watchdog.
AUTO_RESTART_E+28 Uvesentlig Aktiverer automatisk restart etter alarm.
AUTO_RESTART_D+29 Uvesentlig Deaktiverer automatisk restart etter alarm.
INPUT_SETUP1+30 hi Oppsett av inndata 1, se kapittel 10.
SCALING_SETUP+31 hi Oppsett av enheter, se kapiitel 11.
ANTI_CAVI_SETUP+32 hi Oppsett av anti-kavitasjon funksjonen, se kapittel 12.
INPUT_SETUP2+33 hi Oppsett av inndata 2, se kapittel 10.

Norsk (NO)
18
17. Oversikt over dataelementer (innsignaler)
Forkortelser som er brukt:
Tabellen viser alle mulige inndata (parametere) i bytes fra DME
pumpen.
Hver parameter er definert som en modul i GSD filen.
Modulene inneholder 1 til 4 bytes med inndata avhengig av stør-
relsen på den aktuelle parameteren. Hver modul inneholder også
en definisjon av 4 brukerdefinerte parametere som er det aktuelle
inndata nummeret i henhold til tabellen nednfor. Det er derfor
mulig å legge til modulene i tilfeldig rekkefølge.
Fordelen med å definere hver parameter som en egen modul i
GSDfilen er at PROFIBUS nettverket kun trenger å lese de inn-
signalene som er derfinert i modulene som er lagt til av nettverks-
ansvarlig. For eksempel er det ikke nødvendig å lese timer-
dosing_volum som bruker 4 bytes med informasjon hvis pumpen
kun skal kjøres i manuell driftsmodus.
Eksempel
Modulen "Puls Doserings Volum" defineres med 4 bytes innsigna-
ler som inneholder:
• pulse_dosing_volume_hi
• pulse_dosing_volume_lo1
•pulse_dosing_volume_lo2
•pulse_dosing_volume_lo3
hvor puls_dosing_volume_hi er den høyest rangerte byten og
puls_dosing_lo3 den lavest rangerte byten.
unsca.: Dataelementet er uskalert
(f.eks et nummer, en teller e.l.).
lo: Dette er det laveste bytet for en 16/32 bits enhet.
Skaleres fra høy til lav.
bits: Dataenheten tolkes som bit. Tolkingen er forklart i
de neste avsnittene.
<unit>: Dataeneheten har denne enheten (unit) (med en
mulig faktor eller prefiks) og enhetens skalering.
Nr. Paramenter
navn
Byte
range-
ring Parameter beskrivelse Skalering Fabrikksinnstilling Område
For-
andres
under
drift
Omreg-
nings
kode
Data
type
0Kommando
Bekreftelse Kommandoen returneres
som en bekreftelse Ja 0 5
1Puls
Doserings
Volum
Hi Doseringsvolum som
brukes i driftsmodus
Pulsdosering 1 nl/P Ja 0 7
2Lo1
3Lo2
4Lo3
5Batch
Dosering
Volum
Hi Doseringsvolum som
brukes i driftsmodus
Batchdosering 0,1 ml Ja –3 7
6Lo1
7Lo2
8Lo3
9Timer
Doserings
Volum
Hi Doseringsvolum som
brukes i driftsmodus
Timerdosering 0,1 ml Ja –3 7
10 Lo1
11 Lo2
12 Lo3
13 Timer
Doserings
Periode
Hi Doseringsperioden som
brukes i driftsmodus
Timerdosering 1 minutt Ja 0 6
14 Lo
15 Timer
Dosering Start
Hi Tidspunktet for start av
dosering som brukes i drifts-
modus Timerdosering 1 minutt Ja 0 6
16 Lo
17 Maks Dose-
ringsmengde
Hi Makimal tillatt mengde som
doseres 0,1 ml/h Ja –3 7
18 Lo1
19 Lo2
20 Lo3
21 Kaliberings-
volum
Hi Verdi som bukes når
pumpen kalibreres 0,1 ml Setabell
neden-
for Ja –3 7
22 Lo1
23 Lo2
24 Lo3
25 Språk
Kode for språk i displayet:
0: Engelsk 0-13 Ja 0 5
0: Engelsk
1: Tysk
2: Fransk
3: Tysk
4: Spansk
5: Italiensk
6: Portugisisk
7: Dansk
8: Svensk
9: Finsk
10: Tsjekkisk
11: Slovakisk
12: Polsk
13: Russisk

Norsk (NO)
19
26 Bussdosert
Mengde
Hi Doseringsmengde valgt fra
PROFIBUS 0,1 ml/h Setabell
neden-
for Ja –3 7
27 Lo1
28 Lo2
29 Lo3
30 Timer Hi To-timers teller 2 timer 0-65535 Ja 0 6
31 Lo
32 Temperatur Temperatur i motor/pumpen 1 °C 0-90 Ja 0 2
33 Manuell Dose-
rings Mengde
Hi Doseringsmengde når
pumpen kjører i driftsmo-
dus Manuell dosering 0,1 ml/h Ja –3 7
34 Lo1
35 Lo2
36 Lo3
37 Aktuell Dose-
rings Mengde
Hi Aktuell dosert mengde,
uansett driftsmodus. 0,1 ml/h Ja –3 7
38 Lo1
39 Lo2
40 Lo3
41 Maks Mengde
Pumpe Hi Maksimal mengde for
pumpen 0,5 l/h
DME 2-18: 5
Låst Nei 0 6
DME 4-15: 8
DME 8-10: 15
DME 12-6: 24
DME 19-6: 37
DME 48-3: 96
DME 60-10: 120
DME 150-4: 300
DME 375-10: 752
DME 940-4: 1280
42 Lo
43 Maks Pumpe
trykk Maks trykk ut fra pumpen
(høyde) 0,1 bar
DME 2-18: 180
Låst Nei –1 5
DME 4-15: 150
DME 8-10: 100
DME 12-6: 60
DME 19-6: 62
DME 48-3: 26
DME 60-10: 100
DME 150-4: 40
DME 375-10: 100
DME 940-4: 40
44 LED Kontroll Status på grønne og røde
lysdioder
Hvis ingen alarm:
Bits 1-0: Grønn lysdiode
10: Blinker
Bits 3-2: Rød lysdiode
00: Av
8 bits Ja 0 5
45 Strøm På
Teller Hi Antall ganger pumpen er
slått på. 1 0-65535 Ja 0 6
46
Slag Teller
Lo
Anall doseringsslag pum-
pen har gjort 10-
999.999.
999 Ja 0 7
47 Hi
48 Lo1
49 Lo2
50 Lo3
51 Analog
Inngang
Hi Verdi fra den analoge inn-
gangen
0-20 mA:
4,9 uA Hvis det ikke er noe signal
inn vill bitet ha verdien 0 0-4095 Ja 0 6
52 Lo 4-20 mA:
3,9 uA
53 Digitale
Innganger
Logisk verdi på digitale
nivåinnganger:
Bit 0: Nivå alarminngang
Bit 1: Nivå advarselinngang
Bit 2: Ekstern stopp inn-
gang+
Bit 3: Overvåking inngang+
Bit 4: Lekkasje/membran
inngang+
Bit 5: Puls inngang+
Hvis det ikke er noe
signal inn vill bitet ha
verdien 0 8 bits Ja 0 5
Nr. Paramenter
navn
Byte
range-
ring Parameter beskrivelse Skalering Fabrikksinnstilling Område
For-
andres
under
drift
Omreg-
nings
kode
Data
type

Norsk (NO)
20
* Kun DME (2-48 l/h)
+Kun DME (60-940 l/h).
54 Aktuell Status
1Faktiske verdier status nr. 1
Bits 2-0: Driftsmodus:
001: Stopp
Bits 5-3: Kontrollmodus:
000: Manuell dosering
Bit 6: Anti-kavitasjon:
0: Deaktivert
Bit 7: Auto restart etter
alarm
0: Deaktivert
8 bits Ja 0 5
55 Aktuell Status
2Faktiske verdier status nr. 2
Bit 5: Status taster:
0: Ulåst
Bit 6: Watchdog funksjo-
nen:
0: Deaktivert
8 bits Ja 0 5
56 Aktuell Status
3Faktiske verdier status nr. 3
Hvis ingen alarm:
Bits 2-0: System modus:
000: Normal
Bit 3: Aktiv alarm:
0: Ingen alarm
Bit 5: Kalibrerings modus:
0: Deaktivert
Bit 6: Utlufting
0: Deaktivert
8 bits Ja 0 5
57 Alarm Kode
Disp Identisk med alarm kode Hvis ingen alarm:
00-255 Ja 0 5
58 Advarsel Kode Aktuell advarselkode Hvis ingen advarsel:
00-255 Ja 0 5
59 Alarm Kode Aktuell alarmkode Hvis ingen alarm:
00-255 Ja 0 5
60 DME SW
Versjon DME software versjon 160 0-255 Nei –2 5
61 PROFIBUS
SW versjon PROFIBUS software
versjon 140 0-255 Nei –2 5
62 Innsignal
Oppsett 1* Oppsett av innsignaler
Bits 1-0: Ekstern stopp:
01: Normalt åpen
Bits 3-2: Nivåmodus:
01: Normalt åpen
Bits 6-4: Analog modus:
000: 4-20 mA
8 bits Ja 0 5
63 Skalering
Oppsett Enhet som vises i displayet
til DME Bits 1-0: Enhet i displayet:
00: Metrisk (liter) 8 bits Ja 0 5
64 Anti-Kavita-
sjon Oppsett+Oppsett av antikavitasjons-
funksjonen
Bits 2-0: Kapasitetsreduk-
sjon:
000: 0 (maks kapasitet
redusert til 75%)
8 bits Ja 0 5
65 Innsignal Opp-
sett 2+Oppsett av innsignaler
Bit 0: Membran inngang:
0: Normalt åpen
Bit 1: Overvåkingsinn-
gang:
0: Deaktivert
8 bits Ja 0 5
Nr. Paramenter
navn
Byte
range-
ring Parameter beskrivelse Skalering Fabrikksinnstilling Område
For-
andres
under
drift
Omreg-
nings
kode
Data
type
This manual suits for next models
9
Table of contents
Languages: