Hallowell Acadia 024 User manual

Hallowell International 110 Hildreth Street, Bangor, ME 04401
t:(207) 990.5600 --- f:(207) 990.5602 --- info@gotohallowell.com --- www.gotohallowell.com
Last Revised 03.25.09
50‐00394‐E

CONTENTS
1
InstallationChecklist3
SafetyConsiderations6
InstallationRecommendations6
Installation 7
Step1–CheckEquipmentandJobSite7
UnpackUnit7
InspectEquipment7
Step2–InstallonSolid,LevelMountingPad7
Step3–ClearanceRequirements7
Step4–CheckIndoorExpansionDeviceandInstallAirHandlingUnit8
AirHandlerInstallation
8
Step5–MakePipingConnections9
RefrigerantTubingandFilterDryer9
PrecautionsDuringLineSetInstallation9
SweatConnection10
LeakTesting10
Evacuation10
FinalTubingCheck11
Step6–MakeElectricalConnections11
RouteGroundandPowerWires11
ConnectGroundandPowerWires11
RouteControlWiring11
ConnectControlWiring11
ConfiguringYourHeatPumpComponents12
FinalWiringCheck12
Step7–ChargeUnitandStartup12
Step8–CheckCharge14
UnitCharge14
HeatingCheckChargeProcedure14
Step9–FinalChecks14
Extras15
HydronicCoilSupplementalHeat15
HallowellControlTimers16
Troubleshooting17
ControlCodeErrors17
HeatingModeOperation18
CoolingModeOperation19
AppendixA–Settings20
Figure1–FactorySuppliedAirHandlerControlBoard20

CONTENTS
2
HallowellTXVKitInstallationInstructions20
Figure2–AirFlowChartforAirHandler21
Figure3–ElectricHeatAirflowTapsforFactorySuppliedAirHandler21
Figure4–ControlJumpers22
Figure5–ThermostatSettings23
ThermostatSettingDescriptions24
AppendixB–WiringDiagrams25
Figure6–LineVoltage25
Figure7–HallowellProprietaryControl26
Figure8–AirHandlingUnit27
Figure9–Thermostat27
Figure10–EntireControl28
AppendixC–AcadiaChargingR410A29
Figure11–HallowellAcadiaChargingChart29
Figure12–Pressure/TemperatureChartR410A30
AppendixD–OutdoorUnitMounting31
Figure13–TypicalUnitMounting31
AppendixE–AcadiaComponents32
Figure14–AcadiaComponents32
AppendixF–EWCZoneControl33
Figure15–EWCZoneControlWiring33
AppendixG–SpecificationSheets34
ContractorCheckList38
DataSheet 39

INSTALLATIONCHECKLIST
3
PleaseCheckorfilloutasCompleted
PIPINGCONNECTIONS
Ensurebothvaporandliquidlinesarefullyinsulatedseparatelywithatleast½”wallinsulation.
Ensuretheliquidlinefilterdrierisinstalledneartheairhandler,andinsulatedaswell.
Ifaverticalriserof10’ormoreispresentonthelineset,thelinesetmustbeproperlytrappedtopreventoil
sluggingtothecompressors;goodpracticeinanyriser.
Whenmakingbrazedconnections,tricklenitrogenthroughthesystem(e.g.2PSI)tomaintaincleanbrazejoints
andeliminatecarbonizationinsidethepipingduringthebrazeprocess.TheAcadiasystemcomespre‐charged
with50PSIofdrynitrogen.Thiscanbeusedfornitrogentricklingbycrackingtheservicevalvesslightly.
AIRHANDLER
Installindoorairhandler,ensuringproperductsealing,insulation&distribution.
Ensureallregisters,supplyandreturn,areopenandunblocked.
Ensureaductflexconnectorisusedtoeliminatevibrationtransmissiontothehome.
Ensureaproperairfilterisinstalledonthereturnsideoftheairhandler.
Ensurecondensatedrainisinstalledproperly,andtrapped.
Run10‐conductor(minimum),18AWGcontrolwiringfromairhandlertothethermostat,andfromairhandler
tooutsidecondenserunit.
Connectcontrolwiringfollowingcolorcodesprovidedintheinstallmanual,AppendixB.
Disconnectthelow‐voltageleadsfromthetransformerprovidedintheairhandlerfromtheairhandlercontrol
board24VACandCommonterminals.Line‐voltageleadstothetransformermustremainconnectedtopower
theECMblowermotor.
Connect24VACand24Cprovidedfromoutdoorunittothe¼”terminalslabeledCOMand24VAContheindoor
AHUcontrolboard(seeninAppendixA,FIG1).
Ensuretheelectricalservicetotheairhandlerisadequateforboththeairhandlerandelectricheatkit,ifoneis
installed,perNECand/orlocalcodes.
Ensureappropriateelectricaldisconnectsizeisinstalled,perNECand/orlocalcodes.
EnsuretheHP/ACjumperontheairhandlercontrolboardissettoHP(HeatPump).
Ifanelectricheatkitisinstalled,ensuretheHEAT/NOHEATJumperontheairhandlercontrolboardissettothe
HEATside.LeavingthisjumperonNOHEATdisablesallauxiliaryheatrelays.
SetairflowjumpersinairhandlerinaccordancewithAppendixA.
THERMOSTAT
Installthermostatinalocationwhereitwillnotbedirectlyexposedtoconditionedairordraftsfromdoors
and/orwindows.
Insulatebetweenthebaseplateofthethermostatandthewalltopreventdraftsfromaffectingthethermostat.
EnsurethatajumperbetweenW2andW/Eisnotinstalledonthethermostat.
EnsurethatajumperbetweenRCandRHisinstalledonthethermostat.
Configurethethermostat’sinstallerconfigurationmenuasindicatedintheinstallationmanual,AppendixA:
‘ThermostatSettings’.

INSTALLATIONCHECKLIST
4
OUTSIDECONDENSERUNIT
EnsureproperclearancesareobservedaroundtheunitinaccordancewithAppendixDintheinstallation
manual,makingsuretoprovideappropriatespaceforaccessibilitytothecompressorcompartment’saccess
panel(30inchesminimum).
Ensurecondenserisplacedonappropriatesnowstands(notblocks,sleepers,etc.)perclimateregionwitha
minimumof12”clearancetoground.
Ensureoutdoorunitislevel.
Ensuretheoutdoorcoil’sdrainageholesarenotobstructed,providingfulldrainagerunoffduringthedefrost
cycles.
Checkfactorytubingtoensuretubesarenotrubbingagainsteachotheroranysheetmetal.Paycloseattention
todistributortubesonbothindoorandoutdoorcoils.
Ensuretransformeriswiredappropriatelyforappliedlinevoltage.Forcorrectwiring,seeLineVoltagediagram
inAppendixB.Unitisfactorywiredfor230VAC.
Ensurethe10conductor,18AWGcontrolharnesshasbeencorrectlywiredbetweenthethermostat,indoorair
handler,andoutdoorunit,followingcolorcodesandschematicsprovidedinAppendixB.
Ensuretheelectricaldisconnectisproperlysizedfortheoutdoorunit,perNECand/orlocalcodes.
Ensureallelectricalconnectionsareweathertight.
Ensureallcabinetandelectricalfastenersaresecure.Shippingvibrationcanloosenconnections.
Ensurecontrolwiringisnotchaffing/grommetisinstalled.
ChargingtheSystem
Ensurebothvaporandliquidservicevalvesareopenandback‐seated.
Ensuresystemhasbeenproperlyevacuatedtoatleast500microns.Atripleevacuationisthepreferredmethod
foracleaninstallation.
EnsuretheR‐410AINITIALCHARGEisweighedinasaliquidthroughthe3/8”servicevalveportinsidethe
compressorcompartment.FINALCHARGE(ifrequired)istobeweighedinthroughthe¼”chargingportonthe
outsideoftheunitwhilethesystemisoperating(thisportisalwaysreadingthelowpressuresideofthe
system).Thevaporservicevalveportishigh‐pressuregasduringheatingoperationandlow‐pressuregasduring
coolingoperation.
Chargingoperationsshouldalwaysbeperformedinheatingmode.Iftheunitmustbechargedincoolingmode,a
returntripmayberequiredtocheckthechargeduringheatingseason.
Totalchargeamountisdependentonthetotallengthoftheliquidline.SeetheLineSetChargingChartin
AppendixC.

INSTALLATIONCHECKLIST
5
SystemStartupandCheckout
EnsuretheaccesscovertotheairhandlerisinplacetoestablishproperairflowacrosstheindoorA‐coilwhile
thesystemisoperating.
Afterapplyingpower,ensureelectricalvoltageratingsarewithinspecifications.Ifthevoltageisoutsideof
specification,contactyourlocalutilitycompany.
Verifycontrolboardheartbeatisactive,andnoerrorconditionsarepresent.
Obtainanaccuratemeasurementoftheoutdoortemperatureattheoutdoorunit.
Measureliquidlinetemperaturebyattachingandinsulatinganaccuratethermistortypeorelectronic
thermometertothe3/8”liquidlineneartheoutdoorcoil.
PlacethesystemintoaStage2heatingcall(24VonY2terminalatoutdoorunit).Aminimumanti‐shortcycle
timerof5minuteswillelapsebeforeanycompressoroperationispermittedbythecontrolboard.
Operatetheunitforaminimumof30minutesbeforecheckingcharge.
MeasureliquidservicevalvepressurebyattachinganaccurateR410Aratedgaugetothe3/8”serviceport.
RefertoAppendixC‘ChargingChart’forrequiredsubcoolingtemperatures.
Forevery1lbofadditionalrefrigerantadded,allowasufficienttimeforthesystemtosettlebefore
takinganothersubcoolingindication.
Completetheservicestickerontheelectricalboxcoverduringinstallation.
IMPORTANT:Beforeleavingthejob,besuretodothefollowing:
Ensurethatallwiringandtubingissecureinunitbeforeaddingpanelsandcovers.Securelyfastenall
panels/coversandensureallfastenersremaintight.
Tightenservicevalvestemcapsto1/12‐turnpastfingertight.
LeaveOwner’sManualwithowner.Explainsystemoperationandperiodicmaintenancerequirements
outlinedinmanual.
Gooverowner’schecklistwiththenewAcadiaowner.
FillouttheDealerInstallationChecklistandplaceincustomerfile.
FillouttheinstallationdatasheetonthelastpageandmailorfaxittoHallowellInternational.

SAFETY
6
SAFETYCONSIDERATIONS
Improperinstallation,adjustment,alteration,service,
maintenance,orusecancauseexplosion,fire,electrical
shock,orotherconditionswhichmaycausedeath,personal
injury,orpropertydamage.
Consultaqualifiedinstaller,serviceagency,oryourdistribu‐
torformoreinformation,orassistance.Thequalifiedinstaller
oragencymustusefactory‐authorizedkitsoraccessories
whenmodifyingthisproduct.Refertotheindividualinstruc‐
tionspackagedwiththekitsoraccessorieswheninstalling.
Followallsafetycodes.Wearsafetyglasses,protectivecloth‐
ing,andworkgloves.
Usequenchingclothforbrazingoperationstoprotectsystem
components.
Havefireextinguisheravailable.Readtheseinstructionsthor‐
oughlyandfollowallwarningsorcautionsincludedinlitera‐
tureandattachedtotheunit.Consultlocalbuildingcodes
andNationalElectricalCode(NEC)forspecialrequirements.
Recognizesafetyinformation,symbolsandwords:
(DANGER) Identifies serious hazards which will
result in severe personal injury or death.
(CAUTION) Identifies unsafe practices which would
result in minor personal injury or product and
property damage.
(NOTE) is used to highlight suggestions which will
result in enhanced installation, reliability, or
operation.
INSTALLATIONRECOMMENDATIONSNOTES
1.) Positionunitawayfromwindows,patios,decks,etc.
wheretheunit’soperationalsoundmaydisturb
customer.
2.) Ensurethatvaporandliquidtubediametersare
appropriatetocapacityofunitandthatbothlinesare
wellinsulated.
3.) Runrefrigeranttubesasdirectlyaspossiblebyavoiding
unnecessaryturnsandbends,keepingtubestheshortest
lengthpossibletoreducerefrigerantchargeamountand
increaseefficiency.
4.) Whenpassingrefrigeranttubesthroughthewall,sealthe
openingwithRTVorotherpliablesilicon‐basedcaulkand
insulate.
5.) Installfilterdryerindoorsatairhandlerandinsulate.
6.) Insureunitisplacedawayfromroofendswhererain,ice,
snow,whereiciclesmayform,oranyotherdebrismay
fallontopof,anddamageunit.
7.) Besuretoaddanoiltraptothevaporlineforevery10ft
ofverticalrise.
8.) Avoiddirecttubingcontactwithwaterpipes,ductwork,
floorjoists,wallstuds,floors,walls,brick,orother
constructionmaterial.
9.) Donotsuspendrefrigeranttubingfromjoistsandstuds
witharigidwireorstrapwhichmaycomeindirect
contactwithtubing.
10.) Whennecessary,usehangerstrapswhichconformto
shapeoftubinginsulation.
11.) Isolatehangerstrapsfrominsulationbyusingmetal
sleevesbenttoconformtoshapeofinsulation.
12.) Insulateboththevaporlineandtheliquidlines
separatelysobothwillhavetheirowninsulation.The
Acadiautilizesthewasteheatonthe3/8”liquidlineat
lowertemperatures.Thatiswhywemustinsulate.
13.) Ifthelinesetisroutedontheexteriorofthehome,be
suretoaddadditionalinsulationtoboththeliquidand
vaporlinestominimizethermallossesfromthelineset.
(Note:Exteriorlinesetsmayhavehighthermallosses
thatcanreducesystemcapacityandefficiency.)
14.) Ensurethattubinginsulationispliable,sealedwithtape
orglueandcompletelysurroundstheVapor,andthe
Liquidtubesseparately.
15.) Maximumlinesetlengthis50ft;consultfactoryifother.
16.) Maximumverticalrise10ft;consultfactoryifother.
IMPORTANT:Maximumliquid‐linesizeis3/8–inO.D.forall
residentialapplications.The3/8‐inliquidlinemustbe
insulatedindependentlyfromthevaporlineinsulation.
(CAUTION) USE ONLY R410A RATED SERVICE
EQUIPMENT
Onlyinstallthefactory‐suppliedheatpump(bi‐flow)liquid
linefilterdrierontheliquidlineattheindoorunit.
Installationofthefilterdryerinsideistohelppreventheat
lossduringheatingoperation.Thefilterdriermustbe
insulated.Obtainreplacementbi‐directionalR410Arated
filterdriersfromyourlocalsupplydistributor.

INSTALLATION
7
Step1—CheckEquipmentandJobSite
Outdoorcondenserunitisheavy.Takethenecessary
precautionsanduseappropriateequipmenttomoveand
install.
UNPACKUNIT
Movetofinallocation.Removecarton,takingcarenotto
damageunit.
INSPECTEQUIPMENT
Checkovertheunitforanysignsofshippingdamage.If
shipmentisdamagedorincomplete,fileaclaimwiththe
shipmentcompanyassoonaspossible.
Checktheunitfornitrogenpressureusingapressuregauge.
Theunitshouldhaveachargeof50psi(+/‐10%)ofnitrogen.
Iftheunit’snitrogenchargeislow,orlacksnitrogenpressure,
donotinstalltheunituntilHallowellfactoryserviceis
contacted.
Step2—InstallonaSolid,LevelMountingPad
orFoundationRack
MounttheAcadiaonasolid,level,foundationpadwith
propersub‐baseanddrainagetoensuretheunitwillnotshift
duringitslifetime.
SeeAppendixD,Figure13forappropriatemounting
configurationsoftheoutdoorunit.
ELEVATEUNIT
NOTE:Accumulationofwaterandiceinbasepanmay
causeequipmentdamage.Elevateunitperlocalclimateand
coderequirementstoprovideclearanceaboveestimated
snowfalllevelandensureadequatedrainageoftheunit.
UseonlyHallowellApprovedsnowstandsinareaswhere
prolongedfreezingtemperaturesareencountered.Ensure
thatoutdoorcoildrainageholesarenotobstructedbysnow
stand.Ensurethemountingpadwillnotshiftorswellfrom
seasonalfrostheaves.
Theunitmustbeplacedonasecure,andlevelmounting
padorracktopreventmovementduetofrostorice
build‐upandtoallowforpropersystemdrainage.
Theunitmustbesetabovetheaveragesnowfalllinein
theareaofinstallation.
Duetoicingontheoutdoorcoil,unitmustbemounted
sothatrunoffofwaterduringdefrostwillnotcausea
safetyproblemwhenwaterrefreezes.Note:Donotset
unitsothatdefrostcondensatewillrunacrosssidewalk.
Ensuretheunitisnotplaceddirectlyunderroofdrains,
eaves,orunderroofpitcheswhererain,ice,orfalling
snowmayfallonanddamageunit.
UnitmustbemountedonHallowellApprovedsnow
standstoallowwatertodrain‐outduringadefrostcycle,
andsothaticebuildupwillnotinterferewithunit
operation.
Besurethatthemountingofthesnowlegsareonthe
supportrailsofthesystemandnotonthebasepansoit
willallowthewatertodrainoutoftheunitduring
defrost.
CAUTION: Donotblockdrainageholesunderoutdoor
coil.Icebuildupwilldamagecoil.
CAUTION: DonotallowPOElubricanttocomeinto
contactwithroofingmaterial.POEmaydeterioratecertain
typesofsyntheticroofing.
NOTE:Onrooftopapplications,mountonlevelplatformor
frame.Placeunitaboveaload‐bearingwallandisolateunit
andtubingsetfromstructure.Arrangesupportingmembers
toadequatelysupportunitandminimizetransmissionof
vibrationtobuilding.ConsultlocalCodesgoverningrooftop
applications.
NOTE:Unitmustbeleveltowithin±2°.
Step3—ClearanceRequirements
Wheninstalling,allowsufficientspaceforairflow,
clearance,wiring,refrigerantpiping,andservice.
Allowatleast30‐in.ofclearanceattheserviceendof
unit,and48in.aboveunitforproperairflow.
Recommendedclearanceontheremainingsidesis18in
(12inminimum).Unitisnottobeinstalledinanytypeof
enclosedstructure.
Maintainadistanceof36in.betweenunitsinmulti‐unit
applications.
Positiontheunitssothatwater,snow,oricefromroofor
eavescannotfalldirectlyonunit.

INSTALLATION
‐8‐
Coverpipingtoinsurethatsnowandicewillnotdamage
therefrigerantlines,andinsulation.
NOTE:Onrooftopapplications,locateunitatleast12in.
aboveroofsurface.
Figurea‐ClearanceRequirements
Step4—CheckIndoorExpansionDeviceand
InstallinAirHandlingUnit
Forproperunitoperation,reliability,andperformancethe
unitsmustbeinstalledwithabalanceport,bi‐directional
heatpumpTXVspecificallydesignedtooperatewithR‐410A
refrigerant.Donotinstallanairhandlerwithevaporatorcoils
havingcapillarytubeororificemeteringdevices.
AIRHANDLERINSTALLATION
NOTE:Intheeventtheairhandlerwasinstalledpriorto
therestofthesystem,itisrecommendedthatallair
handlersettingsandwiringbedoublecheckedatthispoint.
Airhandlersusedwithmulti‐stageunitsmustbecapableof
operatingwithaminimumof2blowerspeeds.Onvariable
speedunits,ensurejumpersareplacedforrecommendedair
flowrequirements.Allairhandlingunitsmustbeinstalledas
specifiedbythemanufacturer’sinstallationinstructions.
However,thefollowingrecommendationsshouldbe
consideredtominimizenoiseandserviceproblems:
Taketheproperprecautionswhenmountingtheair
handlerfornoiseandvibrationdampening.Useduct
isolatorsonboththesupplyandreturnductsconnecting
totheairhandler.
Ensureallfittingsandbrazejointsareleaktestedbefore
startingthesystem.
Donotrunthesystem/airhandlerfanwhile
constructionisinprogress.
Allductworkmustbeproperlysizedforproperairflow.
Undersizedductswillreducethesystem’sperformance,
resultinginunitdamage,areducedlifeandhigher
operationalcosts.
Ensurethatallairregistersareinthefullyopenposition.
Insulateandsealallductwork.
Ensureductworkdoesnotcomeincontactwith
structuralbuildingmembers.
Utilizeflexconnectionsatthemainductworksupplyand
returntoisolatepotentialvibrationsandnoise.
BesurethefiltercoverisinstalledontheHallowell
matchedairhandler,ensuringeasyaccesstothefilterfor
routinemaintenanceoffilterchange.Anygaps,holes
andjointsshouldbeproperlysealedtopreventair
leakage.
Besurethecondensatedrainorthelinesetdonotblock
accesstothefilterdoor,oranyoftheaccesspanelsof
theairhandler.
IMPORTANT:DuetothehighoutputcapacityoftheAcadia
duringcertainoutdoorambientconditions,aductbypass
maynotbeused.ConsultHallowelltechnicalsupportfor
additionalsupport.
IMPORTANT:Anairfiltermustbeinstalledupstreamofthe
returnsideoftheairhandlersuchthefilteriseasytoaccess
forroutinefilterchanges.
NOTE:Improperinstallationofequipmentmayresultin
undesirablenoiselevelsinlivingarea.

INSTALLATION
‐9‐
TheHallowellMatchedairhandlerscomefromthefactory
withbi‐flowTXVsspecificallydesignedforR‐410A.
Installationisrequired.
IMPORTANT:Ifreplacinganexistinghotairfurnacemake
suretheductworkissizedappropriatelyfortheairflow
neededbytheAcadia,sealedandinsulated.
IMPORTANT:Whenmatchingtheoutdoorunitwiththe
Hallowellfactoryairhandler,anR‐410AratedTXVmustbe
installed.NOOTHERTYPEOFMETERINGDEVICEMAYBE
USED!Contactthefactoryforanyquestionsaboutsizingor
applications.
IMPORTANT:TheTXVshouldbemountedasclosetothe
indoorcoilaspossiblewiththethermalbulbsecurely
mountedandinsulated.
NOTE:WhenyouareusingtheHallowellapprovedair
handlerand/orTXVkitseeAppendixA‐HallowellTXVkit
installationinstructions.
Step5—MakePipingConnections
DANGER:Relievepressureand/orrecoverallrefrigerant
beforesystemrepairorfinalunitdisposaltoavoidpersonal
injuryordeath.
CAUTION: Anoiltrapmustbeinstalledatthebottomof
anyriser.Iftheriserisover10feetcallthefactoryfor
support.
NOTE:Outdoorunitmustbeconnectedtoafactory‐
approvedindoorairhandler.
NOTE:Outdoorunitischargedwithnitrogen.Ifnonitrogen
isrelievedfromoutdoorunit,contactthefactorybefore
goingfurther.Additionalstepsmayberequiredifsystem
haslostfactorynitrogencharge.
Thewholesystem,wheninstalled,mustbeevacuatedto500
micronstoeliminatecontaminationandmoistureinthe
system.
Theseoutdoorunitsarecarefullyevaluatedandlistedwith
specificindoorcoilsandfansforpropersystem
performance,efficiencyandreliability.
REFRIGERANTTUBING&FILTERDRIER
CAUTION: ThefilterdryermustbeaBi‐Flow,Heatpump
R410Atypefilterdryer.
NOTE:Thefilterdryermustbeinstalledattheairhandler
andinsulatedtopreventheatloss.TheAcadiauseswaste
heatofftheliquidline.
Thefilterdryermustbeinstalledintheliquidlineascloseto
theHallowellMatchedairhandingunitaspossible.DONOT
installaliquidlinesightglass.
IMPORTANT:Insulatethefilterdryerwith½inchthick
insulationafterinstallationtohelpretainheatintheliquid
line.
PRECAUTIONSDURINGLINESETINSTALLATION
CAUTION: BesureNitrogenisflowingthroughthesystem
priortoanybrazingforthepreventionofoxidationand
contaminationofthesystem.
CAUTION:SystemusesPOEoilforthecompressor
lubricant.Preventativemeasuresshouldbetakento
minimize/eliminatethepossibilityofatmosphericpressure
enteringthesystem.Useanitrogenpurgetoprevent
ambientairfromenteringthesystemduringpiping
connections.Taketheproperprecautionduringpiping
installation.
NOTE:Boththevaporlineandtheliquidlinemustbe
insulatedseparately.
IMPORTANT:Keeplinesfreeofdebrisandmoisture
EnsurealllinesettubingmeetsR410Arefrigerant
requirements
Installthelineswithasfewbendsaspossible,reducing
90°bendswherepossible.Caremustbetakennotto
damagethecouplings,orkinkthetubing.UseACR,hard
drawncoppertubingwherenoappreciableamountof
bendingaroundobstructionisnecessary.Ifsoftcopper
mustbeused,caremustbetakentoavoidsharpbends
whichmaycausearestriction.
Thelinesshouldbeinstalledsothattheywillnot
obstructserviceaccesstothecoil,airhandlingsystem,or
airfilter.
Caremustalsobetakentoisolatetherefrigerantlinesto
minimizenoisetransmissionandvibrationfromthe
equipmenttothestructure.
Thevaporlinemustbeinsulatedwithaminimumof½”
foamrubberinsulation.Theliquidlinemustalsobe

INSTALLATION
‐10‐
insulatedwithaminimumof½”foamrubberinsulation
separatelyfromthevaporline.
UsePVCorothersuitablepipingasaconduitforall
undergroundinstallations.
Packfiberglassinsulationandasealingmaterialsuchas
permagum,orRTVaroundrefrigerantlineswherethey
penetrateawalltoreducevibrationandtoretain
flexibility.
Useonlylongradius90°foranyharddrawncopper.
SWEATCONNECTION
CAUTION: Purgelinesetswithnitrogenbeforeandwhile
brazingoccurstopreventinternaloxidizingcontaminants
fromenteringthesystemandtoprotectthePOEoil.
1. Runtheline‐setfromtheAirHandlerUnit(AHU)tothe
outdoorunit.Besuretokeeptheendsofthepipe
sealedsonoforeigndebrisormoisturecangetintothe
pipe.
2. Beforebrazing,anitrogenpurgemustbesetuptorun
thenitrogenthroughthe7/8”or3/4”servicevalve.Be
suretoremovetheSchradervalvecorefromboththe
vaporandliquidservicevalves.Setthenitrogenpurgeto
nomorethe2psistanding.
3. Brazingonejointatatime,workyourwayaroundthe
line‐setstartingwiththevaporlineconnectionatthe
outdoorunit.Besuretowraptheservicevalveswith
wetcloths.Thiswillprotecttheservicevalvefrom
overheating.
4. Useindustrystandardbrazingpractices.Useofabrazing
shieldmayberequiredtokeepfromburningtheside
panelofthesystem.
5. AttheAHU,brazethevaporlinetothevaporconnection
ontheAHU.
6. Atthe3/8”liquidlineconnectionontheAHU,inserta
shortpieceof3/8”pipeandbrazeattheAHU.
7. InstalltheLiquidlinefilterdryeronthe3/8”linecoming
outoftheAHUandbrazeinplace.
8. Insertthe3/8”linefromtheline‐setintotheotherend
ofthefilterdryerandbrazeinplace.
9. Thelastbrazejointisattheoutdoorunit’s3/8”
connection.Todothelastbrazejointremovethe
Schradervalvecorefromthe3/8”servicevalve.
10. Wraptheservicevalvewithawetrag,preventingthe
servicevalvefromoverheating.Insertthepipeand
brazeintoplace.Theuseofabrazingshieldmayneedto
beusedtokeepfromburningtheunit.
11. Re‐installtheSchradervalvecoresintothevaporand
liquidservicevalves.
12. Leaktestthelinesetbyadding400psiofnitrogentothe
line‐setandAHUcoil.
13. Thesystemisnowreadyforevacuation.
Openallserviceportsandallflow‐controldevicesoncethe
systemispiped.Donotleavesystemopentoatmosphere.
ThePOEoilinthecompressorsisextremelysusceptibleto
moistureabsorption.Alwayskeeptheendsofthetubing
sealedduringinstallationandfreeofdebris.
LEAKTESTING
Leaktestalljointsontheindoor/outdoorunits,and
refrigeranttubing.Openbothservicevalvesbyturningcenter
stemfullyCCWuntilstemreachesthetopofthevalve.
NOTE:Ensurebothservicevalvesareopenedandnitrogen
purgeisremovedbeforeevacuation.
NOTE:Outdoorunitischargedwithnitrogenthatmustbe
releasedbeforeevacuation.
NOTE:Boththevaporandliquidlinesmustbecompletely
insulatedusingminimum½”wallinsulationseparatelyafter
leaktesting.
EVACUATEREFRIGERANTTUBING,INDOORCOIL,AND
OUTDOORUNIT
Evacuationrequiresavacuumpumpcapableofachievinga
minimumvacuumof500micronsandamicrongaugefor
indication.(Note:Besuremicrongauge,hoses,and
manifoldsetareingoodworkingconditionandleakfree.)
Thevacuummethodisthemosteffectivewayofassuringa
systemisfreeofleaks,airandmoisture.

INSTALLATION
‐11‐
Refrigerantsystemmustbeevacuateddowntoaminimumof
500microns.Once500micronshasbeenreached,the
systemshouldbesealedoffandheldat500micronsfora
minimumof15minutestoperformafreeairtest.
IMPORTANT:Breakanysystemunderavacuumwith
nitrogenpressureforrepairs,preventingambientairfrom
enteringthesystem.
FINALTUBINGCHECK
IMPORTANT:Ensurebothindoorandoutdoorunitshavenot
shiftedduringshipment.Ensuretubesarenotrubbingagainst
eachotheroranysheetmetal.Paycloseattentionto
distributortubesandserviceportstems.Checkinsulationon
vaporandliquidlines,andmakesureitissealedproperly
withtapeorglue.
Step6–MakeElectricalConnections
DANGER:Toavoidpersonalinjuryordeath,donot
supplypowertounitwithcompressorterminalboxcover
removed.
CAUTION:Besurefieldwiringcomplieswithlocaland
nationalfire,safety,andelectricalcodes,andvoltageto
systemiswithinlimitsshownonunitratingplate.Contact
localpowercompanyforcorrectionofimpropervoltage.
Seeunitratingplateforrecommendedcircuitprotection
device.
Useaminimumof18AWG,10conductorwireharnessfor
controlconnectionsbetweenthethermostat,airhandler,
andoutdoorunit.Aminimum10conductor18AWGwire
harnessmustbeusedtopreventincorrectwiringofthe
unit.
IMPORTANT:Keepwiringcolorcodedaccordingtosystem
drawingsforeasytroubleshootingandstandardization.For
colorcodereference,seeFigures6‐10inAppendixB.
NOTE:Operationoftheunitonimproperlinevoltage
constitutesabuseandcouldaffectunitreliability.Seethe
unitratingplate.Donotinstallunitinsystemwherevoltage
mayfluctuateoutsideofnormalvoltagefluctuationsof198
–253VACinaccordancewiththespecificationsheets
(AppendixG).
NOTE:Usecopperconductorsonlybetweenthedisconnect
switchandtheunit.
NOTE:Installabranchcircuitdisconnectofadequatesize
perNECtohandleunitstartingcurrent.Locatedisconnect
withinsightfromandreadilyaccessiblefromunit,per
Section440ofNEC.
ROUTEGROUNDANDPOWERWIRES
DANGER:Theunitcabinetmusthaveanuninterruptedor
unbrokengroundtominimizepersonalinjuryifanelectrical
faultshouldoccur.Thegroundmayconsistofelectricalwire
ormetalconduitwheninstalledinaccordancewithexisting
electricalcodes.Failuretofollowthiswarningcanresultin
anelectricshock,fire,ordeath.
Removeaccesspanelandelectricalboxcovertogainaccess
tounitwiring.Extendwiresfromdisconnectthroughpower
wiringholeprovidedandintounitcontrolbox.Sizewiresper
NEC.
CONNECTGROUNDANDPOWERWIRES
CAUTION:LineVoltageandControlwiresmustberouted
clearofanysystemcomponentstopreventwiringchafing/
electricalshorts.
CAUTION:Ensurelineandcontrolvoltagewiresare
routedawayfromterminalconnectionsofrelaysand
capacitors.
Connectthegroundwiretothegroundconnectionluginthe
controlboxforsafety.ConnectpowerwiringtoindicatedL1
andL2connectionsusingappropriatelysizedwirenuts.For
clarificationseethelinevoltagedrawinginFigure6,Appendix
B.The75VAtransformerlocatedintheoutdoorunitisfactory
pre‐wiredfora240VACinput.Iftheunitisbeingconnected
tosupplyvoltagesotherthan240VAC,consultthewiring
diagraminFigure6,AppendixB.
ROUTECONTROLWIRING
Toroutecontrolwirestotheinterioroftheheatpumpunit,it
isnecessarytopiercethe½”rubbergrommetandslidethe
controlwiresintotheelectricalcabinetoftheoutdoorunit.
Whileroutingcontrolwiresthroughtheunit,avoidrouting
acrossoraroundthecontrolboard,asthismaygenerate
unwantedinterference.
CAUTION:Testgroundconnectionusingamulti‐meter.
CONNECTCONTROLWIRING
NOTE:Thesystemissuppliedwitha75VAtransformer
withabuilt‐in3.7ampbreaker.

INSTALLATION
‐12‐
NOTE:Ifusingexistingcontrolwiring,besuretheharnessis
aminimumof18awg,10conductorminimumandallthe
wiringisingoodcondition.
IMPORTANT:Ensurethatnoothercontrolvoltage
transformerisconnectedtothesystem.Useonlythe75VA
transformersuppliedintheoutdoorunit.
IMPORTANT:Makesuretoadjustthelinevoltageleadsto
the75VAtransformerifthelinevoltageisotherthan240V.
IMPORTANT:Disconnectthesecondaryleads(controlvoltage
wires)fromtheairhandlercontroltransformertotheair
handlercontrolboard.
Using10or12‐conductor,18AWG,color‐coded,insulated
(35Cminimum)wire,connectthecontrolsystemcomponents
betweentheheatpump,HallowellMatchedairhandler,and
thermostat(asshowninFigure9,AppendixB).Ifthedistance
betweenthethermostatandtheheatpumpunitismorethan
100feet(asmeasuredbythecontrolwiring)16AWGwire
shouldbeutilizedtoavoidunnecessaryvoltagedrop.All
wiringmustbeNECClass1andmustbeseparatedfromthe
incomingpowerleads.Theoutdoorunitprovidesamaximum
of75VA,24VACforcontrolpower.Toensurecorrect
operationofthesystem,the40VAtransformerlocatedinthe
IndoorAirHandlermustbedisconnectedfromthecontrol
board,andproperlyinsulatedtopreventpossibleshorts.
NOTE:24VACneedstobesuppliedtotheairhandler
controlboard;24VACterminalandCOMterminal.
FollowingthecolorcodesprovidedinFig7‐10,AppendixB,
makeconnectionstothethermostat,airhandler,andout‐
doorunit.Connectionsmaybemadeusingeither¼”female
disconnects,orusingstrippedwireconnectionswiththe
screwterminalsprovided.
NOTE:Ensurethesuppliedthermostatandindoorair
handlerareinstalledandproperlywired.
NOTE:Ensuretheairhandlerjumpersareplacedintheir
appropriatepositionandthatallwiringfollowscolorcode
instructions.
CONFIGURINGYOURHEATPUMPCOMPONENTS
Minimumairflowforthe48Ais1300cfmonaY2call.
Setthecontroljumpersintheairhandleraccordingly.If
usingthefactorysuppliedairhandlingunit,seeFigures
1‐2,AppendixA.JumpersettingsofHeat:ADelay:A
Cool:DAdjust:B.
Minimumairflowforthe36Ais1000cfmonaY2call.
Setthecontroljumpersintheairhandleraccordingly.If
usingfactorysuppliedairhandlingunitseeFigures1‐2,
AppendixA.JumpersettingsofHeat:ADelay:ACool:B
Adjust:B.
Minimumairflowforthe24Ais800cfmonaY2call.Set
thecontroljumpersintheairhandleraccordingly.If
usingfactorysuppliedairhandlingunitseeFigures1‐2,
AppendixA.JumpersettingsofHeat:ADelay:ACool:B
Adjust:B.
IfelectricheatisinstalledintheAHU,besuretheair
handlerunitisproperlyconfiguredforelectricheat.Be
suretheHeat/NoHeatjumperontheAHUunitissetto
Heat.Ifusingthefactorysuppliedairhandlingunit,see
Figure1,AppendixA.
UsingthetableinFigure5,AppendixA,programthe
thermostatforproperoperationwiththeHallowell
Acadia.
ItisessentialtoplacethejumperbetweenRCandRHas
indicatedonthethermostatdiagram(Figure9,Appendix
B)toallowcorrectoperation.
Ensurethejumpersontheoutdoorcontrolboardarein
theproperposition;JMP2ManualDefrostononepin,
andJMP1Economyjumperonbothpins.
Ifthesystemisusingthefactoryrecommendedzone
control,consultFigure15,AppendixFforproperwiring
usingtheEWCzonecontrol.
FINALWIRINGCHECK
IMPORTANT:Checkthefactorywiringandwireconnections
toensureterminationsaresecuredproperly.Checkthewire
routingtoensurethewiresarenotincontactwithtubing,
sheetmetal,electricalboxcomponents,etc.
Step7–ChargeUnitandStartup
CAUTION:ENSUREBOTHTHEVAPORLINEANDLIQUID
LINESERVICEVALVEAREOPENANDTHELINESETIS
PROPERLYINSULATED.
NOTE:Theminimumoutdooroperatingambientincooling
modeis50°F,andthemaximumoutdoorambientincooling
modeis125°F.Theminimumallowedheatingoperationis‐
30°Fandthemaximumoutdoorambientis82°F.
Topreventcompressordamageorpersonalinjury,observe
thefollowing:
Donotoverchargethesystemwithrefrigerant.Follow
thechargingchartandweighinR410arefrigerant.

INSTALLATION
‐13‐
Donotoperatetheunitinavacuumoratnegative
pressure.
Donotdisablethelow‐pressureorhigh‐pressure
switches.
EnsuretheAirHandlerfilterisclean
EnsuretheAirHandlerAdjustmentsaresetcorrectly.
Checkthatallsupplyandreturnregistersareclearand
notblocked.
Topreventpersonalinjuries,wearsafetyglasses,protective
clothing,andgloveswhenhandlingrefrigerantandobserve
thefollowing:
USEONLYR410ARATEDREFRIGERANTEQUIPMENT.
IMPORTANT:KEEPEQUIPMENTANDHOSESCLEAROF
DEBRISANDMOISTURE.
IMPORTANT:Donotventrefrigeranttotheatmosphere.
Recoverrefrigerantduringsystemrepairorfinalunit
disposal.
CAUTION:Ifthereiseveraquestionofhowmuchcharge
hasbeeninducedintothesystemwhilecharging,recover
theunitandre‐charge.Recordtheamountoffinalcharge
withapermanentmarkerontheservicestickerwhereitwill
bevisible.
Followthesestepstoproperlystartupthesystem:
1. Closetheelectricaldisconnectstoenergizethesystem
andensurethesystemcontrolheartbeatandthermostat
energizes.
NOTE:Intheeventoutdoortemperatureswillnot
allowthefullamountofchargeintotheliquidline
serviceport,completethechargethroughthe¼
inchchargingportaftersystemisrunning.
NOTE:Theoutdoorunitisequippedwithcrank
caseheaterswhichoperatewhenlowsump
temperaturesoccur,ensuringseparationofoiland
refrigerant.Ensurethecrankcaseheatersare
energizedbeforeadmittinginitialcharge.Ifpower
hasbeenlost,orunithasbeende‐energizedfor4
hoursormoreafterchargehasbeenadmitted,
allowthecrankcaseheaterstoenergizefora
minimumof12hours.Notfollowingwarningsmay
resultincompressorchatteringandpermanent
damagetocompressors.
2. Theinitialunitchargedependsonthelengthoftheliquid
lineused.Besuretoaccuratelymeasuretheliquidline
length.Afterevacuationiscomplete,chargetheunit
withR410Arefrigerantthroughtheliquidlineservice
port,usingtheamountsonthechartshownbelow.
HallowellACHPLineSetChargingChart
Lineset
length
(ft)
Acadia024Acadia036&
Acadia048
0‐109lb 12lb‐8.0oz
119lb‐0.6oz12lb‐8.6oz
129lb‐1.2oz12lb‐9.2oz
139lb‐1.8oz12lb‐9.8oz
149lb‐2.4oz12lb‐10.4oz
159lb‐3.0oz12lb‐11.0oz
169lb‐3.6oz12lb‐11.6oz
179lb‐4.2oz12lb‐12.2oz
189lb‐4.8oz12lb‐12.8oz
199lb‐5.4oz12lb‐13.4oz
209lb‐6.0oz12lb‐14.0oz
219lb‐6.6oz12lb‐14.6oz
229lb‐7.2oz12lb‐15.2oz
239lb‐7.8oz12lb‐15.8oz
249lb‐8.4oz13lb‐0.4oz
259lb‐9.0oz13lb‐1.0oz
269lb‐9.6oz13lb‐1.6oz
279lb‐10.2oz13lb‐2.2oz
289lb‐10.8oz13lb‐2.8oz
299lb‐11.4oz13lb‐3.4oz
309lb‐12.0oz13lb‐4.0oz
319lb‐12.6oz13lb‐4.6oz
329lb‐13.2oz13lb‐5.2oz
339lb‐13.8oz13lb‐5.8oz
349lb‐14.4oz13lb‐6.4oz
359lb‐15.0oz13lb‐7.0oz
369lb‐15.6oz13lb‐7.6oz
3710lb‐0.2oz13lb‐8.2oz
3810lb‐0.8oz13lb‐8.8oz
3910lb‐1.4oz13lb‐9.4oz
4010lb‐2.0oz13lb‐10.0oz
4110lb‐2.6oz13lb‐10.6oz
4210lb‐3.2oz13lb‐11.2oz
4310lb‐3.8oz13lb‐11.8oz
4410lb‐4.4oz13lb‐12.4oz
4510lb‐5.0oz13lb‐13.0oz
4610lb‐5.6oz13lb‐13.6oz
4710lb‐6.2oz13lb‐14.2oz
4810lb‐6.8oz13lb‐14.8oz
4910lb‐7.4oz13lb‐15.4oz
5010lb‐8.0oz14lbs

INSTALLATION
‐14‐
3. Thethermostatmustbesetupatthistimetoproperly
workwithyourHallowellAcadia.SeethetablesinFigure
5,AppendixA.
4. SetthethermostattoFanON,ensuringairflowand
jumpersareproperlyplacedintheHallowellMatchedair
handler.Testtheemergencyheatsettings.
5. SettheFantoAUTOorONasdesired,thensettheroom
thermostattoCOOLorHEAT.Waitfortheappropriate
timedelay(s).Operatetheunitfor30minutesafterinitial
charge,continuouslyensuringthethermostatsettingwill
notbesatisfied.(Openwindowsordoorsifnecessary)
NOTE:Whilewaiting,besurethelinesetissecure
andinsulatedseparately.Thisisagoodtimeto
doublechecktheinstallationprocedure.Check
overthesystemforanyunusualvibrations/noises.
6. Settheroomthermostat10degreesormoreaboveor
belowdesiredroomtemperatureallowingsecondstage
operationwhilecharging.Thismaybringonathird
stagecallfromthethermostatandturnonauxiliaryheat.
NOTE:Donotallowthetemperaturesettingsto
bereacheduntilchargeiscomplete.Openthe
doorsandwindowsifnecessarywhilechargingto
ensurethiscondition.Besurethesetpointisabove
orbelowindoorambientandissethighorlow
enoughtoenergizedesired2ndstageoperation.
7. Ensuretheproperstageisoperatingbyreviewingthe
systemthermostatrequirementsforasecondstagecall,
andtheindicatorlightsprovidedontheoutdoorunit
controlboard.SeeFigure4,AppendixAforthelocation
oftheLEDindicatorlightsandtheircorrespondingmode.
EnsurethesystemdiagnosticoutputLEDisenergizedand
beating.SeeFigure4,AppendixA.
Step8–CheckCharge
UNITCHARGE
Withtheunitoperating,chargethesystem(ifnecessary)with
liquidR410AusingacommercialtypeR410Aratedmetering
devicemanifoldandhoseassembly.Chargethesystemwith
refrigerantintothe¼”chargingport.Checkthechargein
heatingmodeonly.Adjustthechargeinheatingusingthe
followingprocedure.
NOTE:Theunitistobechargedinhighcapacityonly(2nd
stagethermostatcall).
NOTE:Above60°F,chargetheunitusingthelinesetchart
(seestep7orAppendixC).Youmayhavetoreturnin
heatingseasonanddoublecheckchargeamountforoptimal
efficiency.
HEATINGCHECKCHARGEPROCEDURE
CAUTION:R410AismisciblewithPOEoilinthe
system.Letthesystemruninnormaloperationforan
adequateamountoftimeafterstartuporadefrost
cycletoensureanaccuratesubcoolingreading.
1. Operatetheunitaminimumof30minutesbefore
checkingcharge.
2. Measuretheliquidservicevalvepressurebyattachingan
accurateR410Aratedgaugeto3/8”serviceport.
3. Measuretheliquidlinetemperaturebyattachingand
insulatinganaccuratethermistortypeorelectronic
thermometertotheliquidlineneartheoutdoorcoil.
Usethepressure–temperaturecharttocalculatesub‐
cooling(Figure12,AppendixC).
4. Refertothechargingtableforrequiredsubcooling
temperatures(Figure11,AppendixC).Ifsubcoolingis
otherthatwhatisindicatedonthechart,consult
Hallowelltechnicalsupport.
NOTE:Forevery1lbofadditionalrefrigerantadded,allow
anadequatetimeforthesystemtosettlebeforetaking
anothersubcoolingreading.
Youmustensurethatyouwillhavea2ndstagecallonthe
thermostat.Setthethermostatwellaboveindoorairtemp
andopendoorsandwindowsifneeded.
Tocheckthesystemchargeincoolingoperation:
1. Thesystemischargedforheatingperformance.Ifthe
chargeofrefrigerantisinquestion,recovertheunit
chargeandweighintheappropriatecharge,accordingto
thelinesetchargingchart.
2. Ifthesystemisinstalledasanewinstallationduring
coolingseason,areturntriptorecheckthecharge
amountduringheatingseasonmaybeneeded.
Step9–FinalChecks
IMPORTANT:Beforeleavingthejobsite,besuretodothe
following:

INSTALLATION
‐15‐
1. Ensurethatallwiringandtubingissecureintheunit
beforeaddingpanelsandcovers.Securelyfastenall
panels/coversandensureallfastenersremaintight.
2. Tightentheservicevalvestemcapsto1/12‐turnpast
fingertight.
3. LeavetheOwner’sManualaswellastheInstallation
Manualwiththecustomer.Explainthesystemoperation
andperiodicmaintenancerequirementsoutlinedinthe
manual.
4. FillouttheDealerInstallationChecklistandplaceina
customerfile.
5. Besuretotalktothecustomeraboutthegeneral
maintenance,shovelingaroundtheunitandkeepingit
clearofdebris,basicthermostatuseandtheimportance
ofperiodicalfilterchanges.
6. Discouragethecustomerfromsetbacksofthe
thermostatprogram.
7. Ensurethesupplyregistersarediffusedproperly.
8. Ensurethechargeamountiswrittenontheservice
stickerprovidedontheelectricalboxcoverofthe
outdoorunit.
9. Talktothecustomeraboutthedefrostoperationand
howitwilleffecttheregistertemperature.
10. Besurethecustomerknowswheretopurchasemoreair
filters.
11. Ensurethesupplyregistersaredefusedawayfromheavy
trafficareasandnotdirectlyonthecustomer.
CAREANDMAINTENANCE
Forcontinuinghighperformance,andtominimizepossible
equipmentfailure,periodicmaintenancemustbeperformed
onthisequipment.Frequencyofmaintenancemayvaryde‐
pendingupongeographicareas,suchascoastalapplications.
Paycloseattentiontocleanlinessofindoor/outdoorcoils
andproperductcirculationandsealing.
Incoastalregions,theoutdoorcoilmustbewashedannually
byaqualifiedservicetechnician.
Yourservicingdealermayofferaneconomicalservice
contractthatcoversseasonalinspections.Askforfurther
details.
Extras
ZoneControls.
TheonlyzonecontrolthatisfactoryauthorizedistheEWC
UZCseriesofzonecontrol.Thezonecontrolwillbewired
andsetupaccordingtothedrawinginAppendixF.Thiszone
controlworksverywellwiththeAcadiaaslongassomerules

INSTALLATION
‐16‐
6. Toprotectthecoilfromdamage,useanti‐freezein
thehydroniclooptopreventfreezing.Afreeze‐stat
canalsobeusedtoprotectthecoil.
7. HydroniccoilsaddedinternallytotheHallowellAHU
arenotapproved.
Installingthesystemwithahotairfurnace
Hallowellwillapproveaparallelfurnaceinstallationpending
afactoryconsultation.Theductworkmustbeinstalledwith
damperssothattheairflowwillnotshortcyclethrough
eithersystemwhenitison.Anisolationrelaymustbeused
sothatthefurnaceisnotallowedtooperatewhentheAcadia
isrunning.
HallowellControlTimers
1. TemperatureStabilityTimer(5Min)–Inorderforthe
systemtochangeoperationalBINSfromonetoanother,
thesystemmustsenseatemperaturechangeinthenew
BINforatleastfiveminutes.
2. DefrostLockoutTimer(45Min)–Thistimerpreventsthe
systemfromgoingintoanotherdefrostwithin45
minutesofthepriordefrost.
3. Y2ValidationTimer(1Min)–Theoutdoorunitmust
senseaY2callfromthethermostatforatleast1minute
beforeitwillchangestages.Thiswillprohibitnuisance
stagingoftheoutdoorunit.
4. Anti‐ShortCycleTimer(3min)–Preventstheshort
cyclingofcompressoroperation.
5. MaximumDefrostTimer(8Min)–Maximumallowable
timeforadefrostcycle.
6. MinimumDefrostTimer(3Min)–Minimumallowable
timeforadefrostcycle.
7. FaultRestartTimer(10Min)–Iftheunitsensesafault,it
willstandbyfor10minutesbeforeattemptingtorestart.
(NOTE:anyfaultreoccurringthreetimeswithin30
minutewilllockoutthesystemand“CallForService”will
beindicatedonthethermostat.)
8. FanPurgeTimer(20seconds)–Runsthefanfor20
secondsattheendofadefrostcycletoremovewater
dropletsfromtheoutdoorcoil.(Reversingvalvewill
cycleattheendofthefanpurgeandendsdefrost)
NOTE:Inadditiontotheabovetimers,Hallowell’sAcadia
utilizesmanyproprietarytimerstoensureproperand
efficientoperationoftheunit.Ifthereareanyquestions
abouthowtheunitisoperating,contactHallowellfactory
support.

Troubleshooting
‐17‐
CONTROLERRORCODES
Intheeventofafailureintheoutdoorunit,thecontrolhasa
builtindiagnosticLEDfortroubleshootingpurposes.
AppendixA,Figure4showsthelocationofthediagnostic
LEDontheAcadiacontrolboard.Duringnormaloperation
thisLEDfadeson,andblinksoffcontinuously.Ifforanyrea‐
sontheunithasencounteredanerrorcondition,theerror
maybediagnosedusingtheerrortablebelow.
StatusIndicatorSequenceSystemStatus
FadeIn,FastOff(Heartbeat)NormalOperation
1Flash,OFFfor3SecondsControlBoardWatchdog
Reset
2Flashes,OFFfor3SecondsPowerBrownoutReset
3Flashes,OFFfor3SecondsSystemPressureSafety
Shutdown
6Flashes,OFFfor3SecondsInterstageOver
temperatureShutdown
7Flashes,OFFfor3SecondsOutdoorAirTemperature
SensorFault
8Flashes,OFFfor3SecondsCoilTemperatureSensor
Fault
9Flashes,OFFfor3SecondsInterstageTemperature
SensorFault
10Flashes,OFFfor3
Seconds
SpareTemperatureSensor
Fault
IftheHallowellAcadiahasencounteredanoperationalerror,
theoutdoorunitwillshutdownforaperiodof10minutes,
afterwhichitwillattempttorestartinitslastknownoperat‐
ingmode.Iftheunitisabletorestartandrunfor30continu‐
ousminuteswithoutanerror,allerrorcodeswillbecleared
andnormaloperationshallcontinue.If,however,this
attempttorestartfails,theoutdoorunitwillshutdownfor
another10minutes.Ifathirderroroccurswithin30minutes
oftheoriginalerror,theunitwillshutdownalloperationand
activateaMAINTENANCEREQUIREDoutput.Thisshould
causeaCALLFORSERVICEindicatortobedisplayedonthe
thermostat,signifyingtheneedtocontactaqualifiedinstaller
ortechnician.
BrownoutFault
InthecaseofaBrownout,useamulti‐metertocheckline
voltagetobesurethatthevoltageiswithinnameplate
tolerance.Ifsoresetthepowertotheoutdoorunitand
checkfornormaloperation.Ifvoltageislow,contactthe
PowerCompanyandletthemknowoftheproblem.
PressureSafety
Pressuresafetiesaresetasfollows:
HighPressure CutOut575psiCutIn450psi
LowPressureCutOut5psi CutIn20psi
InthecaseofaPressureSafetyfault,checkthesystem
pressures.Thepressuresafetyswitchesareanautomatic
resettypesoyoumayhavetorunthesystemtocheckthe
pressures.Ifpressureislowchecksystemforleaks,and
repair.Inverycoldclimatesthelowpressurewilldrop
systemoutatacoiltemperatureof‐45degF.
Alsoiftheunithasnotgoneintodefrostandthecoilis
coveredinice,thiscouldcausethecoiltemperaturetodrop
below‐45degF.Installthemanualdefrostjumperonthe
outdoorunitcontrolboard.Ifunitdefrostcheckthe
TemperatureSensorFaultsectionoftroubleshootingguide.If
theunitdoesnotgointodefrostchecktheDefrost
Troubleshootingguide.
Theoutdoorunitmaybeoutonahighpressuresafetyreset.
Youwillhavetoruntheunitandwatchtheheadpressure.If
unitisinheatingmodechecktheindoorfan,andthefilter.If
theunitisincoolingchecktheoutdoorcoilandoutdoorfan
motor.
TemperatureSensorFault
NOTE:Makesurethesystempowerisoffbefore
troubleshootingthetemperaturesensors.
Ontheupperrighthandcorneroftheoutdoorunitcontrol
boardistheplugforthetemperatureRTDsensors.Youwill
needtounplugthesensorsfromthecontrolboardbypulling
theplugstraightoffthecontrolboard.Checktheconnection
ofthewiresintheplugmakingsurethatthewireisnot
brokenortheinsulationisintheplug.Youwillneeda
thermocouplereaderandsensor,andamulti‐meter.Using
thethermocoupletakethetemperatureateachsensor.
TheBluewiresensoristhecoilsensorandislocatedonthe
seconddistributortubefromthebottomofthecoil.The
Yellowwiresensoristheinterstagesensoranditislocated
onthesuctionlinegoingtotheprimarycompressor.The
Whitewiresensoristheoutdoorairsensorandislocatedon
thepipeconnectionsideoftheunit.
Usingamulti‐meter,ohmouteachsensorandcheckthe
resistanceofeachcomparedtothetemperatureonthechart
below.

Troubleshooting
‐18‐
ResistanceVsTemperature
Temperature(°F)Resistance(Ω)
‐4084.21
‐3086.41
‐2088.61
‐1090.81
093.01
1095.2
2097.38
3099.57
40101.74
50103.9
60106.06
70108.22
80110.38
90112.53
100114.68
110116.82
120118.97
130121.1
Tolerances
Temperature±Tolerance
°F°FΩ
‐1001.10.3
00.70.2
320.60.1
1000.70.2
Ifanyofthesensorsdonotohmoutcallyourdistributorfora
newsensorandreplaceit.
HardwareFault
IncaseofaHardwareFaultcontactHallowellInternational
LLC.Thisisahardwareproblemonthecontrolboardandit
willneedtobereplaced.
UnitIsnotChangingModesofOperation
Theoutdoorunitlooksatthecallfromtheindoorthermostat
andtheoutdoortemperaturetodeterminetheoptimized
runningmode.Checkforinputcallsfromthethermostat.If
ok,checktoseewhatmodeofoperationyoushouldbein.
Seethechartbelow.Iftheunitisnotchangingmode,dothe
Temperaturesensorfaulttest.
HeatingModeOperation
TheHallowellAcadiaoperateswith6modesofheating
capacityavailable.Thesemodesareasfollows:
Mode1:Singlecylinderprimarycompressor
Mode2:Twocylinderprimarycompressor
Mode3:PrimaryTwocylinderplusW1(1ststageauxiliary
heat)
Mode4:PrimaryTwocylinderandBoostercompressors.
Mode5:PrimaryTwocylinderandBoostercompressorsplus
W1(1ststageauxiliaryheat).
Mode6:W1(1ststageauxiliaryheat)
These6modesofheataredeterminedbyacombinationof
theY1andY2inputsfromthethermostatandtheoutdoorair
temperatureasseenbytheunit.
Thetablebelowillustratestheoperatingmodesallowedas
thetemperaturevaries.
FahrenheitCelsius
BINAAMB≤‐30°FAMB≤‐34.4°C
BINB‐30°F<AMB≤15°F‐34.4°C≤AMB<‐9.4°C
BINC15°F<AMB≤25°F‐9.4°C≤AMB<‐3.8°C
BIND25°F<AMB≤31°F‐3.8°C≤AMB<‐0.5°C
BINE31°F<AMB≤41°F‐0.5°C≤AMB<5°C
BINF41°F<AMB≤62°F5°C≤AMB<16.6°C
BINGAMB>62°FAMB>16.6°C
Table1:OutdoorAmbientTemperatureBins
NOTE:OncetheunitgoesfromM1toM2,theunitshall
notgobacktoM2(i.e.Stg1‐>Stg2willnotrevertback).This
istoreducethenumberofcompressorcyclesthatoccur.
Inthetablebelow,Y2OUTisonif“Y2O”isinthetable.

Troubleshooting
‐19‐
HeatModesandY2OUTSTATEvs.BinsandY1/Y2
Deman
dCalls
BIN
A
BINBBINCBINDBINEBINFBIN
G
Y1M6/
Y2O
M4/
Y2O
M2M2M2/
Y2O
M1 M1
Y2M6/
Y2O
M5/
Y2O
M4/
Y2O
M3/
Y2O
M2/
Y2O
M2/
Y2O
M1
Table2:StateofY2OUTandHeatModevs.Bins
Atanytimewhilethethermostatisinheatingmode,the
systemcanbeplacedintoemergencyheatingmode,
energizingtheinstalledauxiliaryheatingsystem.
CoolingModeOperation
TheHallowellAcadiaoperateswith2stagesofcooling
capacityavailable,basedonthelevelofdemandfromthe
thermostat.Coolingmodeislimitedtooperationwhenthe
outdoorairtemperatureisabove50Ftoensurecorrect
operationofallcomponentsinthesystem.The2stagesof
coolingcapacityareillustratedbelow,withthemodesof
operationbeingidenticaltothemodesofoperationusedin
heatingmode.
COOLING
ThermostatCall<49F>50F
Y1N.A.M1
Y2N.A.M2
UnitIsNotDefrosting
Setthemanualdefrostjumperonthecontrolboardto
manual.Thisshouldstartadefrostcyclerightawayifthe
unitisrunning.Iftheunitdoesnotgointodefrost,checkthe
LEDsonthecontrolboard.TheLEDsthatshouldbelitareRV,
2Cyl,Y2O.Youshouldhearthereversingvalvethrow,and
theoutdoorfanshouldstop.Theprimarycompressorshould
berunning.
IftheRV(reversingvalve)didnotthrowandtheRVLEDislit,
checkfor24VACattheRVand24Coutputonthecontrol
board.Thisislocatedontheupperleftplugontheboard.If
youhave24VAC,checkthattheplugonRVisconnected.
Checkthewireforcontinuity.Ifthewireisok,thencheckthe
RVCoil.
Checktheresistanceofthereversingvalvecoil.Ifthecoilis
openorshorted,replacethecoil.
Ifthecoilchecksoutok,thenreplacetheRV.
IftheRVLEDislitandyoudonothave24vacattheRV
terminals,replacecontrolboard.
IftheRVLEDisnotlit,replacethecontrolboard.
Ifthemanualdefrostisfunctional,performtheTemperature
sensorfaulttest.
Callforservicelightcomesonduringadefrost
CheckwiringfromW1toXLtanandbrownwire,besurethey
areintherightposition.
PrimaryCompressorwillnotstart
IfnoLEDsarelittheunitmaybeinanantishortcycle.Be
suretogivetheunit3min.tostart.Checkthecontrolboard
foreitherthe1Cylor2CylLEDstobelit.IfnoLEDislit,check
theinputsignalfromthethermostat.Ifyouhaveaninput
fromthethermostatandoneoftheLEDsislit,verifythe
outputtothatLEDontheoutputplugontheupperleftof
controlboardfor24VAC.If24VACisnotpresent,replacethe
controlboard.
Ifthecontactorisnotpulledin,checkfor24VACatthe
contactorcoil.Ifyouhave24VAC,replacethecontactor.If
youdonothave24VAC,replacethewiringtothecontactor.
Checkthecontactor.Ifitispulledin,checkthestartinggear
ofthecompressor.Checkthestartandruncapsandthe
startingrelays.Ifyoufindaproblemwiththestartinggear,
replacethecomponent.Ifitisallok,checkthecompressor
windingsforanopenorshortedwinding.Ifthecompressoris
bad,contactHallowellInternationalLLCforanew
compressorwiththeprovisionsfortheOilEqualizationLine.
BoosterCompressorwillnotstart
CheckthecontrolboardfortheBEoutputLED.
IftheLEDisnoton,checkforthemodeofoperationtobe
surethatboostershouldbeon.PerformtheTemperature
SensorFaultTest.
Ifthatallchecksout,replacethecontrolboard.
IftheLEDison,checkfor24VACattheoutputterminalsfor
BEontheupperleftofthecontrolboard.Ifyoudonothave
24VAC,replacethecontrolboard.
Ifyoudohave24VAC,checktoseeifthecontactorispulled
in.CheckthestartinggearfortheBoosterCompressor.
Checkthestartandruncapsandstartrelay.Ifyoufinda
problemwiththestartinggear,replacethecomponent.
Ifthecontactorisnotpulledin,checkfor24VACatthe
contactorcoil.Ifso,replacethecontactor.Ifyoudonot
have24VAC,replacethewiring.
Ifthestartinggearchecksoutok,checkthecompressor
windingsforanopenorshort.Ifthecompressorisbad,
contactHallowellInternationalLLCforanewBooster
CompressorwiththeprovisionsfortheOilEqualizationLine.
This manual suits for next models
2
Table of contents
Popular Air Handler manuals by other brands

System air
System air Danvent DV user manual

System air
System air VR 300 ECV/B Installation description

System air
System air menerga TX Assembly manual

System air
System air TopVex TX03 Operation and maintenance instructions

System air
System air Topvex SX/C Series installation instructions

Salda
Salda RIS 700 H EKO 3.0 Mounting and installation instructions