HAMWORTHY HEATING LTD. PUREWELL AUTOMATIC IGNITION 500001035/G
4
The flow corresponding o 22°C empera ure rise across
he boiler is he minimum recommended flow a any ime.
For boiler pressure drop see Figure No. 2.
3.4 Time Clock Control
In order o avoid local overhea ing and progressive
calcium deposi ion a zero flow condi ions where boilers
are opera ed from ime clocks, provision should be made
for a 5 minu e circula ing pump over-run af er he las
boiler has ceased firing.
NOTE! Time clocks should no in errup live, neu ral or
ear h connec ions, see Section 9.0: ELECTRICAL
S PPLY for de ails. See Figure No. 12 for wiring de ails.
3.5 Minimum System Pressure
To comply wi h guidance no e PM5 (Health and Safety
Executive), he minimum pressure requiremen s a he
boiler are given below as examples: -
1) Single ins alled boiler running a 82°C flow
empera ure. Minimum head required is no less han 2
me res or 0.2 bar.
2) Single ins alled boiler running a 95°C flow
empera ure. Minimum head required = 5.1 me res or
0.5 bar.
3) Modular boiler ins alla ion running a 82°C flow
empera ure and 11°C rise across sys em. Minimum
head required = 4.3 me res or 0.42 bar.
4) Modular boiler ins alla ion running a 82°C flow
empera ure and 22°C rise across sys em. Minimum
head required = 10.5 me res or 1.03 bar.
See Section 8.11 for Pressurised Wa er Sys ems.
4.0 LOCATION
4.1 (See Figure No. 9 for dimensions/weigh s and
clearances.) The loca ion chosen for he boiler M ST
permi he provision of a sa isfac ory flue sys em and an
adequa e air supply. The loca ion mus also provide
adequa e space for servicing and air circula ion around
each uni . This includes any elec rical runking laid along
he floor.
Allow adequa e space, his should no normally be less
han 460 mm. a he rear, for flow and re urn connec ions.
Also allow a leas 460 mm. on one side, he o her side
mus be no less han 150 mm. Allow 610mm (minimum)
in fron of he boiler for servicing.
The boiler mus be ins alled on a level non-combus ible
surface ha is capable of adequa ely suppor ing i s
weigh (when filled wi h wa er) and any ancillary
equipmen .
Any combus ible ma erial adjacen o he boiler and he
flue sys em mus be so placed or shielded o ensure
ha i s empera ure does no exceed 65°C.
Fur her de ails regarding boiler loca ion are given in
BS 6644.
5.0 GAS S PPLY
5.1 Service Pipes
The local gas region mus be consul ed a he
ins alla ion planning s age in order o es ablish he
availabili y of an adequa e supply of gas. An exis ing
service pipe mus no be used wi hou prior consul a ion
wi h he local gas region.
5.2 Meters
A new gas me er will be connec ed o he service pipe
by he local gas region, or a local gas region con rac or.
An exis ing me er should be checked, preferably by
he gas region, o ensure ha i is adequa e o deal
wi h he ra e of gas supply required.
5.3 Gas Supply Pipes
Supply pipes mus be fi ed in accordance wi h BS 6891
or IM/16 as appropria e. Pipework from he me er o
he boiler mus be of adequa e size. Do no use pipes
of a smaller size han he boiler gas connec ion. The
comple e ins alla ion mus be purged and es ed for
soundness as described in BS 6891 or IM/2 and IM/5
as appropria e.
See Figure No. 11 for recommended gas flows in pipes.
5.4 Boosted Supplies
Where i is necessary o employ a gas pressure boos er,
he con rols mus include a low-pressure cu -off swi ch
a he boos er inle . The local gas region mus be
consul ed before a gas pressure boos er is fi ed.
5.5 Boiler House Control Valve
A manual valve for boiler house isola ion shall be fi ed
in he gas supply line. I shall be clearly iden ified and
readily accessible for opera ion, preferably by an exi .
5.6 Boiler Gas System Leak Check
Al hough he boiler receives a gas leak check and gas
rain componen in egri y check prior o leaving he
fac ory, ranspor and ins alla ion may cause
dis urbance o unions, fi ings and gas valve assemblies’
e c. During commissioning a fur her es for soundness
should be carried ou on he boiler gas pipework and
componen s. A procedure guide is given below. Care
mus be aken no o allow leak de ec ion fluid on or
near any elec rical par s or connec ions (If used). See
Figure No. 3 - Gas valve/pipework leak check es
procedure.