DESCRIPTION
The Hired-Hand High Temperature Monitor provides high
temperature alarm capability for locations such as control
rooms, breaker boxes, etc.
The control setting knob can be set to OFF, 37°C/100°F,
48°C/120°F, or 60°C/140°F. If the control setting knob is set to
one of the temperatures, the customer provided alarm will be
activated when the selected temperature is reached. If the
control setting knob is set to OFF, the alarm will not be
activated.
DANGER
HAZARDOUS VOLTAGES
Failure To Follow These Instructions May Result in Injury
Or Death!
•Do Not Place The Temperature Probe Inside A
Breaker Box Without First Removing Power From
The Breaker Box.
•DO NOT Connect The Alarm Wires To An Electrical
Outlet Or Power Source.
•Only A Certified Electrician Should Install Or
Remove The Temperature Probe From A Breaker
Box.
•Ensure All Cables And Wiring Are Placed And
Secured Before Turning Power ON.
Product Number
Part Number Model
6407-1701 EV High Temperature Monitor
NOTE
The temperature monitor will not reset until the
temperature around the temperature probe drops
10°F (5.5°C) below the set temperature.
The EV High Temperature Monitor is shipped pre-assembled
and ready for installation and wire connections.
The High Temperature Monitor is supplied with a 10 foot
temperature probe cable assembly and a 5 foot alarm cable.
When the monitor is received, check for shipping damage.
LIMITED WARRANTY
All products are warranted to be free from defects in material and workmanship for a period of one (1) year, from the date of purchase if installed and used in strict accordance with the installation
instructions. Liability is limited to the sale price of any products proved to be defective or, at manufacturer's option, to the replacement of such products upon their return. No products are to be
returned to the manufacturer, until there is an inspection and/or a return goods authorization (RGA) number is issued. All complaints should be directed first to the authorized distributor who sold
the product. If satisfaction is not obtained or the name of the distributor is not known, write the manufacturer that appears below, directed to the attention of Customer Service Manager. This
limited warranty is expressly in lieu of any and all representations and warranties expressed or implied, including any implied warranty or merchantability or fitness for a particular purpose. The
remedy set forth in this limited warranty shall be the exclusive remedy available to any person. No person has authority to bind the manufacturer to any representation or warranty other than this
limited warranty. The manufacturer shall not be liable for any consequential damages resulting from the use of our products or caused by any defect, failure or malfunction of our products. (Some
areas do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you). This warranty gives you specific legal rights and
you may also have other rights that vary from area to area.
Alarm Wires
Temperature
Settings
Temperature
Probe
Mounting
Holes
!

HIRED-HAND, INC. •1733 Co Rd 68 •Bremen, AL 35033 •Phone 256-287-1000 •Fax 256-287-2000
Manual Part No. 4801-5152 rev 8-03 Page 2of 4
FIGURE 2
HOW BREAKERS ARE RATED
Circuit breakers are rated for a specific current and up to
104°F(40°C) ambient temperature. After 104°F(40°C),
the current handling capability decreases. Refer to
Figure 2.
Example: A 100 Amp circuit breaker will carry 100 Amps
up to 104°F. At 122°F(50°C), the breaker will
only carry 90 Amps. At 140°F(60°C), the
breaker will only carry 80 Amps.
The temperature inside a breaker box can run as high as
30°F+ or more above the room temperature.
NOTE: Breaker box temperature measurements will not
be reliable unless the temperature probe is
placed inside the secondary cover, near the top
center area.
INSTALLATION
1. Determine the distance from the alarm to the desired
temperature measurement location. Ensure the
provided temperature probe cable and alarm cable
lengths are not exceeded.
2. Install the temperature probe inside the breaker box
secondary cover near the top center. Secure the
probe in place using the supplied adhesive-backed
nylon cable clip. Refer to Figure 3.
FIGURE 3
WARNING
HAZARDOUS VOLTAGES
Failure To Follow These Instructions May Result in Injury
Or Death!
•Do Not Open the Breaker Box Secondary Access
Cover Without Removing Power From The Breaker
Box.
•DO NOT Connect The Alarm Connections Cable To
An Electrical Outlet Or Power Source.
•Only A Certified Electrician Should Install Or
Remove The Temperature Monitor Probe From the
Breaker Box.
3. Secure the High Temperature Monitor enclosure to a
nearby wall or flat surface with customer supplied
hardware and the enclosure mounting holes. Ensure
the monitor enclosure is mounted vertically with the
cables pointing downward.
4. Connect the alarm wires (Black and White) to the
Farm Hand Alert Alarm as shown in the following
wiring diagrams. Refer to Figure 4.
Temperature
(Degrees F)
Rating
Percentage
Lost
4% 8% 12% 16% 20%
104.0
111.2
118.4
125.6
132.8
140.0
Published
Ratin
g
BREAKER DERATIN
G
C
HART
!
Secondary
Access Cover
Place probe at
the top center
and inside the
secondary
breaker box
cover.
WARNING: Do Not Open The Secondary Access Cover With
Power Applied To The Breaker Box.

HIRED-HAND, INC. •1733 Co Rd 68 •Bremen, AL 35033 •Phone 256-287-1000 •Fax 256-287-2000
Manual Part No. 4801-5152 rev 8-03 Page 3of 4
J8
J6
Internal Wiring
High Temperature
Monitor
Inset B Inset A
Black
White
TEMPERATURE
PROBE
ALARM
WIRES
Aux 2Aux 1
High Temperature Monitor
4501-6127
Rev 8-03
®
Bremen, AL
Ph. (256) 287-1000
Fax (256) 287-2000
Connecting External Inputs to the Alert Alarm
FIGURE 4
Farm Hand Alert Alarm
Inset B
Inset A
NOTE: The jumper across J6 and\or J8 must be removed if an
external alarm input is connected.
SIGNAL STATUS
Conditions Normal = N.C.
Alarm Conditions = N.O.