Parameter FSt sets the fan stop temperature. This is the maximum temperature, detected by the evaporator probe, above which the
evaporator fans will stop.
Leave FSt above ambient temperature during commissioning to avoid fan short cycle.
After finishing the defrost phase, there is a stand still drain time, set by parameter Fdt. When this period has expired, the
refrigeration cycle commence but the evaporator fans remain off until Fnd (fan delay) times out.
Spe ial appli ations - Dead Band Control
With [oAC = 1], the compressor relay controls cooling as normal but the 4th (auxillary) relay is used to control a heater. The value
entered in parameter HY will now be set equal on both sides of the S T POINT. xample: If [HY = 1°C] that will create a 2°C Dead Band.
At [S T POINT + HY], cooling switches on. At [S T POINT - HY], heating switches on. ither cooling or heating switch off when
temperature returns to S T POINT.
Alarms
The alarm buzzer can be muted, by pressing any button. The controller will briefly show the reset “r S” label. Parameter tbA defines
how the alarm relay will respond to the muting of the buzzer.
- tbA = 0: The alarm relay will remain active until the alarm condition is rectified.
- tbA = 1: The alarm relay de-activates when the buzzer is muted.
In either case, the display will flash an alarm label until the condition is rectified.
The Dixell Universal-R is provided with an internal watchdog verifying data and memory integrity. Alarm “ ” will flash after
detecting a failure in data or in the internal memory. In this case, the alarm output is enabled.
WHAT TO DO
1. Cancel the alarm by pressing a button.
2. Check the value of the parameters and restore correct values when wrong.
3. Check the correct instrument operation and in case of further errors replace it.
Probe alarms “P1”, “P2” and “P3” start 30 seconds after a fault in probe is detected; they automatically stop 30 seconds after the
probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms “HA” and “LA” automatically stop as soon as the thermostat temperature returns to normal values and when
defrost starts. Temperature alarms “HA2” and “LA2” automatically stop as soon as the condenser temperature returns to normal
values.
Removing se urity level prote tion
It is possible to allow access to any parameter from Pr1 level. To do this, go into Pr2 as previously described. Scroll to the label of
the parameter you require and then press the S T and DOWN buttons in quick succession. The decimal point L D will be on
indicating that access to this particular parameter is now possible from Pr1 level. Its label will now appear when in Pr1
programming level and its value can be altered. To restore security level protection, use the same procedure (the decimal point L D
will go out after pressing both buttons).
LE R410a Operating Instru tions
V1.1 11-12-2015
D AD BAND CONTROL (COOLING & H ATING)
MUTING ALARM BUZZ R & R LAY
ALARM “ ”
ALARM R COV RY
Message Message - Mode Cause Outputs
Flashing Data or memory failure Alarm output ON; Other outputs unchanged.
P1 Flashing Thermostat probe failure Alarm output ON; Compressor output according to parameters Con and CoF.
P2 Alternative with room temperature vaporator probe failure Alarm output ON; Other outputs unchanged; nd defrost is timed.
P3 Alternative with room temperature Second evaporator probe failure Alarm output ON; Other outputs unchanged; nd defrost is timed.
HA Alternative with room temperature High temperature alarm Alarm output ON; Other outputs unchanged.
LA Alternative with room temperature Minimum temperature alarm Alarm output ON; Other outputs unchanged.
HA2 Alternative with room temperature Condenser max temp alarm Alarm output ON; Other outputs unchanged.
LA2 Alternative with room temperature Condenser max temp alarm Alarm output ON; Other outputs unchanged.
dA Alternative with room temperature Door open alarm Alarm output ON; Outputs re-start if parameter rrd = 1.
A Alternative with room temperature Generic external alarm Alarm output ON; Other outputs unchanged.
bAL Alternative with room temperature Serious external alarm Alarm output ON; Other outputs OFF.