
HANDLING MANUAL
SERVICE MANUAL
RAYPAK HI DELTA BOILERS/WATER HEATERS
WITH FAN ASSISTED PREMIX BURNERS
similarl , up to safe limits, but the quantit of gas valves,
blowers and igniters differ from model to model.
Information can be obtained about the actual status of the
operation and faults through the control lights of the outer
and inner panels and time rela s.
Whenever the “SAFETY” light of the outer diagnostic
panel is on 24V AC signal is generated on the “ALARM”
output terminal of the inner panel, which can be carried as
a collected error signal.
The two-wa main power switch can be found on the C
rail located on the front right upper part in the electric
box. The 230V main circuit and the inlet terminal of the
24V control circuit are energized and the “POWER” light
of the outer diagnostic panel is on when the main switch is
switched on. The safet components are instantl supplied
b energ :
At this stage, on condition the preventive safet switches
are closed, the “SAFETY ERROR” light goes out and the
appliance is read for operation.
In case of an error “SAFETY ERROR” light would sta
on and the appliance will not start its operation.
In case of demand for heat of an outer source the
“HEAT DEMAND” light goes on. The pump control
rela starts the pump connected to the gas appliance.
The contacts of the flow switch close if the pump is able
to suppl at least the minimal demanded flow through the
heat exchanger. The “FLOW” light goes on and all
blowers start to operate. The contacts of the air pressure
switches close and the appropriate ordinal number of
“BLOWER” lights up. The thermostat input of the
ignition controller is supplied and a 15 second long pre-
purge period is followed b the glowing up of the hot
surface igniter. The heating up period lasts for about 30
seconds then an attempt for the igniting begins.
The appropriate gas valve is supplied during the four
second long ignition attempt. “STAGE 1” control light
goes on. The gas valve onl sta s open if the remote
sensor is able to sense flame during these four seconds.
Stage 1 begins to operate and its control light sta s on.
Gas valve 2 will be supplied and “STAGE 2” light goes on
in case of further heat demand, following the necessar
time dela .
262ACE model gas valve #3
“STAGE 2” light goes on in case of further heat demand,
following the necessar time dela .
The ignition s stems of models 1532ACE through-
2342ACE are duplicated. At these models upon heat
demand for stage 3 the ignition controller #2 is supplied
and the 15 seconds pre-purge period followed b the
glowing up of the hot surface igniter #2 is started. The
heating up period lasts for about 30 seconds than an
ignition attempt begins.
Gas valve #3 is supplied during the successful igniting
attempt for four seconds. “STAGE 3” control light goes
on. The gas valve onl sta s open if the remote sensor #2
is able to sense flame within these four seconds. Stage 3
begins to operate and its control light sta s on.
Gas valve #4 will be supplied and “STAGE 4” light goes
on in case of further heat demand, following the
necessar time dela .
In case of a failure of one ignition s stem the other will
take over the load automaticall , this wa the appliance is
able to operate at about 50% performance.
The contacts of the flow switch sta open if the pump is
unable to suppl at least the minimal demanded flow
through the heat exchanger. The “FLOW” light does not
go on. The appliance does not start even in case of heat
demand, or it stops operation. Onl “POWER” and
“HEAT DEMAND” lights sta on.
The ignition controller attempts ignition 5 times in
sequence before locking out in case of an ignition failure.
“SAFETY” light goes on.
The appliance purges for 15 seconds before locking out
whenever the “BLOCKED VENT” light is on.
“SAFETY” light goes on.
The appropriate ordinal number “BLOWER” light goes
out if an of the blowers is unable to create the minimal
pressure difference that is needed for the operation. The
appliance purges for 15 seconds before locking out.
“SAFETY” light goes on.