Ice Qube Evolution Series Specification sheet

1
Evolution Series Air Conditioners
Class I Division 2 Groups A, B, C, & D Hazardous Locations or Nonhazardous Locations
OPERATION AND INSTALLATION MANUAL
*** IMPORTANT ***
PLEASE READ this manual and follow the instructions for safe and satisfactory installation and operation of this system.
Keep this manual for future reference. Some information may not apply to all systems.

2
Introduction .................................................................................................................................................................... 3
Basic Unit Operation...................................................................................................................................................... 3
Preservation Instructions............................................................................................................................................... 4
Pre-Installation Test....................................................................................................................................................... 5
Preparing the Enclosure................................................................................................................................................. 6
Mechanical Installation Instruction .............................................................................................................................. 6
Electrical Installation Instruction.................................................................................................................................. 8
Alarm Installation Instruction..................................................................................................................................... 10
Operating Your System................................................................................................................................................ 11
Programming the Standard Controller ...................................................................................................................... 11
Programming the Ethernet Controller ....................................................................................................................... 14
Alarm Operation........................................................................................................................................................... 14
Maintenance.................................................................................................................................................................. 15
Trouble Shooting .......................................................................................................................................................... 15
Schematic Wiring Diagrams........................................................................................................................................ 17
Ordinary Locations .................................................................................................................................................................17
120V/220V/230V................................................................................................................................................................. 17
400V/460V/480V................................................................................................................................................................. 18
Hazardous Locations...............................................................................................................................................................19
120V/220V/230V................................................................................................................................................................. 19
400V/460V/480V................................................................................................................................................................. 20
Specification Drawing................................................................................................................................................... 21
1000EV .....................................................................................................................................................................................21
2000EV .....................................................................................................................................................................................22
3000EV .....................................................................................................................................................................................23
4000EV .....................................................................................................................................................................................24
5000EV .....................................................................................................................................................................................25
6000EV .....................................................................................................................................................................................26
8000EV .....................................................................................................................................................................................27
10000EV...................................................................................................................................................................................28
12000EV...................................................................................................................................................................................29
14000EV...................................................................................................................................................................................30
17000EV...................................................................................................................................................................................31
20000EV...................................................................................................................................................................................32
IQ1-2-3000EV Gasket and Cutout.........................................................................................................................................33
IQ4-5-6000EV Gasket and Cutout.........................................................................................................................................34
IQ8-10-12000EV Gasket and Cutout..................................................................................................................................... 35
IQ14-17-20000EV Gasket and Cutout ................................................................................................................................... 36
Standard Warranty Policy........................................................................................................................................... 37

3
Introduction
Ice Qube computer and electronics enclosure cooling systems have been designed to provide a safe environment for
your equipment. Our cooling systems provide this environment by cooling and dehumidifying the enclosure that
houses your equipment while providing an efficient, modern, and aesthetically pleasing package requiring minimal
maintenance. Our closed-loop circulation design also protects your equipment from air-borne dust and contaminants
which may hinder your equipment operations and cause unnecessary downtime. Ice Qube offers various models of
cooling systems ranging in cooling capacity from 1,000 to 27,000 BTU per hour to provide air conditioning systems
for many of your environmental needs, including hazardous locations. Ice Qube cooling systems are available in top
and side mount packages.
Basic Unit Operation
The Ice Qube Thermal Management System (TMS) is a combination of several systems that function simultaneously
to maintain environmentally friendly conditions for your equipment within the enclosure. The three main thermal
related systems that we employ are the closed-loop cold air supply stream, the heat rejection air stream, and the
vapor-compression refrigeration system.
The closed-loop cold air supply stream circulates cold air from the Ice Qube TMS to your electronics enclosure.
This air returns to the Ice Qube TMS bringing with it unwanted heat and humidity from inside your enclosure. Heat
and humidity is then removed by a heat exchanger which is part of the vapor-compression refrigeration system.
At the heart of the vapor-compression refrigeration system is a quiet, energy efficient rotary compressor, which
circulates environmentally friendly NON-CFC refrigerant to transfer heat from the heat exchanger (evaporator)
located within the closed-loop air stream to a heat exchanger (condenser) located in the heat rejection air system. In
the heat rejection air stream, air is circulated from the ambient air surrounding the enclosure, through a filter, and
across the warm heat exchanger. Here, heat from the enclosure is transferred from the warm heat exchanger to the
heat rejection air stream and dissipated to the ambient air.
Condenser Heat
Rejection Air Stream
Evaporator Cold
Air Supply Stream

4
Preservation Instructions
Unpacking Inspection
Caution: It is recommended using gloves and protective eyewear when unpacking
Verify product is as identified on the packing list. Air conditioner should arrive banded to pallet in the proper
upright position. See arrows on packaging for verification. Any evidence of damage should be noted on the freight
bill. The freight carriers claim procedure should be followed. Ice Qube cannot accept responsibility for damages
that occur during shipping. If the shipping container was damaged or marred in any way, check for scratches,
dents, loose hardware, presence of oil or any other irregularities with the Ice Qube TMS.
Package Contents
Included in the shipment with the air conditioner will be:
1. Operation manual
2. Mounting hardware
3. Condenser air diverter plate
4. Standard master warranty
5. Ethernet controller manual (Optional)
6. Enclosure gasket (Pre-installed)
Handling
Ice Qube recommends that the unit remains in the proper upright position, as indicated on the shipping container.
The unit must remain upright for a minimum of 24 hours before initial operation to ensure oil has returned to the
compressor. Operation before the 24-hour time may cause compressor damage and shorten the life of the system.
Operation before this 24-hour period will void all warranties.
Storage
The storage space temperature should be in the range of -40 to 85°C (-40 to 185°F) in a non-condensing
environment.
HAZARDOUS LOCATIONS MODELS ONLY - CONDITIONS OF ACCEPTABILITY:
When installed in the end use equipment, the following considerations are to be examined:
1. The maximum operating temperature of the devices while subjected to the temperature test at a 60°C
ambient air temperature is in accordance with the temperature class of the below table:
Maximum Temperature
T-Code
Unit
120°C
T4A
IQ1-2-3-4-5-6-8-10-12000EV
160°C
T3C
IQ14-17-20000EV
2. The subject devices must be used within their Recognized “Ratings” and conditions of acceptability as
referenced in the User’s Manual.
3. Consideration is to be given to the Conditions of Acceptability specified in the individual recognitions
when these components are employed in the end-use equipment.

5
Pre-Installation Test
Before installing the Ice Qube system on your enclosure, Ice Qube recommends that the unit operates for 20-30
minutes to ensure it is functioning properly. Although the Ice Qube TMS has been tested at the factory, internal
damage may have occurred during shipping which may have not been apparent during the unpacking inspection.
1. Place the system on a solid base such as a workbench or table. Ensure that the weight of the unit will be
supported. Be sure to allow adequate space for airflow. The cold air supply stream and the heat rejection air
stream must not be restricted.
2. Check that the condenser air filter is in place.
3. Check the data tag for proper electrical requirements. The data tag lists the design voltage and amperage
requirements of the system. Verify that the electrical supply where the system will be connected has the
proper capacity. After noting the above, connect power from a properly grounded electrical connection.
The use of an extension cord is not recommended.
See Electrical Installation Instruction for wiring details. (Page 8)
Note: If any unusual noise or vibration is present during the testing procedure, immediately disconnect the power
and inspect the exterior of the unit for the cause of noise or vibration. If necessary, Contact Ice Qube
immediately to determine cause of the noise/vibration.
4. As soon as power is supplied to the system, the cool air evaporator blower will begin to operate. The
compressor and warm air condenser blower will not operate if the room air temperature is below 80°F
(27°C). This is due to the fact that the programmable controller has a factory set-point of 80°F (27°C). The
digital display on the face of the controller will be displaying room temperature. If the display is indicating
80°F (27°C) or warmer, the “Cool” status LED will flash for 3 ½ minutes before the compressor and the
warm air condenser blower will operate. If testing in low ambient conditions, the condenser fan may come
on for a few seconds and shut off. This is due to a low pressure switch that controls the condenser fan
operation. Once system pressure rises the condenser fan will begin to operate.
Note: If the display is indicating a temperature less than 80°F (27°C), adjust the set-point to a temperature lower
than the room temperature in order for the compressor and warm air condenser blower to operate. Refer to
Programming the Standard Controller in order to change the factory set points. (Page 11 )
5. With the compressor and both blowers functioning, allow the unit to operate for 20 to 30 minutes. This will
provide sufficient time for the vapor compression system to achieve equilibrium. Measure the cool air
outlet temperature with an accurate thermometer. For room temperatures above 70°F (22°C), the cool air
outlet temperature should be at least 10°F (6°C) colder than the air inlet temperature. Inlet air temperature
will be displayed on the programmable controller. In areas of high humidity or ambient temperature below
70°F (22°C), the temperature difference may be less than 10°F (6°C).
6. After completing the above check point, the Ice Qube TMS is ready to be mounted to your enclosure.

6
Preparing the Enclosure
Please read entire section before beginning installation. The Ice Qube TMS has been designed to be light in weight
for easy installation. Side mount units have been designed with a simple two stud alignment feature to make initial
fastening to the enclosure quick and easy. A few modifications must be made to your enclosure to provide proper air
flow, maintain enclosure integrity, and assure secure installation. Required modifications will vary with Ice Qube
TMS model.
1. Ensure the mounting surface and enclosure will support the weight of the Ice Qube TMS and will not
become unstable causing bodily harm or equipment damage. For units mounted on enclosure doors,
confirm hinges will support the weight of the Ice Qube TMS. Refer to individual specification drawings for
model weights.
2. Using the specification drawing, determine the ideal location to install the Ice Qube TMS on your
enclosure.
3. Upon deciding the installation location of the Ice Qube TMS on your enclosure, use the cutout drawing to
determine the necessary modifications to your enclosure surface needed to accommodate mounting of the
Ice Qube TMS. An Electronic copy is available at http://www.iceqube.com/downloads/specification-
drawings/
4. Ensure the Ice Qube TMS will be mounted level.
5. Ensure the inlet and outlet of the cold air stream will not be restricted by equipment or shelving within your
enclosure.
6. Check that the air flow of the warm air stream will not be affected or restricted.
7. Confirm the gasket is properly installed to the Ice Qube TMS. This gasket is required to create a seal
against your enclosure and will maintain enclosure integrity. (See Error! Reference source not found. and
Error! Reference source not found.)
Mechanical Installation Instruction
Caution: Protective safety clothing such as helmet, gloves, and steel toe shoes are recommended.
1. Position the Ice Qube TMS so that the two mounting studs are in alignment with the top two 3/8” (9.5mm)
or 1/2" (12.7mm) depending on model, holes in your enclosure surface.
2. Slide the Ice Qube TMS mounting studs through the 3/8” (9.5mm) or 1/2" (12.7mm) depending on model,
holes in your enclosure and check to see that all openings are aligned.
3. After checking that all opening and bolt holes are in alignment, assemble and tighten the (2) ¼”-20 or 3/8”-
16 nuts and (4, 6 or 8 depending on model) ¼”-20 x 1” bolts supplied with you Ice Qube TMS by hand.
Check to ensure gasket will properly seal the Ice Qube TMS to your enclosure.
4. Using a wrench, tighten the nuts and bolts until the gasket between the air conditioner and the enclosure is
compressed to a maximum thickness of 1/8” (3.175mm). Check the entire perimeter of the gasket/enclosure
interface for compression and seal.
5. The OPTIONAL purge connector is provided as a means to purge harmful gases out of the evaporator
compartment. This ¼” (6.35MM) O.D. push-to-connect fitting is for convenience only and is NOT
REQUIRED as a method of protection. All components are non-ignition source components and DO NOT
require purge protection from any source. (See Figure 2: Push-to-Connect Fitting)
6. The air diverter plate is shipped attached to the condenser outlet below the filter. The air diverter plate can
remain as installed, moved to either of the other 2 sides, or removed entirely for omnidirectional air flow.
7. OPTIONAL Connect external M6x12mm cabinet ground stud to secure earth ground (nut and wire
terminal are provided).
8. Mechanical installation is now complete. Continue with the electrical installation of the Ice Qube TMS.

7
Figure 1: Enclosure Installation
Figure 2: Push-to-Connect Fitting
Ambient Side
Enclosure Side

8
Electrical Installation Instruction
Please read the entire section before beginning the electrical installation of the Ice Qube TMS. Ice Qube air
conditioners have been designed for easy electrical power connection at one specific location on the enclosure side
of the Ice Qube TMS. Each Ice Qube TMS been designed to operate at a range of voltages and frequencies. See unit
label(s) for correct voltage and frequency for your model(s).
••WARNING: ELECTRICAL SHOCK AND EXPLOSION HAZARD••
Electrical connections should only be completed by a qualified technician. Compliance with all
safety and electrical codes are required. Contact local authority having jurisdiction as required. Do
not connect while the circuit is energized. Turn off circuit breaker and install lock out. The area is
to be free of ignitable concentration of gases.
Pre-Installation Checks
1. Check the air conditioner model label or specification for power requirements.
2. Check the designated air conditioner power supply for adequate and proper electrical power requirements.
3. Check that wire routing to the terminal box will not interfere with or become damaged by other
components.
Electrical Installation
1. Check that the air conditioner designated power supply is de-energized and locked out.
2. Locate terminal box on enclosure side of air conditioner.
3. Remove the (2) terminal box cover screws and remove the cover. (See Figure 3: Terminal Cover)
4. The terminal block will be used for power. (See Figure 4: Terminal Block)
5. Remove Dome Plug and route power cable through the 0.875” (22.23mm) hole. Recommended conductor
size is 14AWG. Use an approved strain relief to secure wires. (See Figure 3: Terminal Cover)
6. Connect from left to right, Line 1, Line 2 and Ground. (See Figure 5: Power Terminal Block)
7. Once power is securely connected, install terminal box cover, using the (2) screws.
Figure 3: Terminal Cover

9
Figure 4: Terminal Block
Figure 5: Power Terminal Block

10
Alarm Installation Instruction
Ice Qube offers an optional alarm output that is provided through an alarm relay. This option is a dry contact (no
voltage.) The alarm will be configured both normally open and normally closed. (X03) When the alarm output is
supplied, a 120”(3048mm) cable with 3 flying leads, Common (Black), Normally Open (White), and Normally
Closed (Red) will be installed. (See Figure 6: Alarm Output)
Pre-Installation Checks
1. Ensure that the power connected to the alarm wires is in an NEC approved Class 2 circuit.
2. Check that alarm wire routing from the unit will not interfere with or become damaged by other
components.
Alarm Installation
1. Check that both the air conditioner designated power supply and the alarm power supply is de-energized
and locked out.
2. Route alarm wire cable to the desired location. The alarm wires are 18AWG stranded copper conductors.
Figure 6: Alarm Output

11
Operating Your System
Once the Ice Qube TMS has been installed onto the enclosure and the power cable has been attached to a properly
grounded electrical connection with adequate voltage and current supply, the unit is ready for operation. As soon as
electrical power is supplied to the Ice Qube TMS, the cool air stream blower will start to operate. The blower will
run continuously so that the controller can monitor the enclosure’s internal temperature. The enclosure temperature
will be displayed on the face of the controller.
If the enclosure temperature is greater than the factory cooling set-point of 80°F (27°C), the “Cool” status LED will
flash. This indicates that the compressor’s automatic off cycle timer is working. The off cycle timer is factory set at
3 ½ minutes. At the end of the 3 ½ minutes, the compressor and the condenser air blower will begin to operate and
the cool LED will be steady. This signifies that the cooling system has begun operation to remove heat and humidity
from the enclosure. The model may take 20 to 30 minutes before it achieves full capacity.
If the heat load within the enclosure is less than the cooling capacity of the Ice Qube TMS, the temperature on the
digital display will begin to decrease. When the temperature inside the enclosure decreases 7°F (4°C) below the
“Cooling On” set-point, the compressor and condenser blower will cycle off. The cool air blower will continue to
operate, circulating air within the enclosure. The controller has a factory programmed temperature differential of 7°F
(4°C). Example: “Cooling On” @ 80°F (27°C); “Cooling Off” @ 73°F (23°C).
Ice Qube also offers an Internal Heat Output (IHO) which provides a heater located within the air conditioner for
ordinary locations only. If the enclosure temperature is below the factory heating set-point of 50°F (10°C), the heat
status LED will be lit. This indicates the heat relay has been energized and is providing power to the heater. There is
no time delay before heating begins. When the temperature of the enclosure rises 7°F (4°C) above the set-point, the
controller will de-energize the heat relay and cycle the heater off.
Note: There is a dead band programmed into the controller that prevents heating and cooling from operating
simultaneously.
Note: See the label of the air conditioner for maximum wattage requirement of the heater. (Ord. Loc. only)
Programming the Standard Controller
The digital controller has many features that may or may not be required for all applications. The controller has
been programmed at the factory with typical default settings for immediate system operation.
Please review the following default settings:
1. Cooling system on temperature 80°F (27°C)
2. Heating system on temperature 50°F (10°C); optional (Ord Loc Only)
3. High enclosure temperature alarm 100°F (38°C)
4. Low enclosure temperature alarm 40°F (4.4°C)
5. Audible and Visual alarm ON
6. Digital display in degrees Fahrenheit
7. Filter maintenance alarm 0 days –Disabled
8. High condenser temperature alarm 170°F (77°C)

12
Figure 7: Standard Controller
To change the factory default settings, enter the programming code sequence below:
“1 Adjust-up” arrow
“2 Adjust-down” arrow
“3 Select”
“4 Exit”
After pressing the above sequence the program LED should illuminate along with three alternating flashing boxes
on the display face, indicating the code was accepted. If no selection is made within 1 minute, the controller returns
to the normal operating mode.
Note: Pressing the “4 Exit” button at any time while in the programming mode returns the controller to the
normal operating mode.
Press “3” to continue programming. The set temperature “HI”LED illuminates with the display indicating the
“Cooling On” Set-point. The compressor will begin operation at this temperature and will remain operating until the
enclosure temperature decreases approximately 7°F (4°C). Press “1”or “2” until the desired set-point is displayed.
The range for this adjustment is 70° to 126°F (21° to 52°C). When the adjustment is complete, press “3” to
continue.
The set temperature “LO” LED is on with the display indicating the optional “Heating On” set-point. The heating
system will begin operation at this temperature and remain operating until the enclosure temperature increases
approximately 7°F (4°C). Press “1”or “2” until the desired set point is displayed within a range of 0°F to 63°F (-
17.8°C to +17°C).
Notes: Heat is only available with Ordinary Location Units
Notes: Review alarm settings if the “Cool On” or “Heat on” set-points have been changed.
Press “3” to continue. The set alarm “HI” LED is on with the display indicating the high temperature alarm set-
point. The alarm will activate at this temperature and will automatically reset at 2°F (1°C) below this temperature.
Press “1” or “2” to change the alarm set-point within a range of 8°F (4°C) above the set temperature “HI” set-point,
to 131°F (55°C).
Press “3” to continue. The set alarm “LO” LED is on with the display indicating the low temperature alarm set
point. The alarm will activate at this temperature and will automatically reset at 2°F (1°C) above this temperature.
Press “1” or “2” to change the alarm set-point within a range of 8°F (4°C) above the set temperature “LO” set-point,
to -20°F (-29°C).
Press “3” to continue. The “Alarm”LED will flash and the display will show “ALL” indicating the “ALL” alarm
on/off status. Press “3” and the display will show either “ON” or “OFF”, indicating current alarm status. Press “1”
or “2” to toggle the mode as desired. If the “OFF” mode is selected, no alarms will activate and the audible on/off
select and POA, Power Off Alarm, functions are skipped.

13
Press “3” to continue. The “Audible” LED will flash and the display will show “AUD”, indicating the audible alarm
on/off status. Press “3” and the display shows “ON” or “OFF” indicating the current audible alarm status. Press “1”
or “2” to toggle the mode desired.
Press “3” to continue. The “Alarm” LED will flash and the display will show “POA”, indicating the Power Off
Alarm status. Press “3” and the display shows “ON” or “OFF” indicating the current alarm status. Press “1” or “2”
to toggle the mode desired.
(Version 3.18 and later only)
Press “3” to continue. The “C” LED will flash and the display will show either “F” for degrees Fahrenheit or “C”
for degrees Celsius. Press “1” or “2” to toggle the mode desired.
Press “3” to continue. The “Code” LED will flash and the display will show “PIN”. To set a new user PIN code,
press “1”. The display will flash “4”, prompting an entry of a four button sequence using the “1”, “2”, “3, and/or
“4” buttons. Any sequence of the four buttons may be programmed as the code. As the buttons are pressed, the
display will show the number of buttons that were pressed.
Note: After pressing a button, there will only be 5 seconds to press the next button. If the next button is not
pressed within the allotted time, the system will default to no PIN code, indicated by “0” on the display. Once the
sequence is entered the display will no longer flash, and will show “4”.
To program the no PIN code mode, press “2” and the display will show “0”, indicating no PIN code. With no PIN
code, pressing any button will permit access to the program.
•••CAUTION•••
ALWAYS RECORD THE SELECTION SEQUENCE (PIN CODE) AND STORE IN A SECURE PLACE
Press “3” to continue. The “filter” LED flashes and the display will show “FIL”, indicating the filter alarm day
quantity selection. Press “3” and the display will show the number of days that the alarm is set in half day
increments. Note that the alarm is based on compressor run time. (Example: 10.5 indicates that the alarm will
activate every ten and a half days or 252 hours of compressor run time.)
Press “1” or “2” to vary the desired number of days. Programming “0” days will disable the alarm.
Note: The required number of days to set this alarm will be determined by the ambient air conditions.
Press “3” to continue. The “Alarm” LED will flash and the display will show “Por” indicating the Power status. The
“Cool”, “Heat”, “Alarm”, and “Filter” LEDS will be flashing. Press “3” and the display shows “ON” or “OFF”
indicating the current power supply status to line voltage motor circuits. Press “1” or “2” arrow to toggle the mode
desired.
(Non-Hazardous Location models only, Version 3.18 and later)
Programming of the microprocessor is now complete. Press “3” to review all of the settings. Press “4” to enter the
selected settings and to return to the normal operating mode.
Note: if “4” is not pressed, any changes to the program settings will not be saved.

14
Programming the Ethernet Controller
Ice Qube offers an optional Ethernet controller. The Ethernet Thermal Management Center (ETMC) is an innovative
approach to monitoring and controlling the thermal equipment on electrical, electronic, and telecommunications
equipment. With the ETMC, it is easy to connect the thermal management equipment to a network anywhere there is
access to a node. Ice Qube ETMC has all the features of the standard digital controller, plus a user-friendly LCD
message center, expanded temperature and alarm ranges, improved functionality, and the capability to communicate
on an Ethernet network. For more information or questions concerning the ETMC contact Ice Qube technical
assistance.
Alarm Operation
1. The enclosure temperature is above or below the alarm set-point:
The “Alarm” LED will light, the display will flash, the “HI” or the “LO” LED will flash, and the audible
alarm sounds (if activated.) The enclosure temperature must rise or fall 2°F (1°C) before the alarm will
reset.
2. The condenser temperature is above the condenser alarm set-point:
The “Alarm” LED lights, the display flashes the condenser temperature, and the audible alarm sounds (if
activated.) the condenser temperature must fall 4°F (2°C) before the alarm will reset. The above alarms
can be manually reset by entering the PIN code into the system.
3. The filter day timer has expired:
The “Alarm” LED lights, the display flashes “FIL”, the “Filter” LED flashes with the display and the
audible alarm sounds (if activated.) The filter alarm may be cleared by pressing “4 Exit”.
4. The power is turned off:
The “Alarm” LED lights, and the display flashes “OFF” indicating someone has manually interrupted
power to the motors’ electrical circuits. This alarm will be rest when the Por “ON” has been selected in the
program menu. (Version 3.18 and later only)
5. Optional Alarm Output:
Ice Qube offers an optional dry contact alarm output (XO3) that provides both a normally open (close on
alarm) and a normally closed (open on alarm) set of contacts. This alarm signal is provided from a relay
through a 3 conductor cable (Black/Common, White/Normally Open, and Red/Normally Closed) passing through a
strain relief to the left of the internal controller.
6. Sensor Malfunctions:
E-O: Evaporator sensor open
E-C: Evaporator sensor shorted
C-O: Condenser sensor open
C-C: Condenser sensor shorted
Alternating E-O and C-O: Sensor connector disconnected
7. Incorrect Voltage Supply:
A continual flashing value of the program version (“3.1x” where x indicates current program version) on
the display screen indicates the supply voltage is either too high or too low.

15
Maintenance
The Ice Qube TMS is designed to provide many years of trouble-free operation with minimal amount of
maintenance. Primary maintenance consists of checking the condition of the ambient air filter and the condensate
management system.
1. Ambient Air Filter:
It is recommended that the ambient air filter be inspected and cleaned regularly: frequency will depend
upon ambient conditions. To check the condition of the air filter, it is recommended to remove electrical
power from the Ice Qube TMS. Next, locate the filter. Slide the filter from the internal filter rack through
the end slot and clean by soaking in warm soapy water. Rinse with clean water. Use a shop-vac to remove
excess water from the filter before returning it to the system. Replace the filter if it shows signs of
deterioration. See website for air filter cleaning demonstration at http://www.iceqube.com/ice-qube-tv/.
2. Condensate Management System:
The condensate management system should be checked periodically for scale, sludge and debris that may
cause the system to fail. The type of environment will determine the frequency of required maintenance.
Maintenance of the condensate management system will require access to the bottom of the air conditioner.
Removal of the neoprene tubing is necessary. Replacement of the tubing is recommended if it appears to
have internal build-up or has become brittle. Using a soft tube/pipe cleaner, insert into the drain nipple and
move in a circular motion to clear anything that may cause failure.
3. Cooling System Cabinet:
The cooling system cabinet may also need to be cleaned occasionally. To clean the system cabinet, simply
wipe it with a damp, lint free cloth. A mild soap solution may be used if necessary.
Trouble Shooting
Contact Ice Qube if the air conditioning system should fail to operate satisfactorily during the first year of operation.
DO NOT remove the cover without first notifying customer service. Removal of the cover will immediately void
the warranty.
If an operating problem should occur, please review the items outlined on the following page “Trouble Shooting
Check List.” If the problem persists, obtain model and serial number before contacting Ice Qube for technical
assistance.

16
Trouble Shooting Checklist
Model No:
Serial
Number:
Voltage Rating:
Amps:
Phase:
Frequency:
Options:
Is proper electrical power available at the power supply?
Yes
No
Is your power cord connected to the power supply and IQ terminal block?
Yes
No
Is the controller set-point temperature below the enclosure temperature?
Yes
No
Is the evaporator (cold air stream) blower operating?
Yes
No
Is the compressor and condenser (warm air stream) blower operating?
Yes
No
Is the enclosure door closed tightly?
Yes
No
Are all of the gaskets in place?
Yes
No
Has the condenser (warm air stream) filter been cleaned or changed
recently?
Yes
No
Is the system mounted level on the enclosure?
Yes
No
Is there adequate space within the enclosure for air flow?
Yes
No
Is there adequate space around the air conditioner for airflow?
Yes
No
Has the enclosure population remained the same?
Yes
No
Notes:
For additional support call:
Ice Qube at 1-888-867-8234
Please have above checklist completed before you call.

17
Schematic Wiring Diagrams
Ordinary Locations
120V/220V/230V
Figure 8
IQ350942 Rev A

18
Ordinary Locations
400V/460V/480V
Figure 9
IQ350943 Rev A

19
Hazardous Locations
120V/220V/230V
Figure 10
IQ350921 Rev A

20
Hazardous Locations
400V/460V/480V
Figure 11
IQ350922 Rev A
Other manuals for Evolution Series
1
This manual suits for next models
12
Table of contents
Other Ice Qube Air Conditioner manuals