Idex LIQUID CONTROLS HML210 User manual

Installation & Operation Manual
HML210 Converter
LCMag Electromagnetic Flowmeters
www.lcmeter.com
Installation

2
!!
!!
!WARNINGWARNING
WARNINGWARNING
WARNING
• Before using this product, read and understand the instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, installation, and
maintenance of equipment and/or systems in accordance with all applicable codes and ordinances.
• Failure to follow the instructions set forth in this publication could result in property damage, personal injury,
or death from fire and/or explosion, or other hazards that may be associated with this type of equipment.
Table of Contents
Publication Updates and Translations
The most current English versions of all Liquid Controls publications are available on our website, www.lcmeter.com.
It is the responsibility of the Local Distributor to provide the most current version of LC Manuals, Instructions, and
Specification Sheets in the required language of the country, or the language of the end user to which the products are
shipping . If there are questions about the language of any LC Manuals, Instructions, or Specification Sheets, please
contact your Local Distributor.
Introduction ................................................................ 3
Safety ......................................................................... 4
Technical Specifications ............................................. 5
Converter Dimensions ............................................... 6
Electrical Connections ............................................... 7
Wiring Instructions ..................................................... 8
Optional Modules ..................................................... 10
Digital Input .............................................................. 12
On/Off Digital Output Wiring .................................... 14
Converter Key Board ............................................... 15
Converter Display Screens ...................................... 16
Manufacturer Pre-Settings ....................................... 17
Security Levels......................................................... 18
Programming Functions ........................................... 19
1-SENSOR .................................................. 19
2-SCALES ................................................... 20
3-MEASURE ............................................... 23
4-ALARMS .................................................. 25
4-ALARMS (continued) ............................... 26
5-INPUTS .................................................... 26
6-OUTPUTS ................................................ 28
7-COMMUNICATION .................................. 30
8-DISPLAY .................................................. 30
9-DATA LOGGER ........................................ 31
10-DIAGNOSTIC......................................... 32
11-INTERNAL DATA.................................... 32
12 - BATCH ................................................. 33
Batch Programming ................................................. 34
Programming Menu Map ......................................... 36
Troubleshooting ....................................................... 38
Error messages and corrective actions to be taken38
Troubleshooting ....................................................... 39
Error messages when the converter is turned on. ... 39
Display flag description ............................................ 39
Continuity Test ......................................................... 41
Insulation Test .......................................................... 41
Appendix .................................................................. 42
Display Rotation ....................................................... 42
Notes ........................................................................ 43
Description Page Number Description Page Number

3
Introduction
Liquid Controls offers a broad selection of electromagnetic
(Mag) flow meters for industrial, water, and waste water
flow measurement applications, worldwide. The LCMag
family consists of seven sensor models for specific
applications. The models include micro-flow, wafer,
sanitary, flanged, pipe clamp, and insertion meters. The
units are offered in a wide variety of sizes, materials, and
flow ranges for many industrial and OEM applications.
The LCMag family of electromagnetic flow meters offers
the best solution for measuring the flow of electrically
conductive liquids (5µS/cm minimum), for the following
reasons:
• Accuracy is not affected by fluid characteristics such
as viscosity, density, temperature, or suspended
solids.
• No moving parts.
• Virtually no pressure drop.
• Clean-in-place construction (HMS501 and HMS2410
with remote converter only).
• Minimal maintenance.
• Easy to install and operate.
• Wide range of nominal diameters from 1/8" to 72".
• Wide range of flow rates from as low as 0.1 GPM to
as high as 400,000 GPM.
• Automatic, dual flow range capability.
• Broad selection of liners, electrode materials, and
process connections.
• High, full-scale accuracy, ±0.2% over a 10:1 range
(for liquid velocity greater than 4 ft/second) with some
sensor/converter combinations.
LCMag meters are available in a full selection of
configurations and sizes. Models are available in flow
ranges from 0.10 GPM to 400,000 GPM and in process
fittings from 1/8" NPT to 72" flanged meters and up to 80"
for insertion meters. Connections include flanged,
threaded, wafer, pipe clamp, and sanitary. A scaled, digital
pulse output is standard. A wide range of additional outputs
are available. These include: analog (0–20mA or 4–20mA)
serial (RS-232 or RS-485), relays, Profibus DP, additional
inputs, and data logger.
HML210 mounted on an HMS2500 Flange Sensor
The HML210 Converter is for use with all HMS series
flow sensors (except HMS600 and HMS5000). The
converter is a programmable, microprocessor-driven unit
providing automatic zeroing, EEPROM data protection on
loss of power, empty pipe detection, and self diagnostics.
The optional display matrix is 128 x 64, 8-line (16
characters per line) with three external membrane
programming keys.
Features
• Available with three external membrane programming
keys
• IP67 rating
• Available with an LCD display; 8 lines, 16 characters,
backlit
• Two digital outputs
• Four internal totalizers
• Panel mount configuration available
Accuracy
Capable of ±0.2% for liquid velocity > 4 ft/sec (with full
bore sensors)
Repeatability
Capable of 0.01% or better

4
Safety
Before applying power to the instrument please,
verify the following:
• Power supply voltage must correspond to that
specified on the name plate of the instrument.
• Electrical connections must be made as described
on pages 8-9.
• Ground connections must be correctly installed.
Periodically Verify:
• The integrity of the power supply cables, wiring, and
other connected electrical equipment.
• The integrity of the instrument’s housing. The
housing must not have any damage that could
compromise the environmental sealing.
• The torque setting of elements such as cable glands,
covers, etc. (Use supplied fittings if using hard
conduit).
• The integrity of the front panel, display, and keyboard.
Damage may compromise the environmental sealing.
• The mechanical attachment of the sensor to the pipe
and the converter mounted to a wall (for remote
converter mounting).
Grounding Instruction
For correct operation of the instrument, it is essential
that the sensor and the liquid are at the same electrical
potential. Always connect the sensor and converter to
a dedicated earth ground.
Always establish a reliable electrical connection to ground before using the instrument.
Verify that the supply voltage is the same as written on the nameplate of the converter.
Ensure that the power supply voltage is not connected to the outputs or to any terminals of terminal
blocks M1 or M2.
Carefully close the rear cover of the converter when the electrical connections are completed.
Do not open the converter’s rear cover when the power is on.
Avoid any attempt to repair the converter or sensor. If the system is not functioning properly, please
call the nearest authorized service center.
Legend
Dangerous voltage. Terminals identified by this symbol are subject to variable voltages that may exceed
60VDC and cause electric shock. Terminals 12 and 13 (page 7) have a 60VDC max with 250V spikes
during magnetic field switching.
Dangerous voltage. May cause severe electric shock.
General warning.
Caution.

5
Classification of the instrument:
• Class I Division 2, IP 67.
Environmental Specifications
•This instrument can be installed inside or outside of
buildings subject to the specifications indicated.
•Altitude: -650 to 19,680 feet (-200 to 6,000 m).
•Humidity range: 0 to 100% (IP 67, NEMA 6/6P).
Temperature Specifications
Ambient Temperature: -4º to 122ºF (-20º to 50ºC)
Input / Output Isolation
•Inputs and outputs are isolated up to 500V.
•The 4- 20mA analog output and the 24VDC output
are electrically connected.
Power Supply Versions Power Supply voltage Power Supply Frequency PMax Current Max
HV 90 to 265 VAC 44 to 66Hz 20W/25VA 0.25A
LV 18 to 45 VAC/DC 0-44 to 66Hz 20W/25VA 1.6A
LLV 10 to 35 VDC 20W 1.5A
Technical Specifications
Electrical Specifications

6
Integral (Compact) Mount Version. Remote Wall Mount Version.
Panel Mount Version
Converter Dimensions
Sensor Cover Pre-Amplifier

7
Electrical Connections
Terminal Block M1 For Panel Mount Versions
Terminal Block M1 For Integral and Remote Mount Versions

8
Wiring Instructions
Sensor to Converter Connection
There are several options for the Sensor to Converter
interface.
• HML210 Converter mounted integrally on the sensor
(compact).
• HML210 Converter mounted remotely from the
sensor (remote). This requires cable assemblies
C015 and C016.
• HML210 Converter mounted remotely from the
sensor in a panel (remote).
If the HML210 is mounted remotely from the sensor, the
following guidelines must be adhered to:
• Maximum distance from the HML210 to the sensor
is 30 ft for fluids with a conductivity less than 200µS
(micro siemens).
• Maximum distance from the HML210 to the sensor
is 65 ft for fluids with a conductivity greater than
200µS.
For applications where these conditions are not met, a
preamplifier is required. This mounts directly on top of
the sensor. With a preamplifier installed, the maximum
distance from the sensor to the HML210 is 1,640 ft
(500m).
NOTE: For proper installation, the cables must be ordered
with the unit. User supplied cables may void warranty
coverage and could affect the functioning of the meter.
Preamplifier Version
NOTE: Maximum length of cable C014 is 1,640 ft (500m).
!!
!!
!IMPORIMPOR
IMPORIMPOR
IMPORTT
TT
TANTANT
ANTANT
ANT
For North American Installations, the installation must be fully in accordance with the National Electrical Code (US)
or the Canadian Electrical Code respectively to maintain the hazardous location ratings on the product.
For European installations, the installation must be fully in accordance with EN60079-14 to maintain the hazardous
location ratings on the product. This may involve using special cable glands for all connections.
Sensor Converter Terminal Block M1

9
Wiring Instructions
Connecting Power to the Converter
As described in the Technical Specifications on page 5,
there are three different configurations for converter input
voltage. Before connecting the power source to the
converter, verify that the supply voltage falls within the
limits indicated on the converter nameplate.
•The power supply line must be equipped with an
external device for overload protection (10A
maximum fuse or circuit breaker).
•Ensure that a circuit breaker is installed in proximity
to the converter and is clearly identified and easily
accessible by the operator.
•Use only approved (fireproof) conductors for all field
wiring.
NOTE: The converter for DC power supply (10-35VDC)
is not protected against reverse polarity. Do not apply
reverse polarity voltage.

10
Optional Modules without Relays
Optional Modules
The module name is viewable when powering on the
converter.
•ME200: two programmable ON/OFF digital outputs.
(Option C)
•ME201: one programmable ON/OFF digital output
and one high frequency output. (Option D)
•ME202: one 0/4 to 20mA analog output and two
programmable ON/OFF digital outputs. (Option E)
•ME203: one RS-232 port and two programmable ON/
OFF digital outputs. (Option F)
•ME204: one RS-232 port, two programmable ON/
OFF digital outputs, and one 0/4 to 20mA analog
output. (Option G)
•ME220: Data logging module. (Option M)
Legend for RS-232 Communication
•SC: Cable shield, electrically connected to ground
and to the chassis.
•CTS: RS-232 Input “CLEAR TO SEND”.
•RD: RS-232 Input “RECEIVE DATA”.
•TD: RS-232 Output “TRANSMIT DATA”.
•SG: “SIGNAL GROUND” common to all signals of
the RS-232 port.
•C: “COLLECTOR” of the transistor + output.
• E: “EMITTER” of the transistor - output.

11
Digital Input
There are three types of digital input:
1. Functions assignable to digital input 1 only (page 12).
2. Functions that act directly on the inputs and
independently from the selected input (page 13).
3. Functions assignable to input 1 only and functions
assignable to input 2 only, which can affect each other
based on their current state.
NOTE: Activation of any Batch function automatically
disables other functions. A table describing the
relationships between these outputs is on page 34.
Optional Modules
•ME207: two relay outputs with one NO contact and
one NC contact each, 2A 250VAC, 60W/125Va.
(Option T).
Legend
•SC: Cable shield, electrically connected to ground
and to the chassis.
•C: Relay - common.
•NC: Normally closed contact.
•NO: Normally open contact.
Optional Modules with Relays

12
Digital Input
NOTE: Time T must be ≥to TMIN
Input Operation (Generic Functions)
Sampling TMIN HMS2500
Frequency
10Hz 220ms
20Hz 110ms 12"
50Hz 45ms 1" to 10"
80Hz 30ms
150Hz 15ms
Activate Auto-Calibration from a Remote Input
TMIN < T < 1 second = Autocalibration
T > 1 second = Autozero
Necessary conditions for this function to be enabled:
•Calibration enabled (10-DIAGNOSTIC menu).
•Batch on digital input 1 disabled (5-INPUTS menu).
•Batch on digital input 2 disabled (5-INPUTS menu).
NOTE: This feature should not be used for applications
with large viscosity variations.
Disable Totalizer from a Remote Input
Necessary conditions for this function to be enabled:
•Count lock enabled (5-INPUTS menu).
•Auto batch disabled (12-BATCH menu).
•Cons. mode disabled (12-BATCH menu).
Activate Range Change from a Remote Input
Necessary conditions for this function to be enabled:
•Range change enabled (5-INPUTS menu).
•Batch on digital input 2 disabled (5-INPUTS menu).
•Batch functions assigned to digital input 2 disabled.
•Out1, Out2, Out3, or Out4 batch end functions
assigned to digital output 2 and digital output 1 or 2 is
disabled (6-OUTPUTS menu).
Reset Totalizer from a Remote Input
Necessary conditions for this function to be enabled:
• One of the following must be enabled:
• T+ RESET (5-INPUTS menu).
• T- RESET (5-INPUTS menu).
• P+ RESET (5-INPUTS menu).
• P- RESET (5-INPUTS menu).
(It is recommended that only the partial totalizers P+/P- be
enabled to avoid losing continuous totalizer data.)

13
Digital Input
Input Operation on Inputs 1 and 2 (Batch Function)
Start Batch on Remote Input 1,
END BATCH on Out1 or Out4, Formula 00 or 01 on Remote Input 2
Inhibit Totalizer on Remote Input 1
Start, Resume, or Reset Batch on Remote Input 2
Inhibit Totalizer or Reset Totalizer on Remote Input 1
Start Batch on Remote Input 2 and Consent Mode to Enable Batch
Inhibit Totalizer always interrupts the batch. Pulsing
Input 2 again:
• T < 1 sec = resumes interrupted batch.
• 1 sec < T < 4 sec = starts a new batch.
NOTE: It is necessary to generate a new start pulse to
input 2 (T < 1 sec) to begin a new batch.
Necessary conditions for this function to be enabled:
•Count lock enabled (5-INPUTS menu).
•Out1 or Out4 on “END BATCH”.
•Batch function assigned to input 2 (option) enabled
(5-INPUTS menu).
•P+ RESET enabled (5-INPUTS menu).
Activation of the totalizer reset inhibit always interrupts
a batch. When reset T2 inhibit on input 1 completes,
input 1 resets the totalizer of the current batch. The
presence of an input signal on input 2, or a new pulse
signal on input 2 will start a new batch.
Necessary conditions for this function to be enabled:
•Count lock enabled (5-INPUTS menu).
•Batch function assigned to input 2 (option) enabled
(5-INPUTS menu).
•Cons.mode enabled (12-BATCH menu).
•P+ RESET enabled (5-INPUTS menu).
Necessary conditions for this function to be enabled:
•INP.2 enabled (optional module required).
•Out1 or Out4 set to “END BATCH”.
• Batch function with formula selection 00/01
assigned to input 2 (optional) enabled (5-INPUTS
menu).

14
On/Off Digital Output Wiring
Out 1/Out 2 Standard - Out 3/Out 4 with optional
modules
• Opto-isolated output with isolated collector and
emitter terminals.
• Maximum switching voltage: 40VDC.
• Maximum switching current: 100mA.
• Maximum saturation voltage between collector and
emitter @ 100mA: 1.2V.
• Maximum switching frequency (load on the collector
or emitter, RLMIN=470Ω, VOUT = 24VDC): 1,250Hz.
• Maximum reverse current on the input during an
accidental polarity reversal (VEC): 100mA.
• Isolation from other secondary circuits: 500VDC.
On/Off output wiring (Up to 10,000 Hz) (high
frequency): only with optional ME201 module
• Opto-isolated output with isolated collector and
emitter terminals. In order to get the maximum
performance, it is necessary to connect the emitter
to the common terminal of the outputs (0V), while
the load is on the collector. This output is internally
connected to the power supply source 24 VDC
available on the terminal block.
• Maximum switching voltage: 40VDC.
• Maximum switching current: 100mA.
• Maximum saturation voltage between collector and
emitter @ 100mA, load on the collector and internal
power supply: 0.3V.
• Maximum switching frequency, load on the collector
and internal power supply: (RLMIN=470Ω, VOUT =
24VDC): 1,250Hz.
• Maximum switching frequency, load on the emitter
or external power supply: (RLMIN=470Ω, VOUT =
24VDC): 10,000Hz.
• Isolation from other secondary circuits (except 24V
and 4 to 20mA outputs): 500VDC.
Technical Characteristics Analog Output (0-4/20
mA)
• Opto-isolated output.
• Maximum load 1,000Ω.
• Maximum voltage without load 27VDC.
• Refresh frequency is the same as the sample
frequency of the connected sensor.
• Protected against constant over voltage up to 30VDC.
The converter CHECK checks the load on the 4-20mA
output; to disable this function set the value mA Val. Fault
to “0” (4-ALARMS menu).
Circuit Characteristics:
Analog Output (0-4/20 mA)
On/off outputs wiring (Up to 1,250 HZ)
On/off outputs wiring (Up to 10,000 Hz)

15
Converter Key Board
The three keys of the converter programming keyboard
have the following functionality:
Short Press (< 1 Second):
• Increases the numeric value or the parameter
selected by the cursor.
• Goes to the previous item in the menu.
• Batch start/stop (when enabled).
Long Press (> 1 Second):
• Decreases the numeric value or the parameter
selected by the cursor.
• Goes to the next item in the menu.
Short Press (< 1 Second):
• Moves the cursor to the right in an input field.
• Goes to the next item in the menu.
• Change the display of the process data.
Long Press (> 1 Second):
• Moves the cursor to the left in an input field.
• Goes to the previous item in the menu.
Blind Converter Programming
For converters without a keyboard or display (blind
version), programming is accomplished using this
interface cable connected to a desktop or laptop
computer and running the interface software.
Access to the Instrument Key Board
Short Press (< 1 Second):
• Enters or exits the selected function.
• Enables the main menu for instrument configuration.
• Cancels the selected function in progress.
Long Press (> 1 Second):
• Exits the current menu.
• Enables the totalizer reset request (when enabled).
• Confirms/enables the selected function.
IF2, PC Interface

16
Converter Display Screens
Press to change the display.
!!
!!
!IMPORIMPOR
IMPORIMPOR
IMPORTT
TT
TANTANT
ANTANT
ANT
•Direct exposure of the converter display to sunlight could damage the liquid crystal display.
•To adjust the display Contrast setting, refer to page 29.
NOTE: The maximum number of digits shown on the
display is 9, independent of the number of decimal places
selected. Once this value is exceeded, totalizer count
resets to 0.
125
%
0
(1)0 s 10 Time scale
% full scale
Active scale
0.000
100 .
75 .
50 .
25 .
% 0 .
1 +
gal/m
100
75
50
25
% 0
30 s
0...20...40...60...80...100...120
Flowrate value and graphic
representation
Alarm indication
Scale: 1=low
2=high
Converter Display with
Currency Function Enabled
0.000
+0.00%
.000
0.00
1 +
gal/m
CTgal
USD
01/01/05 00:00
Currency value
% full scale bar graph
0.00
+
gal/m !1
Flow rate value
Scale in use
Flow direction
Unit of measure
Currency Total/gal
0.5797
+11.59%
2107.825
452.552
1 +
gal/m
10*
T-gal
P-gal
01/01/05 00:00
Flow totalizers;
continuous and partial;
Reverse Flow
0.5797
+11.59%
10657.749
3624.837
1 +
gal/m
10*
T+gal
P+gal
01/01/05 00:00
Flow rate value
% full scale
Date/time or alarm
Sampling rate
Flow totalizers;
continuous and partial;
Normal Flow

17
Manufacturer Pre-Settings
The converter is factory programmed and delivered with
the following standard configuration:
•Dip switches: ON (Switch position as shown below).
•Lock level: 3
•Keycode L2 = 11111
The 0-QUICK START menu shown above may display
different parameters from those shown after programming
the converter.
Factory Settings Access Codes
The information in this manual is related to all functions
available with the Keycode L2 access code. Functions
available at higher security levels are protected. These
are critical to operation and should only be adjusted with
proper guidance from factory personnel.
Access code description: Keycode L2 (11-INTERNAL
DATA menu).
A. With Keycode L2 set to 11111 the 0-QUICK START
menu may be accessed by pressing the key.
Main menu may then be accessed by entering the
Keycode L2 code of 11111.
B. With Keycode L2 set to 22222 (11-INTERNAL DATA
menu) the access code is not required. Pressing
the key advances the display to the MAIN
MENU.
CAUTION: This allows anyone access.
NOTE: The availability of any function is related to the
selected security level (see page 18).
C. With Keycode L2 set to a custom value (set by the
user) pressing the key prompts for the access
code to the MAIN MENU. The 0-QUICK START
menu will not appear.
NOTE: Remember to record the new code entered.
There is no way for the user to retrieve the code if it
is forgotten.
To enter the MAIN MENU from the 0-QUICK START
menu, position the cursor on the word Main menu and
press the key for less than one second. Enter the
Keycode L2 access code 11111 and press the key
for less than one second.
All the functions of the converter are now available, except
those reserved for factory personnel, which can only be
accessed with a different access code.
NOTE: All meters must have the Autozero Calibration
function performed once installed in line. Refer to page
19 for details.
When powered up with the above preset values, the
instrument will show one of the display screens described
on page 16. Press the key to access the 0-QUICK
START menu.
100.00
1.000
1.00000
0050.00
13
EN
0-QUICK START
Fs1=gal/m
Tot.MU=gal
Impl=gal
Tpul1=ms
Contrast=
Language=
Main menu
0-QUICK START
Descriptions appear on:
page 20
page 20
page 20
page 20
page 29
page 29

18
Setting Security Levels
Security Levels
To set the security level, follow the steps listed below:
• Set the dip switches in the OFF position (see picture
on page 17).
• Access the MAIN MENU.
• Press the key until the selection bar is on “11-
Internal data”.
• Press the key and then the key to scroll to
the function Lock level=.
• Press the key to access Lock level= and choose
the desired security level by pressing the key.
Confirm the choice by pressing the key.
• To enable the level of security selected, place the
DIP switches back to the original ON position (see
picture on page 17).
Security Level Options
Lock level 0: Completely disables access to the
functions. The following procedures may be accessed
through the keyboard:
• Changing the display mode.
• Batch Start/Stop (when the batch function is enabled).
• Printing data (when an RS-232 module is installed
and the function is enabled).
Lock level 1: Enables access to the following functions:
• Totalizer resetting.
• Batch function modifications.
NOTE: Lock level must be set to 1 for custody transfer
applications.
Lock level 2: Enables access to the following functions:
•0-QUICK START menu (Keycode L2 = 11111).
•2-SCALES menu with full access.
•8-DISPLAY menu with partial access.
•10-DIAGNOSTIC menu with partial access.
Lock level 3: Enables access to all the functions of Lock
level 2. When the Dip-switches are in the OFF
position, all the functions are accessible. Functions
requiring an access code higher than Lock level 2
are reserved for factory personnel.
NOTE: By setting the Lock level to 1and changing L2
to “22222”, the operator is locked out of programming.
However, simply turning off the lock switch allows easy
access to programming without the need to remember a
keycode.
Press or to scroll
through the fields, stopping on
Main menu.
Press to access
Keycode L2.
Enter the keycode using the
and keys and then
press . This advances
the display to the MAIN
MENU.
Press to access the 0-
Quick Start menu.
The MAIN MENU contains
twelve sub-menus. Access
these sub menus by scrolling
with the and the
keys and then pressing the
key.
As there are twelve sub-
menus accessible from the
MAIN MENU, and the display
contains eight lines maximum,
the screen will wrap around
when the bar reaches the
bottom or the top of the
display.
Accessing the MAIN MENU from the main display screen
is done by entering the Keycode L2 access code from
the 0-QUICK START menu. Follow the steps below to
gain access to the twelve sub-menus.
Main Menu Access
100.00
1.000
1.00000
0050.00
13
EN
00000
0-QUICK START
Fs1=gal/m
Tot.MU=gal
Impl=gal
Tpul1=ms
Contrast=
Language=
Keycode L2:
MAIN MENU
1-Sensor
2-Scales
3-Measure
4-Alarms
5-Inputs
6-Outputs
7-Communication
0.00
+0.00%
10657.749
3624.837
1 +
gal/m
10*
T+gal
P+gal
CURR.LOOP OPEN
Main Display Screen
0-Quick Start Menu
MAIN MENU
100.00
1.000
1.00000
0050.00
13
EN
0-QUICK START
Fs1=gal/m
Tot.MU=gal
Impl=gal
Tpul1=ms
Contrast=
Language=
Main menu
100.00
1.000
1.00000
0050.00
13
EN
11111
0-QUICK START
Fs1=gal/m
Tot.MU=gal
Impl=gal
Tpul1=ms
Contrast=
Language=
Keycode L2:
8-Display
9-Data logger
10-Diagnostic
11-Internal data
12-Batching

19
Programming Functions
ND=mm is the Nominal Diameter (in millimeters) for the
sensor. This value can be found on the sensor
nameplate. Enter this value using the keypad. Enter a
value between 3 and 2000 (1/8" to 80").
NOTE: If ND= is set to “0”, the display will show the
velocity of the liquid through the sensor, but the totalizers
will not be valid.
KA= represents the signal amplification value. It is
calculated during sensor calibration. This value is on
the sensor nameplate. Verify that this value matches
the one on the nameplate. If it doesn’t, enter the correct
value (between ±0.5000 to ±9.9999) using the keypad.
KL=+, KL=- are coefficients used for improving low end
accuracy of the sensor. These values are factory set
and should not be adjusted. The default value for both
of these fields is “0”.
Cable len.= is the length of the cable (in meters) used to
connect the converter to the sensor. The converter
accepts values in multiples of 10 meters. Enter a value
that represents this cable length. If the converter is
mounted directly to the sensor (compact), set this value
to “000”.
E.P.detect= is a function that enables the empty pipe
detection feature. To determine the empty/full pipe
condition, the signal is analyzed within a one second
window. This setting toggles between ON and OFF.
Select the desired option with the keypad.
NOTE: E.P. detect should remain off until a calibration
of this function is performed on site ad sidrected in
E.P.calibr.
1-SENSOR
When the converter detects an empty pipe condition, the
following occurs:
•“EMPTY PIPE”will display on the screen.
• An empty pipe alarm output will occur if assigned to
one of the outputs (Out1 or Out2).
• Flow rate indicator will show “0”.
• Flow totalizers will stop incrementing.
When the pipe fills again, EMPTY PIPE will disappear
from the screen, the alarm output will reset, flow rate will
display a flow rate, and the totalizers will continue
counting from where they left off.
Autozero cal. is used to initiate the automatic zero
calibration function.
NOTE: It is necessary to perform this function at start-
up or if the sensor has been empty for a long period
of time.
To perform automatic zero calibration, it is absolutely
necessary that the sensor be full of liquid and that the
liquid is not moving. Even minute movements of liquid
will affect autozero calibration and the accuracy of this
calibration. Once these conditions are obtained, proceed
with autozero calibration.
With the selection bar on Autozero cal. press .
Check to ensure that the percentage flow rate value
stabilizes around zero. If it does not, repeat the operation
again. When the value stabilizes around zero, press .
NOTE: If the unit does not stabilize around zero, check
to ensure the converter and sensor are properly
connected to a dedicated earth ground.
E.P.calibr.is used to calibrate the converter for the empty
pipe detection function.
Before performing empty pipe calibration, the sensor
must be completely filled with liquid so that the lining and
electrodes are wetted. The sensor then must be emptied.
When this is accomplished, press the key. The
display will replace E.P.calibr. with “EXECUTE?”. Press
the key to confirm the operation or to cancel
the operation. The display will flash “DONE”when it is
complete.
To enable this function after calibration, select E.P.detect
and change to “ON”.
00050
-01.8377
+00.0000
+00.0000
000
OFF
1-SENSOR
ND=mm
KA=
KL=+[0]
KL=-[0]
Cable len.=m
E.P.detect=
Autozero cal.
E.P.calibr.

20
Programming Functions
Fs1= is the full scale value for the sensor connected to
the converter. There are four fields to select to set this
parameter. From left to right these are:
1. Volume Unit of Measure (gal)
2. Type of Unit (/)
3. Time Unit of Measure (m)
4. Numeric Value of Full Scale Measure (099.99)
STEP 1: With the selection bar on Fs1, press to
gain access to the four fields. Move the cursor to “/”
using the key and press the key to change the
type of unit of measure. The options are metric, British
or American, mass, or volume units.
When scrolling through the four options, the following
will be displayed:
oz/ :select for non-metric mass units
l/ :select for metric volume units
kg/ :select for metric mass units
in³/ :select for non-metric volume units
Scroll to the desired option and press to accept the
value, to move to the next field, or to move to
the previous field.
STEP 2: Selection of the “/” field changes the options for
the unit of measure field. Selecting the time base field
changes the available options of the unit of measure field
as well. Therefore, after selection of the “/” field, set the
time base field by pressing once.
The options for time base are:
s:per second
m:per minute
h:per hour
d:per day
Make the selection and press twice to move to the
first field to set the unit of measure. The options available
are determined by the rate base and type of unit already
selected. The following tables contain the available units
of mass and volume.
STEP 3: With the three fields selected, proceed to
program the full scale value. Press to move to the
first digit of the numeric value representing full scale for
the sensor connected. Use to scroll through 0-9 for
each position. When the full scale value has been
entered, press to exit the field.
NOTE: The converter accepts any kind of combination
of units of measure satisfying both the following
conditions:
• Numeric field value i s ≤99999.
•1/25 fsmax ≤numeric field value ≤fsmax.
Where fsmax is the maximum full scale value
corresponding to the sensor, equal to a 10m/sec liquid
velocity.
NOTE: It is recommended that this value be set
approximately 10% above the desired maximum flow
rate. If the Fs1 value is reached, an alarm appears on
the display: “FLOW RATE>FS”.
2-SCALES
“kg/” Selection Options
g grams
kg kilograms
t tonnes
“in³/” Selection Options
in³ cubic inches
gal American gallons
GAL British gallons
ft³ cubic feet
bbl standard barrel
BBL oil barrel
yd³ cubic yards
kgl 1000 American gallons
KGL 1000 British gallons
“oz/” Selection Options
oz ounces
lb pounds
ton short tons
“l/” Selection Options
l litres
dm³ cubic decimeters
dal decaliters
hl hectoliters
m³ cubic meters
cm³ cubic centimeters
ml milliliters
099.99
1.000
1.00000
1.00000
0050.00
0050.00
01.0000
2-SCALES
Fs1=gal/m
Tot.MU=gal
Imp1=gal
Imp2=gal
Tpul1=ms
Tpul2=ms
Sg=kg/dm³
Table of contents