iLight Network
Termination
Connection
to the iLight
Network
Connection to
non-PoE port on
ethernet switch
Power Supply
+10 - 24V DC @ 750 mA Max
Device
Identication
Switch
Data LED
Status LED
Power Supply Jumper
Enables iLight Network BUS power when in the ‘ON’ position. Disables
iLight Network BUS power when removed or in the ‘OFF’ position.
Caution: This product requires 10-24V@750mA. When using the network
to power this device ensure adequate power is available on the network.
9850-000916--00
. E&OE.
Typical Connection Diagram
EG2-S
Ethernet Gateway
Status LED
Green LED ashes – device OK
Data LED
Red LED ashes when messages sent on network.
Device Identication
Press and release switch.
Sending a message to identify the device on the
network (red Data LED ashes)
Device LEDs and Buttons
iCAN network wiring
Cable connections to the iCAN network are made to
a removable 5-way connector block located on the
EG2-S
Function iCANnet Cable Colour
0V Black
CAN L Blue
Shield Silver
CAN H White
+V Red
+V CAN H SHIELD CAN L 0V
Maximum segment distance: 500m (1640 ft)
Devices per segment: 100 (without bridge or repeater)
Consult iLight for information on alternative cable
types.
IMPORTANT NOTE: Connecting a mains potential
cable to the iCAN Network terminals is likley to
damage the unit and other devices connected, and
invalidate warranty.
Network termination
EG2-S is supplied with termination
disabled as standard. If it is connected
as an end device on the iCAN network,
the jumper will need to be moved to
enable termination.
To enable termination, move the jumper
downwards from the top two pins to
the bottom two pins. Termination
OFF
Termination
ON