Isolite ELCD 1008 User manual

Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 1
Branch Circuit Emergency Lighting Transfer Switch
Compliance
Overview
The ELCD 1008 Branch Circuit Emergency Lighting Transfer Switch (BCELTS) transfers a single lighting
circuit from its normal power source to an emergency power source in the event of the loss of normal power or
an external trigger (e.g., fire alarm).
Front panel accessible push–and–hold Test
Switch
Front panel accessible Laser Test, enabling
remote testing with the use of a laser pointer (or
similar)
Front panel status indicators for Normal Power
(green) and Emergency Power(red)
Fire alarm dry contact input, which can be set for
normally open or normally closed operation
Auxiliary relay for 0–10V or Digital Addressable
Lighting Interface (DALI) control signals
The ECLD 1008 includes the following features
and functions:
UL Listed to UL1008 for Branch Circuit Emergency Transfer Switch Equipment
cUL Listed to CSAC22.2 Emergency Transfer Switch Equipment
UL Listed to UL2043 for plenum rated products
Complies with ANSI/ NFPA110, Standard for Emergency and Standby Power
Systems
The ELCD 1008 meets or exceeds the following regulatory standards:
Satisfies requirements of the National Electrical Code (NFPA70):
Article 700–Emergency Systems
Article 701–Legally Required Standby Systems
Article 702–Optional Standby Systems
Section 518.3(C)–Assembly Occupancies
Section 520.7–Theatres and Similar Locations
Section 540.11(C)–Motion Picture Projection Rooms
REMOTE TEST
NORMAL POWER
EMERGENCY POWER
TEST
WARNING More than one live circuit - disconnect all sources before
servicing.
Attention ll y a plus d’un circuit sous tension. Veuillez deconnecter
toutes les sources avant la maintenance.
CAUTION This switch will not transfer if the internal fuse(s) open due to a
fault.
Continuous load current not to exceed 100 percent of the switch rating.
Use Copper Wire Only 60/75C or greater conductors.
For use with Lighting Loads Only including Incandescent, Tungsten and
Electric Discharge Lamp.
120-277V, 50/60 Hz, 20 A Max. Load
Suitable for installation in air handling spaces (plenums)
UL-2043 LISTED
Isolite2575 Metropolitan Drive, Trevose PA
ELCD-1008
Emergency Lighting UL-1008 Transfer Device
Suitable for 2 Wire Dimming
120-277VAC, 50/60Hz, 20A
BCELTS
Branch Circuit Emergency Lighting Transfer Switch
When protected by an internal fuse of the specific Manufacturer,
type and ampere rating as maked below, this transfer switch is
suitable for use in circuits capable of delivering the short circuit
current at the amximum voltage marked
Short Circuit Current Voltage Manufacturer Type Rating
10kA RMS Sym 480 Littelfuse Class G 30A
SLC
Specific Fuse Manufacturer and Type Listing
EMERGENCY TRANSFER
SWITCH
EMERGENCY TRANSFER
SWITCH
Branch Circuit Emergency
Lighting Transfer Switch
Emergency Lighting
Transfer Switch

Installation Requirements
Note:
Ambient Environment
•
Electrical Specification
Normal and Emergency Rated Operational Voltage Input
Load Rating
Transfer Initiation
Short Circuit Current Rating
Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 2
Install the ELCD 1008 in a location that is accessible by qualified personnel for testing of the transfer function
using either a laser pointer (or similar) or the on board test switch.
The ELCD 1008 installs to a flat surface, has four conduit entry locations, and has four mounting holes.
Mounting and conduit hardware are provided by others.
Suitable for use in other spaces used for environmental air (plenums) in accordance with
Article 300 of the National Electrical Code (NFPA70).
NEMA Type1 Enclosure suitable for installation location that conforms to the following ambient environment:
0–40°C, 5%–95% non–condensing humidity
Note:
Continuous load current not to exceed 100% of the switch rating.Use copper wire only, minimum
75°C conductors.
120–277 VAC +/-10%, 50/60Hz
Supports a continuous load of up to 20A for tungsten and resistive load types, and supports
electronic ballast loads of up to 16A (80% of the switch rating)
Continuous load current not to exceed 100% of the switch rating
When normal power is lost, meaning the voltage drops below 85VRMS, the unit transfers the output
load to the emergency power source.
When normal power is restored, meaning the voltage rises above 90VRMS, the unit transfers the
output load to the normal power source.
Short circuit capacity of 10kA

Fire Alarm Input
•
•
0–10V Auxiliary Output
Installation
Mounting and Conduit
ELCD 1008 Outline Drawing
Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 3
The Fire Alarm Input allows power transfer to the emergency power source (if emergency power is present)
when triggered by an external system.
Note:
This transfer is activated even when normal power is still present.
The contact input can be configured for normally open or normally closed operation using switch settings on the
control board. Normally open and normally closed refer to the normal operational state of the external circuit,
not to the de-energized state of the external relay.
When the contact input is triggered, the unit will transfer to the emergency power source.
When the contact input trigger is removed, the unit will transfer back to the normal power source, if present,
or will remain on emergency power until normal power is restored.
Note:
The fire alarm input functions with up to 1,000ft (300m) of 18AWG wire connected between the
input and the switch. Fire Alarm Inputs of up to 10 ELCD 1008 units can be wired together using a
single normally open or normally closed contact. See Fire Alarm Input on page 7 for details.
The 0– 10V Auxiliary Output provides an additional single pole relay that opens when the unit is in the
emergency state. This allows connection of 0– 10V or DALI ballasts that need the removal of the
control signal in order to illuminate at full in an emergency state.
Using the mounting holes in the bottom of the
enclosure, secure the ELCD 1008 enclosure to
a flat surface using four 1/4-20 mounting bolts or
screws (provided by others).
Four knockouts are provided on the side of the
enclosure. Install conduit fittings (provided by
others).
The ECLD1008 enclosure can be
r o t a t e d 9 0 ° , t o c ha n g e t h e
orientation as needed for the
installation.
The front cover has a legend
printed on both sides to insure
correct indication of status LEDs
and Test Switch.
Note:
8.00
9.00
8.50
9.50
4x mounting holes
4x conduit
entry

Wire Terminations
Terminal W ire Ran ge St rip
Le ng t h
Torqu e
Rat ing
10 –18 A W G (cop per w ire 3/ 8”
Line / Load / Term inals 1–8 10 in–lbs
solid/ stranded) (10m m )
Co ntrol (signal) / Term inals 9–12 10 –20 A W G (copper w i re
stranded only)
1/ 4”
(6m m ) 4 in–lbs
6– 14 A W G (cop per w ire 3/ 8”
Eart h Ground 35 in–lbs
solid/ stranded) (10m m )
Wire and Terminal Specifications
Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 4
The ELCD 1008 can accommodate installations that require a Simple Transfer of normal and
emergency power or more complex installations that utilize a Dimmed or Switched Load. See the
related instruction for your installation type. Additionally, the unit can accommodate installations that
utilize 0–10V Auxiliary Output control and for use with either normally open or normally-closed
operation.
WARNING: Before you begin pulling and terminating wire to the ELCD 1008 BCELTS
enclosure, make sure the main circuit breaker cabinet or other readily accessible input power
disconnect device for both normal and emergency power input is locked out and tagged out.
Enclosures installed without an accessible input power disconnect device cannot be serviced
or operated safely. Follow all local codes and restrictions. When the disconnect device is not
located near the installed enclosure, the disconnect must allow for proper lockout/tagout.
Power Supply
Power Supply
Emergency Input
Connections
Normal Input
Connections
Sense Circuit
Connections
Load Output
Connections
Earth Ground
Fire Alarm (contact input)
0-10V (relay)

Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 5
1. See Wire and Terminal Specifications for wire size, strip length, and terminal torque.
2. Terminate load wires.
a. Run a neutral and a hot load wire through conduit to the load position for the load to be
transferred from the ELCD 1008.
b. Terminate to the respective terminals LOAD 2N (neutral) and LOAD 1H (hot) in the ECLD 1008
enclosure, securing each terminal screw onto the wire.
3. Install normal sense jumpers.
a. Install a jumper wire between terminals SENSE 3H
(hot) and NORMAL 5H (hot).
b. Install a jumper wire between SENSE 4N (neutral) and
Normal 6N (neutral).
4. Terminate normal power wires.
a. Run a neutral and a hot wire through conduit from the
normal power source to the ELCD 1008.
b. Terminate the neutral wire to the NORMAL 6N
(neutral) terminal and secure the terminal screw onto
the wire and the jumper fork terminal.
c. Terminate the hot wire to the NORMAL 5H (hot)
terminal and secure the terminal screw onto the wire
and the jumper fork terminal.
5. Terminate emergency power wires.
a. Run a neutral and a hot wire through conduit from the emergency power
source to the ELCD 1008.
b. Terminate to the respective terminals EMERGENCY 8N (neutral) and EMERGENCY 7H (hot)
in the ELCD 1008 enclosure, securing each terminal screw onto the wire.
See Wire and Terminal Specifications on Page 4 for specification of wire, strip length, and terminal
torque ratings, then prepare and terminate your earth ground wire to the lug provided in the enclosure.
A simple transfer installation would be used for a load that is intended to be always on. In the event of
loss of normal power, the load is transferred to the emergency power source but remains on. There is
no control over the load.
Earth Ground
Simple Transfer
SENSELOAD NORMAL EMERGENCY
H
2
N
4
H
5
N
6
H
7
N
3
1
H
8
NEmergency
power panel
Normal power
panel
Load
4
H
5
N
6
H
N
3
SENSE NORMAL
Step 3

Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 6
Note:
If using a separate neutral for the sense circuit, do not install the jumper. If using a three-wire
feed as shown above, install the jumper as described in step 3.
The ELCD 1008 has the ability to separate the sensing of normal power from the load itself; this allows you to
have a light switch or dimmer controlling the load when normal power is available, but to have the load transfer to
emergency power in the event of normal power loss.
The ELCD 1008 can be used with switched or dimmed power control.
Dimmed or Switched Load
1. See Wire and Terminal Specifications on page 4 for wire size, strip length, and terminal torque.
2. Terminate load wires.
a. Run a neutral and a hot load wire through conduit for the load to be transferred from the ELCD
1008 to the load position.
b. Terminate to the respective terminals LOAD 2N (neutral) and LOAD 1H (hot) in the ELCD 1008
enclosure, securing each terminal screw onto the wire.
3. Install a jumper wire between SENSE 4N (neutral) and Normal 6N (neutral).
4. Terminate normal power wires.
a. Run a neutral and a hot wire through conduit from the normal power source (controlled
dimmer or switch) to the ELCD 1008.
b. Terminate the neutral wire to the NORMAL 6N (neutral) terminal and secure the terminal
screw onto the wire and the jumper fork terminal.
c. Terminate the hot wire to the NORMAL 5H (hot) terminal and secure the terminal screw
onto the wire.
5. Terminate normal sense wire
. a. Run a hot sense wire from a non–controlled output of the normal power source through
conduit to the ELCD 1008.
b. Terminate to SENSE 3H (hot) in the ECLD 1008 enclosure, securing the terminal screw onto the
wire.
6. Terminate emergency power wires.
a. Run a neutral and a hot wire through conduit from the emergency power
source to the ELCD 1008.
b. Terminate to the respective terminals EMERGENCY 8N (neutral) and
EMERGENCY 7H (hot) in the ELCD 1008 enclosure, securing each terminal screw onto the wire.
SENSELOAD NORMAL EMERGENCY
H
2
N
4
H
5
N
6
H
7
N
3
1
H
8
N
dimmer
or
switch
Emergency
power panel
Normal power
panel
Load
see step 3 note

Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 7
Note:
The system supports connection of up to 10 ELCD 1008 units connected in
parallel to the fire alarm device.
The ELCD 1008 features a single pole auxiliary relay that provides switching for installations utilizing 0–10V or
Digital Addressable Lighting Interface (DALI) controls. In the event of an emergency, the relay opens the control
circuit, sending any connected loads to their full intensity output.
0-10V Auxiliary Output
Note:
All low–voltage Class 2 wiring must be separated from all Class 1 wiring. Follow local codes
and installation restrictions.
Isolite recommends limiting the distance run for the 0–10V control wiring from the
controller to the last ballast (driver) to 300ft, based on 18 AWG wire.
1. Run a +10V wire, typically purple, between the 0–10V controller and the 0–10V terminal 10 in the ELCD 1008
and secure the terminal onto the wire.
2. Run a +10V wire, typically purple, between 0–10V ballast and the 0–10V terminal 9 in the ELCD 1008 and
secure the terminal onto the wire.
3. Run a common wire, typically gray, between the 0–10V controller and the 0–10V ballast.
Fire Alarm Input
The ELCD 1008 features a single dry–contact input that can
be used to force the transfer from normal to emergency
state, even if both normal and emergency power are
present. The contact may be configured for either normally
closed (NC) or normally open (NO) operation by setting
switch 1 and 2 on the ELCD1008 control board.
1. Run a positive control wire between the fire alarm device
and the FIRE ALARM 11 “+” terminal in the ELCD 1008
and secure the terminal onto the wire.
2. Run a negative (common) control wire between the fire
alarm device and the FIRE ALARM terminal 12 “-”and
secure the terminal onto the wire.
3. Set the fire alarm contact input configuration switches for
either normally open or normally closed operation.
+ (purple wire)
+ (purple wire)
- (grey wire)
0-10V controller
0-10V ballast
9
10
0-10V
ELCD 1008
ELCD 1008
Connect up to
10 units
Fire Alarm
11
12
FIRE
ALARM
+
-
11
12
FIRE
ALARM
+
-
ON
FIRE
ALAR
M
S1-1 S1-2
12

LED St a t e s
Red
LED
Green
LED State Notes
Blink ing Off
Off Off
Ne ither norm a l nor em ergen cy
pow er are being supplied to the
unit .
If the LEDs are not lit as expected w hen
pow er is present, it is possible that one or
both of the internal fuses have blow n. See
Fu se Replacement on p age 9
Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 8
Final Installation and Power Up
1. Check that each termination point is
secure.
2. Check that the fire alarm contact input
switches are set for correct switch
operation, either normally open or
normally closed.
3. Clear all debris from the inside of the
enclosure.
4. Remove and discard the orange plastic
strip that is securing the relays in place.
5. Attach and secure the front cover to the
enclosure.
6. Apply both normal and emergency power
to the unit.
7. Test the operation of the ELCD 1008 as
described in Operation and Test below.
Operation and Test
It is important to test the ELCD 1008 regularly because it is a life safety device. NFPA 101 Life Safety code
requires testing of life safety devices every 30 days.
Test the ELCD1008 unit using either the test button or laser test as described in the following sections.
Step 4
On On
Normal and Emergency power are
both present. The ELCD 1008 is
supplying Normal power to the load.
Off On Normal power is present,
Emergency power is not.
This may be due to the loss of normal
power, the making of the fire alarm contact,
or the activation of the test mode
The ELCD 1008 is supplying Normal power
to the load and will not transfer
Blinking Blinking Relays are detected in an invalid
state.
If both LED’s are blinking, the ELCD 1008
relays need to be manually reset to a known
state. See Troubleshooting on page 10 for
details.
The ELCD 1008 is supplying
Emergency power to the load

Installation Guide
ELCD 1008
Isolite Corp 31 Waterloo Ave, Berwyn PA 9
WARNING: RISK OF ELECTRIC SHOCK! More than one live circuit is present
inside the enclosure. Make certain the main circuit breaker cabinet or other
readily accessible input power disconnect device for both Normal and
Emergency power input is locked out and tagged out before removing the cover
from this enclosure.
Note:
All low–voltage Class 2 wiring must be separated from all Class 1 wiring. Follow local
codes and installation restrictions.
Isolite recommends limiting the distance run for the 0–10V control wiring from the
controller to the last ballast (driver) to 300ft, based on 18 AWG wire.
Press and hold the “PUSH TO TEST” button to place the ELCD 1008 into emergency mode and transfer the
load from normal power to emergency power. The ELCD1008 remains in emergency mode until you release
the “PUSH TO TEST” button. If emergency power is not present for the test, the ELCD1008 will remain in
normal mode.
Test Button
Fuse Replacement
Directing a laser pointing device at the “REMOTE TEST” sensor located on the front of the ELCD 1008
enclosure places the ELCD 1008 into emergency mode and transfers the load from normal power to
emergency power. The ELCD1008 remains in emergency mode for 10 seconds and then returns to normal
mode. If emergency power is not present for the test, the ELCD 1008 will remain in normal mode.
Laser Test
In–line fuses are present for the normal power input and the emergency power input. Replace fuses only with
Class G SLC 30A fuses.
1. Disconnect both power supply sources and lock/tag out appropriately.
2. Loosen the four screws and remove the cover.
3. Use a voltmeter to test if the fuses are functional, and replace the ones that have failed.
4. Replace the cover to the enclosure.
5. Re-apply power from both sources and test the unit. See Operation and Test on page 8 for instructions on
testing the unit.

Installation Guide
ELCD 1008
Troubleshooting
When both of the ELCD 1008 LEDs are blinking, the relays need to be manually reset to a known state.
WARNING:RISK OF ELECTRIC SHOCK! More than one live circuit is present inside the
enclosure. Make certain the main circuit breaker cabinet or other readily accessible input
power disconnect device for both normal and emergency power input is locked out and
tagged out before removing the cover from this enclosure.
1. Disconnect both power supply sources and lock/tagout appropriately.
2. Loosen the four screws and remove the cover.
3. Locate the four relay switches near the
status LEDs.
4. Using a flat blade screwdriver, carefully
slide the relay switch to the left.
5. Repeat for all four relays in the ELCD 1008
enclosure.
6. Replace the cover to the enclosure.
7. Re-apply power from both sources and
retest the unit.
See Operation and Test on page 8 for
instructions on testing the unit.
Isolite Corp 31 Waterloo Ave, Berwyn PA 10
Table of contents