NOTES:
1. If the furnace is equipped with NOx screens and is to be
used with LP (propane) gas, the screens must be removed
prior to start-up.
2. Drip leg in the gas line must be installed.
3. The furnace controls require correct polarity on the power
supply and a proper ground.
4. Y & G must be connected to the control board for cooling
operation.
5. External filters are required on all configurations.
6. Electrical or gas entry is available on both casing sides.
7. To measure total static pressure, add supply duct pressure
to the return duct pressure, add pressure drop across the ‘A’
coil, and add pressure drop across the filter. Ignore negative
signs on the readings.
8. Inlet gas pressure should be 7” w.c. for natural gas and 11”
w.c. for propane. Nominal manifold gas pressure is 3.5” w.c.
for natural gas and 10” w.c. for propane at max. input.
9. For downflow application the vent blower must be rotated 90
left or right as shown.
†Other airflows are available. see Tech Guide for all CFM options.
* Cool Tap.
** Adjustment Tap.
LED INDICATOR
Slow Green Flash - Normal operation in standby mode.
Slow Amber Flash - Normal operation with call for cooling.
Two Amber Flashes - Normal operation with call for heat.
Three Amber Flashes - Normal operation, burner is on at end of
thermostat cycle.
Six Amber Flashes - Normal operation with call for heat pump
heating.
Any Red Flash - Fault condition. NOTE: 4 or 5 flashes may indi-
cate a blown fuse on the circuit board.
Models
Airflow CFM (Bottom Return without Filters) Minimum Wire
Size awg @ 75'
One-Way
Maximum
Over Current
Protection
0.5" ESP (Nominal)†
*D-A** *C-A** *B-A** *A-B**
TM9V060B12MP11 600 690 1000 1305 14 15
TM9V080B12MP11 600 680 1000 1290 14 15
TM9V080C16MP11 850 905 1175 1670 14 15
TM9V100C16MP11 870 910 1160 1655 14 15
TM9V100C20MP11 960 1155 1605 2215 12 20
TM9V120D20MP11 960 1160 1595 2180 12 20
Models Input
Rate Total Unit
Amps Air Temp. Rise
Max Input °F Air Temp. Rise
Min Input °F
Time For 1 ft3Natural Gas
(1030 Btu/Ft3) Seconds
(On Max. Rate)
Max Min
TM9V060B12MP11 60,000 21,000 9 35 - 65 35 - 65 62
TM9V080B12MP11 80,000 28,000 9 35 - 65 30 - 60 46
TM9V080C16MP11 80,000 28,000 12 35 - 65 35 - 65 46
TM9V100C16MP11 100,000 35,000 12 35 - 65 30 - 60 37
TM9V100C20MP11 100,000 35,000 14 35 - 65 35 - 65 37
TM9V120D20MP11 120,000 42,000 14 35 - 65 35 - 65 31
This document does not replace the installation instructions, which must be referred to for
detailed information.
CLEARANCES
* 24" clearance in front and 18" on side recommended for
service access.
All furnaces approved for alcove and attic installation.
DIMENSIONS
SUPPLY END RETURN END
LEFT SIDE
Combustion Air Inlet
Condensate Drain
(Downflow)
Vent Connection
Outlet
Thermostat
Wiring
29.5”
28.5”
RIGHT SIDE
Condensate Drain
(Downflow)
14”
1”
1.5”
23”
Combustion Air Inlet
Gas Pipe
Entry
Electrical
Entry
Condensate
Drain
Optional Return Air
Cutout (Either side)
FRONT
A
33”
Clips can be flipped
into the up position
for coil cabinet or
plenum attachment
A-COIL
Follow all national and local codes and standards in addition to this document.
The installation must comply with regulations of the serving gas supplier, local building,
heating, plumbing, and other codes. In absence of local codes, the installation must comply
with national codes and all authorities having jurisdiction.
B
24.25”
.56” .56” 20”
3”
23.8”
.56”
Combustion
Air Inlet
2” Diameter
Vent Connection
Outlet
B
DURING INSTALLATION,
DOORS MUST REMAIN ON
FURNACE WHEN MOVING
OR LIFTING.
Vent Connection
Outlet
Application Upflow Downflow Horizontal
Top 1" 0" 0"
Vent 0" 0" 0"
Rear 0" 0" 0"
Side 0" 0" 1"
Front* 0" 0" 0"
Floor Combustible Combustible1
1. For combustible floors only when used with special
sub-base.
Combustible
Closet Yes Yes Yes
Line Contact No No Yes
Cabinet Size A (in) B (in)
All 'B' Cabinet Furnaces 17-1/2" 16-3/8"
All 'C' Cabinet Furnaces 21" 19-7/8"
All 'D' Cabinet Furnaces 24-1/2" 23-3/8"
QUICK REFERENCE GUIDE
96%TWO STAGE MULTI-POSITION RESIDENTAL
GAS FURNACES (33” TALL)
Subject to change without notice. Printed in U.S.A. 438336-URG-A-0209
Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
*438336*
Furnace is multi-position and may be installed in any of the configurations shown.
Ensure that all PVC venting has at least 1/4” per foot slope towards the furnace.
The furnace condensate pan is self priming and contains an internal trap.
.Do not install an external condensate trap
When drain hose routing changes are required (shown in red), be sure to cap
all unused openings.
If rerouting hoses - excess length should be cut off so that no sagging loops will
collect and hold condensate, which will cause the furnace to not operate.
Move rain gutter hose
to this position.
HORIZONTAL LEFT
Move pressure switch
hose to this position.
NOTE: May require the
longer hose that is
provided with wider
cabinets.
Change condensate drain
connection to the 90° fitting provided.
Move condensate drain hose to this position.
Move rain gutter hose to this position
NOTE: May require hose extension that
is provided with wider cabinets.
UPFLOW
DOWNFLOW
Move condensate drain
hose to this position.
For downflow applications, the gas
valve must be rotated upwards.
Inducer must be rotated 90° in
either direction for this installation.
HORIZONTAL RIGHT
Move pressure switch
hose to this position.
Change condensate drain
connection to the 90° fitting provided. Move rain gutter hose
to this position.
Move condensate drain
hose to this position.
Move rain
gutter hose
to this position.
Move pressure switch
hose to this position.
NOTE: May require the
longer hose that is provided
with wider cabinets.
AIRFLOW
AIRFLOW
MOST COMMON INSTALLATION CONFIGURATIONS (MORE OPTIONS AVAILABLE WHICH IS COVERED IN THE INSTALLATION MANUAL)WITH INDUCER ROTATION,
Rain
Gutter
Hose
Pressure
Switch
Hose
Condensate
Drain Hose
For 100 & 120K input furnaces, the condensate
drain is factory set toward the left casing outlet.
For 060 & 080K input furnaces, the condensate
drain is factory set toward the right casing outlet.
MULTI-POSITION CONFIGURATION INFORMATION:
1
2
3
4
1
2
5
4
3
1
2
3
4
In upflow and downflow installation - Condensate drain hose may go out either side.
AIRFLOW
5
Move rain gutter hose
to this position.

This manual suits for next models

5

Other Johnson Controls Furnace manuals

Johnson Controls EBE23A User manual

Johnson Controls

Johnson Controls EBE23A User manual

Johnson Controls TG9S*MP User manual

Johnson Controls

Johnson Controls TG9S*MP User manual

Johnson Controls TM8X*MP Series User manual

Johnson Controls

Johnson Controls TM8X*MP Series User manual

Johnson Controls TM9X Quick setup guide

Johnson Controls

Johnson Controls TM9X Quick setup guide

Johnson Controls MM9E Series Guide

Johnson Controls

Johnson Controls MM9E Series Guide

Johnson Controls TM8X MP Series User manual

Johnson Controls

Johnson Controls TM8X MP Series User manual

Johnson Controls TM9X MP Series User manual

Johnson Controls

Johnson Controls TM9X MP Series User manual

Johnson Controls TM8T*MP User manual

Johnson Controls

Johnson Controls TM8T*MP User manual

Johnson Controls 33” Multi-position Gas Furnaces Guide

Johnson Controls

Johnson Controls 33” Multi-position Gas Furnaces Guide

Johnson Controls GG9S040A08MP11 Quick start guide

Johnson Controls

Johnson Controls GG9S040A08MP11 Quick start guide

Johnson Controls TM9E User manual

Johnson Controls

Johnson Controls TM9E User manual

Johnson Controls TM9V*MP User manual

Johnson Controls

Johnson Controls TM9V*MP User manual

Johnson Controls York EBE Series Manual

Johnson Controls

Johnson Controls York EBE Series Manual

Johnson Controls EB User manual

Johnson Controls

Johnson Controls EB User manual

Johnson Controls TG9S*MP User manual

Johnson Controls

Johnson Controls TG9S*MP User manual

Johnson Controls MG9S*MP User manual

Johnson Controls

Johnson Controls MG9S*MP User manual

Johnson Controls TM8M/TMLM*MP User manual

Johnson Controls

Johnson Controls TM8M/TMLM*MP User manual

Johnson Controls TM9T*MP User manual

Johnson Controls

Johnson Controls TM9T*MP User manual

Johnson Controls TM8V MP Series User manual

Johnson Controls

Johnson Controls TM8V MP Series User manual

Johnson Controls 33" Guide

Johnson Controls

Johnson Controls 33" Guide

Johnson Controls GG9S*MP User manual

Johnson Controls

Johnson Controls GG9S*MP User manual

Johnson Controls TP9C C User manual

Johnson Controls

Johnson Controls TP9C C User manual

Johnson Controls RL18 User manual

Johnson Controls

Johnson Controls RL18 User manual

Johnson Controls TM9T Guide

Johnson Controls

Johnson Controls TM9T Guide

Popular Furnace manuals by other brands

United States Stove ASHLEY AF1600E Owner's installation and operation manual

United States Stove

United States Stove ASHLEY AF1600E Owner's installation and operation manual

Bryant DELUXE 355AAV Product data

Bryant

Bryant DELUXE 355AAV Product data

Carrier DELUXE 58DXC Service and maintenance instruction

Carrier

Carrier DELUXE 58DXC Service and maintenance instruction

Bryant B Series Service and maintenance procedures

Bryant

Bryant B Series Service and maintenance procedures

Daikin DM97MC Service instructions

Daikin

Daikin DM97MC Service instructions

Napoleon HYBRID 100 Installation and operating instructions

Napoleon

Napoleon HYBRID 100 Installation and operating instructions

Carrier 58SB0B operating instructions

Carrier

Carrier 58SB0B operating instructions

Goodman GMEC80 manual

Goodman

Goodman GMEC80 manual

Steffes DLF30B Owner's and installer's manual

Steffes

Steffes DLF30B Owner's and installer's manual

Carrier 59SC2A Product data

Carrier

Carrier 59SC2A Product data

Harman SF1500A Installation & operating manual

Harman

Harman SF1500A Installation & operating manual

International comfort products N8MPN installation instructions

International comfort products

International comfort products N8MPN installation instructions

Lennox G50UH Series installation instructions

Lennox

Lennox G50UH Series installation instructions

Blue Summit BG961UHE installation instructions

Blue Summit

Blue Summit BG961UHE installation instructions

Lennox G60DF(X) Series installation instructions

Lennox

Lennox G60DF(X) Series installation instructions

Carrier 916SA Installation, start-up, operating and service and maintenance instructions

Carrier

Carrier 916SA Installation, start-up, operating and service and maintenance instructions

Ashley 1440E Owner's installation and operation manual

Ashley

Ashley 1440E Owner's installation and operation manual

Carrier FED B Series installation instructions

Carrier

Carrier FED B Series installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.