
10
SNA-Series Tankless Heater Installation
10/17/2014 Keltech • 215-1815 Rev. B; ECN 130011
Perform Operational Test No. 1
AEnsure the enclosure door is closed.
BSet the 3-pole switch or circuit breaker to the
ON Position.
C
Pull out the Emergency Stop Button, heater will
automatically perform a 6 second discharge
from the TepidGuard overshoot purge system.
Wait for purge cycle to complete.
E
Test water temperature and stability at
outlet by viewing the display. Controller
displays (in red) the temperature of water
exiting the heater.
F
Deactivate the shower or eyewash. The
flow sensor will electrically open contacts
and remove power from the elements and
controller so that the display is blank and
bank lights are off. Power light stays on.
D
When flow rate reaches approximately
1.5gpm, the flow sensor recognizes this
condition and begins the heating process.
When the flow sensor activates:
• Green bank energized lights illuminate on the
front bezel verifying power supply connection to
the heating elements via the solid-state relays.
• Element load lights may be solid or flash
in unison as heating elements modulate
depending on the hot water demand.
• Digital temperature controller shows water
temperature. Additional programming is
not necessary.
Located on the panel are 1 (36-63kW) or
2 (72kW-144kW) green ready lights. When
illuminated, the safety circuit is engaged
and ready for use.
Heaters installed in pump-and-well supplied
water systems may require an operating
pressure adjustment to a differential pressure
of approximately 10 psi. For example, if the
high limit pressure is 40 psi, adjust the low
limit pressure to 30 psi with the pressure
switch located on the supply pump.
Heater will not energize heating elements if the
inlet water temperature is equal to or greater than
the temperature set on the digital controller .
If the water flow exceeds maximum heating capacity of the heater, the temperature of water at the
outlet may be lower than the temperature selected on the controller. See Table 3 to determine maximum
temperature rise capabilities.
Maximum Temperature Rise (GPM & °F)
Low Flow Activation* (1.5gpm) High Flow Activation*(15 gpm)
Models
480/600V
kW Low/
High
2.5 gpm
ΔT °F
3 gpm
ΔT °F
5 gpm
ΔT °F
8 gpm
ΔT °F
15gpm
ΔT °F
20gpm
ΔT °F
25 gpm
ΔT °F
30gpm
ΔT °F
35gpm
ΔT °F
40 gpm
ΔT °F
45gpm
ΔT °F
50gpm
ΔT °F
SNA-363 12/36 33 27 16 10 16 12 10
SNA-543 18/54 49 41 25 15 25 18 15 12 10
SNA-633 24/63 57 57 29 20 29 22 17 15 12
SNA-723 27/72 73 61 37 23 32 24 19 16 14 10
SNA-1083 40/108 109 90 54 34 49 36 29 24 21 18 16 14
SNA-1263 47/126 128 106 64 40 57 43 34 28 24 21 19 17
SNA-1443 54/144 147 122 73 46 65 49 39 33 28 24 21 19
Maximum Temperature Rise (LPM & °C)
Low Flow Activation* (1.5gpm) High Flow Activation*(15 gpm)
Models
480/600V
kW Low/
High
9.5 lpm
ΔT °C
11.3 lpm
ΔT °C
18.9 lpm
ΔT °C
30.3 lpm
ΔT °C
56.7 lpm
ΔT °C
75.6 lpm
ΔT °C
94.5 lpm
ΔT °C
113.4 lpm
ΔT °C
132.5 lpm
ΔT °C
151 lpm
ΔT °C
170.3lpm
ΔT °C
189.3lpm
ΔT °C
SNA-363 12/36 18 15 9 6 9 7 6
SNA-543 18/54 27 23 10 8 14 10 8 7 6
SNA-633 24/63 32 32 16 11 16 12 9 8 7
SNA-723 27/72 40 34 21 13 18 13 11 9 8 6
SNA-1083 40/108 60 50 30 19 27 20 16 13 12 10 9 8
SNA-1263 47/126 71 59 36 22 32 24 19 16 13 21 11 9
SNA-1443 54/144 82 68 41 26 36 27 22 18 16 13 21 11
TABLE 3
…continued on next page