Setup of Boiler
1. Place boiler in desired position.
2. Place steel shims or bricks under each corner of boiler to allow an air space, to
prevent moisture from accumulating and rusting base of boiler. The brick should
stick out 2” Past each corner so the jacket has adequate support.
3. Using a level, plumb stoker end of the boiler, adding steel shims as necessary.
Failure to do this will change pitch on stoker unit and may have adverse effects
when burning coal.
4. Using a level, check top of boiler from side to side, adding shims as necessary to level
boiler. Do not place shims completely under boiler. Allow 1” to 2” of shims to extend
out from under the boiler. Shims are used as a base to set insulated jacket upon.
Chimney should be as per NFPA 211- 316 Stainless Steel Liner or Brick Lined and in good
condition, height requirement is 16 feet.
*For Canadian installation: as per NFPA 211- Chimney must be 304, 316, 404, 443 stainless
steel.
Supply & Return Piping System
The top of the boiler has at least 4 openings. The largest opening is the feed line to
your radiation. Since this outlet has a drop tube welded inside the boiler, you must
use for your radiation supply line. Even though it may be necessary to reduce down
to a smaller size, we recommend starting with 1 ¼” pipe and installing a
1 ¼” x 1 ¼” x 1” tee in supply line to be used for a by-pass loop. You may now make
your piping connections from feed outlet on boiler to flow valve.
You may use either of the large openings on the bottom of the stack end of the boiler as
your return. Select the side that will allow convenient access to the circulator for future
servicing. Install return piping and circulator, again referring to the location of by-pass loop.
The 1 ¼” x 1 ¼” x 1” tee must be installed below circulator. Refer to Diagram 1, page 25. The
circulator can be mounted to the feed line to push the water, instead of pulling the water if
it was installed on the return line.
Install by-pass loop as per ISO Plumbing Diagrams, page 24, with 1” pipe size. Place a tee,
1” x ½” F x 1”, in by-pass loop allowing the immersion well, for the 4006B Honeywell Hi-Limit
control, to extend into the full-water flow after its installed.
Over 50 years of installation experience has proven to us that the above-mentioned by-
pass loop is absolutely necessary for optimum performance of your heating system
Install a boiler drain valve in the other large opening at bottom of boiler.
Boiler Fill & Domestic Water Piping
1. Refer to Diagram 1, Pg. 28. Install ½” male adaptors in both fittings on domestic
water coil.
2. Install a ½” male adaptor onto the ½” fittings on the top of the end of the boiler to
be used for a boiler water fill.