-3-
§ ELECTRICAL CONNECTION!
1. Every installation requires an accessible
appropriate rated circuit breaker for future
maintenance. Leakage circuit breaker is also
required in the environment with high humidity.
2. Verify that the supply power voltage and HZ
match the inverter input requirements.
Electrical wiring shall be done in accordance
with the local electrical code by a competent
electrician.
!
!
3. The motor/pump will enter the running mode
automatically after the power ON. For any
failures caused by abnormal electrical power
supply, reset the inverter (disconnect the power
at least 1 minute, for the inverter LED display
off), and then set the power ON.!
4. Good ventilation for the control box is important
to prevent the overheating of inverter and
resulting failures.!
!
§ OPERATION PROCEDURE
1. Pump must be primed by feeding the pump
casing and suction pipe with water before
starting the pump to avoid damage of pump
parts, especially the mechanical seal.
◎For the pump with water supply above the
pump level, remove the pump priming plug,
and put it back securely when the water
overflow from pump priming hole. Vent any
air trapped in supply pipe or casing by
opening the valves in discharge pipe.
◎For the pump with water supply below the
pump level, remove the pump priming plug,
and fill the pump and suction pipe with
water. Any air trapped in suction pipe and
casing must be removed.!
2. Insert a screwdriver into motor shaft end, and
turn the shaft several turns clockwise to check
whether the pump can be rotated freely. If not,
disassemble and clean the pump chamber.
3. Double check the voltage and wiring of the
motor power and then turn the power switch ON.
Open faucet or water appliances on the
discharge piping side. The water should be
delivered after several seconds.
4. If the water does not be delivered after several
minutes, turn off the pump immediately. Repeat
step 2 to pour water into the pump and suction
piping, and switch power ON and OFF
continuously.
5. Once the water is pumped out, close and open
the water appliances on the discharge side
repeatedly to check automatic ON/OFF
operation.
6. When re-start the pump after long term shut
down, please repeat step1~5 to ensure the
normal operation.
§ OUTPUT HEAD SETTING
!
!
!
!
!
¾Step 1ĈMake sure that the inverter display is in
“Head Mode”. If not, press
key continuously until the “Head
Mode” is displayed.
¾Step 2ĈPress or continuously to
adjust the “Setting Head” shown on
the right screen Ą
¾Step 3ĈPress to save the setting.
!
CAUTION
Improper pressure setting will cause pump
failure. Pressure setting too high will fail to stop
while too low will fail to start.