Kilargo IFD44-LL Series User manual

Wall Mounted Systems
15 Wentworth Place, Banyo Qld 4014
T 1300 858 010 |F +61 7 3861 9266 |E [email protected] |www.kilargo.com.au
Step 1 Position damper centrally in penetration aperture as per system drawing with
IBS Backing Rod and temporary supports or packers.
Step 2 Apply Kilargo Intumescent Mastic (supplied separately) to the gaps between
the damper & building element. Ensure fill depth corresponds with those
detailed in the system drawing.
Step 3 Fasten mounting angles to damper with steel self-drilling screws or steel pop
rivets and, if detailed, to the building element with appropriate mechanical
fixings as per system drawing.
Step 4 Ensure product and certification labels are in a prominent position for easy
identification during subsequent maintenance inspections.
Step 5 Connect ductwork to the damper casing with AS 1682.2 compliant breakaway
joint.
IFD44-LL Series: Plasterboard
Installation Instructions:
Ducted
System Notes
• Grilles, louvres, IBS backing rod & fixings are to be supplied by others.
• Kilargo Intumescent Fire Dampers shall be installed in accordance with this detail,
including the use of Kilargo Intumescent Mastic and in accordance with the
requirements of AS1682.2.
• Ensure convenient access is provided for visual inspection and cleaning as necessary.
• 2mm Minimum gap allowable between damper and aperture. For gaps between
2-5mm, a fillet of Kilargo Intumescent Mastic shall be applied.
FRL -/90/-
System No. WP1 (a)
Building element: FR Plasterboard 1 x 16
Application: Mounted in casing DD / DG
Maximum size: 300 x 300 *without build up
FRL -/90/-
Test reference No. FAS200229
*Max size 1200 x 1200 if wall thickness is built
up locally with 100mm wide FR plasterboard to
a minimum thickness of 116mm
Duct to Duct Duct to Grille
Casing length on either
side of wall 150mm MAX.
8G x 50mm Steel Screw
Steel Tek Screw
Ductwork connected
to either side of casing
with AS1682.2 approved
breakaway joint
Kilargo Intumescent
fire damper fixed to
steel casing
Kilargo Intumescent
Mastic applied to entire
perimeter of IFD44-LL
damper (on both sides)
-2 per side for casing lengths up to 250mm
-3 per side for casing lengths 251-400mm
IBS Backing Rod
1 x 16mm FR plasterboard
both sides
Gaps between damper casing and
wall system firestopped with Kilargo
Intumescent Mastic 25mm deep.
Max fill 25mm
Minimum 0.7mm steel angles at least
twice the width of the penetration gap,
fixed to damper casing with steel screws,
bolts or pop rivets and fixed to wall with
steel fixings at maximum 150mm centre
spacing or:
0.7mm or greater
Z275 gal steel casing
positioned centrally
within aperture
Supporting noggings
fixed to vertical studs
Plasterboard penetration
lining optional
Kilargo IFD44-LL fixed into
ductwork with steel tek-screws
or pop rivets as follows:
Side Length Qty of Screws
0-100mm
101-250mm
251-400mm
401-600mm
1 set
2 sets
3 sets
4 sets
Casing length MAX 150mm
from face of the wall
Gaps between damper
casing and wall system
firestopped with Kilargo
Intumescent Mastic 50mm
deep. MAX gap 25mm
Kilargo IFD44-LL fixed into
ductwork with steel tek-screws
or pop rivets as follows:
Wall Mounted Systems
15 Wentworth Place, Banyo Qld 4014
T 1300 858 010 |F +61 7 3861 9266 |E [email protected] |www.kilargo.com.au
Wall Mounted Systems
Step 1 Apply Kilargo Intumescent Mastic to the opposing module.
Step 2 Align and bring modules together and mechanically fix together using U
channels and steel self-drilling screws or steel pop rivets with 2 sets of
screws at 150mm centres as per the modular system drawing on both sides.
Step 3 Fix modular damper to aperture or casing as shown in the appropriate
system drawing and installation instructions.
System Notes
• Fixings are to be supplied by others.
• Optional flat joining strips supplied at the time of order in lieu of U channel on request
for air transfer systems only.
1.50
20
30
U Channel
U Channel
2mm Kilargo
Intumescent
Mastic
IFD44-LL modules fixed together
using steel self drilling screws at
max. 150mm centre spacings
with 2 sets of screws
Galvanised Steel
U Channel 30mm x
20mm x 1.5mm
Frames spot welded together
and mastic applied to joint
IFD44-LL Series: Plasterboard
Installation Instructions:
Ducted - Modular
FRL -/90/-
System No. WP1 (b)
Building element: FR Plasterboard 1 x 16
Application: Mounted in casing DD / DG
Maximum size: 300 x 300 *without build up
FRL -/90/-
Test reference No. FAS200229
*Max size 1200 x 1200 if wall thickness is built
up locally with 100mm wide FR plasterboard to
a minimum thickness of 116mm
Note: To be read in conjunction with system
WP1 (a)

Popular Fan manuals by other brands

Eurapo UCS600 Operation and installation manual

Eurapo

Eurapo UCS600 Operation and installation manual

Sapir SP-1760-C user manual

Sapir

Sapir SP-1760-C user manual

Champion CHBF120 user manual

Champion

Champion CHBF120 user manual

Elta Select Multiflow SMB Installation and maintenance instructions

Elta Select

Elta Select Multiflow SMB Installation and maintenance instructions

Cairox ETALINE EC Series Assembly instruction

Cairox

Cairox ETALINE EC Series Assembly instruction

Maico PushPull PP 45 O Installation and commissioning instructions

Maico

Maico PushPull PP 45 O Installation and commissioning instructions

EVERCOOL EC1238A2LST specification

EVERCOOL

EVERCOOL EC1238A2LST specification

Monte Carlo Fan Company 5ED56WAD-L Series owner's manual

Monte Carlo Fan Company

Monte Carlo Fan Company 5ED56WAD-L Series owner's manual

Clas Ohlson SF-910B4 quick start guide

Clas Ohlson

Clas Ohlson SF-910B4 quick start guide

Sulion 075815 manual

Sulion

Sulion 075815 manual

Mietzsch VRE 560 Series User information

Mietzsch

Mietzsch VRE 560 Series User information

Air Row Fans F-18 Installation operation & maintenance

Air Row Fans

Air Row Fans F-18 Installation operation & maintenance

Stirling Black DL-20-4A quick start guide

Stirling

Stirling Black DL-20-4A quick start guide

Elta Compact SCP Installation and maintenance instructions

Elta

Elta Compact SCP Installation and maintenance instructions

KOSMEN KM-480DS manual

KOSMEN

KOSMEN KM-480DS manual

Ruck Ventilatoren RFA EC Series Assembly instruction

Ruck Ventilatoren

Ruck Ventilatoren RFA EC Series Assembly instruction

Ruck Ventilatoren MPC 30 Series instructions

Ruck Ventilatoren

Ruck Ventilatoren MPC 30 Series instructions

DOSPEL TWIST 160 user manual

DOSPEL

DOSPEL TWIST 160 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.