
KYRAD30SIUNITCOND
41
A73022660 EN
The user must never change the unit’s power cable. If the cable gets
damaged,switch off the unit and have it changed solely by professionally
qualified personnel. If changing the electric power cable, use solely
“HAR H05 VV-F” 3x0.75mm2 cable with a maximum outside diameter of
8 mm.
Room thermostat (optional)(remove the existing bridge terminals 17-18)
IMPORTANT: THE ROOM THERMOSTAT MUST HAVE VOLT-
AGE-FREECONTACTS. CONNECTING 230 V TO THE ROOM THER-
MOSTAT TERMINALS WILL PERMANENTLY DAMAGE THE ELEC-
TRONIC BOARD.
When connecting time controls or a timer, do not take the power supply
forthese devices from their breaking contacts Their power supply must
be bymeans of direct connection from the mains or with batteries, de-
pending on thekind of device.a las pilas, según el tipo de dispositivo.
Accessing the electrical terminal block
Undo the two screws “A” located on the top part of the control panel and remove
thecover.
fig.22 - Accessing the terminal block
3.6 Connection to the flue
The unit must be connected to a flue designed and built in compliance with the cur-
rentregulations. The pipe between the boiler and flue must be made from material
suitablefor the purpose, i.e. heat and corrosion resistant. Ensure the seal at the
joints. At the points of union it is recommended to check the tightness and thermally
insulate the entire duct between the boiler and chimney, in order to avoid the forma-
tion of condensation.
3.7 Condensate drain connection
The unit’s condensate drain must be connected to a suitable disposal system. Com-
plywith the specific local and national regulations on discharging condensate water
into thewaste water disposal system. For boilers not using exclusively low-sulphur
gas oil (Scontent<50 ppm) make sure to provide for a suitable condensate neutral-
isation device.
Connect the condensate drain pipe located at the back of the boiler (fig.25) to the
neutralisation device connected to the waste water system. The condensate dis-
charge pipes must be acidproof and installed sloping at least 3° towards the drain,
with-out any constrictions and obstructions.
IMPORTANT. Fill the trap with water before starting the unit.
Verify. Periodically check the water in the trap.
fig.23 - Condensate drain
4. SERVICE AND MAINTENANCE
All adjustment, conversion, commissioning and maintenance operations described
below must only be carried out by Qualified Personnel (meeting the professional
technical requirements prescribed by current regulations) such as those of the Local
After-Sales Technical Service.
LAMBORGHINI declines any liability for damage and/or injury caused by unquali-
fied and un-authorised persons tampering with the unit.
4.1 Adjustments
TEST mode activation
Press the heating buttons (details 3 and 4 - fig.1) together for 5 seconds to activate
theTEST mode. The boiler switches on irrespective of the system or DHW request.
The heating symbol (detail 24 - fig.1) and DHW symbol (detail 12 - fig.1) flash on
thedisplay. (In case of configuration for DHW)
fig.24 - TEST mode
To deactivate the Test mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes.
Burner adjustment
The burner is factory-set as given in table4. The burner can be set to a different
outputby acting on the pump pressure, nozzle, head adjustment, and air adjustment
as per thefollowing paragraphs. In any case, the new adjusted output must fall within
the boiler’snominal operating range. After making any adjustments, using a com-
bustion analysercheck that the CO2 content in the fumes is between 11% and 12%.
Nozzle flow rate table for oil
Table 2 gives the oil flow rates (in kg/h) according to the change in pump pressure
and nozzles.
N.B. - The values given below are only approximate, since nozzle flow rates can
vary by± 5%. Also, with burners having a preheater, the fuel flow rate decreases by
about 10%.
Table. 2
Pump pressure (bar)
NOZZLE
G.P.H. 8 9 10 11 12 13 14
0,40 1,32 1,40 1,47 1,54 1,61 1,68 1,75
16,6 16,6 17,43 18,26 19,09 19,92 20,75
0,50 1,57 1,65 1,73 1,81 1,89 1,97 2,05
18,62 19,57 20,51 21,5 22,42 23,36 24,31
0,60 1,93 2,01 2,23 2,32 2,42 2,52 2,64
22,89 23,83 26,44 27,51 28,7 29,88 31,31
0,65 2,12 2,25 2,4 2,63 2,74 2,8 2,91
25,14 26,68 28,46 31,19 32,49 33,21 34,51
0,75 2,50 2,65 2,8 2,95 3,07 3,2 3,33
29,65 31,43 33,21 34,99 36,41 37,95 39,49
0,85 2,92 3,1 3,27 3,45 3,6 3,75 3,9
34,63 36,76 38,78 40,92 42,69 44,47 46,25
1,00 3,30 3,5 3,67 3,85 4,02 4,2
39,13 41,51 43,52 45,66 47,67 48,72 51,95
Flow rate at nozzle outlet in kg/h