
• 5 • Installation Manual • FLATAIR ADV2 IOM-MIL161E-0920-09/2020
F-Gas REGULATION
Operators of refrigeration equipment’s must comply with the obligations dened in:
- EU Regulation No 517/2014 on uorinated greenhouse gases
- EC 1005/2009 on substances that deplete the ozone layer
Non-compliance with these requirements is an oence and liable of nancial penalties.
Moreover, in case of problem it is mandatory to prove to the insurance company that the equip
ment complies with the F gas Regulation.
WARRANTY
The warranty of the unit is subject to the warranty denitions as agreed upon in the order. It is expected that the design and instal-
lation of the unit utilise good working practices. The warranty will be legally null and void if:
• Service and maintenance have not been executed in accordance with the regulations; repairs have not been carried out by LEN-
NOX personnel or have been implemented without prior written permission by LENNOX.
• Modications have been made to the equipment without prior written permission by LENNOX.
• Settings and protections have been modied without prior written permission by LENNOX.
• Non-original or other than the prescribed refrigerants or lubricants are used.
• The equipment has not been installed and/or connected in accordance with the installation instructions.
• The equipment is being used improperly, incorrectly, negligently or not in accordance with its nature and/or purpose.
• A ow protection device is not tted.
In these circumstances LENNOX is indemnied from any product liability claims from third parties.
In the event of a warranty claim the machine serial number and LENNOX order number must be quoted.
WARNING - All the technical and technological information contained in this manual, including any drawing and technical descrip-
tions provided by us, remain the property of LENNOX and must not be utilised (except in operation of this product),reproduced,
issued to or made available to third parties without the prior written agreement of LENNOX. The technical information and speci-
cations contained in this manual are for reference only. The manufacturer reserves the right to modify these without warning and
without obligation to modify equipment already sold.
SAFETY
It is essential to follow non exhaustive recommendations hereunder:
• Never work on a unit that is still energized.
• Anymanipulation (opening or closing) of a shut-o valvemust be carried out by a qualied and authorised engineer.These proce-
dures must be carried out with the unit shut-down.
• Never work on any of the electrical components, until the general power supply to the unit has been cut. During any maintenance
operations on the unit, lock the power supply circuit in the open position ahead of the machine. If the work is interrupted, check the
lock before resuming the work.
• WARNING: Even if the unit has been switched o, the power circuit remains energized, unless the unit or circuit disconnect
switch is open. Refer to the wiring diagram for further details.
• For some units, a separate 220V power supply may exist, check the electrical wiring for more information’s
• In case of maintenance operations on fans (grills replacement …) ensure that the power is shut o to avoid automatic restart.
• Before the opening of the refrigerant circuit, check the pressure with manometers or pressure sensors, and purge the circuit.
• Never leave a unit stopped with valves closed on the liquid line, refrigerant could be trapped and the pressure would rise.
• All installation parts must be maintained by the personnel in charge, in order to avoid material deterioration and injuries to people.
Faults and leaks must be repaired immediately. The authorized technician must have the responsibility to repair the fault immedia-
tely. Each time repairs have been carried out to the unit, the operation of the safety devices must be re-checked.
• Follow guidance and recommendations given in safety and machine standards such as EN378, ISO5149, etc.
• Do not use oxygen to purge lines or to pressurize a machine for any purpose. Oxygen gas reacts violently with oil, grease, and
other common substances.
• Never exceed the specied maximum operating pressures. Verify the allowable maximum high- and low-side test pressures by
• Checking the instructions in this manual and the pressures given on the unit name plate.
• Do not use air for leak testing. Use only refrigerant or dry nitrogen.
• Do not unweld or ame cut the refrigerant lines or any refrigerant circuit component until all refrigerant (liquid and vapour) has
been removed from rooftop. Traces of vapour should be displaced with dry air nitrogen. Refrigerant in contact with an open ame
produces toxic gases.
• Do not siphon refrigerant
• Avoid spilling liquid refrigerant on skin or splashing it into the eyes. Use safety goggles.Wash any spills from the skin with soap
and water. If liquid refrigerant enters the eyes, immediately and abundantly ush the eyes with water and consult a doctor.
SAFETY CODES & REGULATIONS