
17
Subprograms of the Heat function:
a) ifTbat in+Ths1 (temperature ofhot start 33°C)theinternal
air fan stays off. When Tbatin>Ths1 the fan starts, then
stops at Tbatin+Ths2 (temperature of hot stop 30°C),
b) if Tbatin+Tsh1 (temperature of external fan stop, 63°C)
the external air fan stops until Tbatin+Tsh2 (temperature
of new start-up, 58°C),
c) defrosting of external battery (evaporator): in heat
mode the external air fan and the inversion valve always
start before the compressor (except when defrosting) for
atime (tac) that can be adjusted from 30 sec toamaximum
of 180 sec. At the end of this time, just before the
compressor starts, the Tbat ex1 is read and memorised.
At every time interval (tsh) from the start of the heat cycle
(tsh 30 min.) Tbat ex is compared with Tbat ex1 and, if
the difference (∆Ths=Tbat ex1-Tbat ex) between the two
temperatures exceeds a value of 14°C, the defrosting
cycle is started. It consists of the following steps:
1 stopcompressorand external and internal air fans (the
partialization solenoid must be open;
2 after time td1 (60 sec.) the valve is de-energized;
3 after a time td2 (20 sec.) the compressor is started
again;
4 on reaching the external battery temperature of end
of defrosting Tbatt ex sf (25°C), or at the end of the
maximum defrosting time tms(9 min.) the compressor
is stopped;
5 aftertime td3 (50 sec.) the inversion valve is energized
again;
6 after time td4 (20 sec.) the heat cycle starts again.
If the difference ∆Ths=Tbat ex1-Tbat ex between the
two temperatures does not exceed a value of 14°C
then tsh resets and counting starts again. At every
time interval (tma) 120 minutes of continuous
operation in heating mode, the defrosting program
must be started only if the initial air temperature (T
bat ex1) was below a value of 0°C; tma resets every
time there is a defrosting due to tsh.
This timing must be reset every time tsh is reset (timing of
start of defrosting).
Active alarms: FS, HP, HTI, CF/RL, OF, TSF (see relative
paragraph). CF/RL + disabled during defrosting.
10.10 Programming timer and schedule
Programming includes n intervals of operation in 24h, shown
on the display in a clear and comprehensible way. The
operating modes are described in the instruction manual.
10.11 Operation of system for disposal of condensation
in cooling mode
When the air conditioner functions in heating mode, the
condensation that forms on the external battery (evaporator)
has to be drained from the device through the pipe. In cooling
mode, the condensation that forms on the internal battery,
however, is used to increase the output of the device through
its re-evaporation on the external battery (condenser). This
also makes it possible, for units designed for cooling only, to
eliminate the need for a condensation discharge system.
The devices that make this possible are, basically, the water
recycling pump and the discharge closure actuator. Through
the pump (that is active only in the cooling and dehumidifying
function), the condensation water is recycled with the aid of
a special distributor on the external condensing battery.
This heat exchanger is at high temperature and is struck by
a strong flow of air. Both these factors ensure that the water
evaporatesquickly, thus further cooling thebattery.The pump
is controlled by a float that signals the level of water in the
tank. In case of problems of operation of the pump there is a
second safety float that stops the device before the water
overflows.
To prevent movement of condensation due to excessive
speed of the air in the external battery, the electronic
mechanisms provide for switching over the external speed to
the minimum every time the pump is started.
In heating mode, as we have already seen, the water has to
drain out because it cannot be re-evaporated. The device
that enables this function consists of a thermoelectric
actuator connected to a lever with a rubber cap closing the
drain hole in the tank under the external battery. The opening
command is given by the electronic logic every time the
machine operates in heating mode.
Considering that the external airflow may contain large
amounts of small particles (insects, pollen, dust, etc.) it is
necessary, when performing maintenance, to clean the
condensation disposal system and all its parts (pump,
perforated distributor, battery).
11 Alarm signals
Theelectronicsystem installed on the air conditioner provides
for displaying a series of operating alarms that make it
possible to promptly identify any malfunctions or errors of
use by the user.
To prevent transitory problems from setting off an alarm, the
logic provides that the safety thresholds must be exceeded
three times in a period adjustable according to the parameter.
The following table summarises all the alarms, the relative
led signal (that blink in case of alarm) on the signal panel.
11.1 Tests of operation and diagnosis of possible
malfunctions
The program introduced in the microprocessor of this device
enables it to run a brief autotest to check that the machine
operates normally by starting the various internal parts.
To run the autotest proceed as follows:
- Power the machine.
- Use a sharp object to press the microkey under the hole
on the left of the panel for at least 10 sec.
- At the beginning and end of the procedure of autotest the
display shows the state of configuration of the machine
for a few seconds according to the following scheme:
red led (filter): off = UNICO;
on = UNICO HP (with heat pump);
green led (compr.): off = with correction of room temperature;
on = without correction of room temperature;
yellow led (timer): off = without correction of room temperature;
on = with correction of room temperature;
green led (power): off = stand-by in case of black-out;
on = restart in case of black-out.
- Check after a few seconds that the device heats normally
(if equipped with heat pump function) for about 2 minutes
and then, after a few seconds, functions for 2 minutes in
cooling mode. Before terminating the autotest the
electronic system controls normal operation of the
temperature sensors. If one of these is broken the
corresponding signal leds stay on for 20 sec. (see table
below).