
Page 19
9 - Operate unit and observe draft gauge reading. ReadĆ
ings will change as heat exchanger warms.
a. Take one reading immediately after startup.
b. Take a second reading after unit has reached steady
state (approximately 5 minutes). Both readings should
fall above the line shown in figure 24.
10- Compare readings to figure 24. Be sure to compare
only like readings (compare startup reading to startup
reading, then compare steady state reading to steady
state reading). ubtract the absolute steady state
readings from one another. This will be the pressure
differential. In order for the furna e to operate, the
larger negative must always be on the ombustion
air blower side of the swit h
Example - one side of the pressure switch reads .60"
and the other side of the pressure switch reads .10".
Pressure differential is .60" - .10"= .50"
The pressure differential should be greater
than 0.20" W.C.
(49.72Pa).
11- When test is complete, remove thermostat demand
and allow unit to cycle off.
12- Remove draft gauge and Tee. Reinstall pressure
switch sensing hose to left side of pressure switch.
If pressure switch does not close at start up or differential is
less than .20" the following should be checked.
1 - Restriction in exhaust and or intake vent.
2 - Pressure switch lines are routed correctly and for
damage.
3 - Condensate in pressure switch lines.
4 - Wiring of pressure switch to furnace.
5 - Blocked heat exchanger or leak in heat exchanger.
II-PLACEMENT AND INSTALLATION
Make sure unit is installed in accordance with installation
instructions and applicable codes.
A-PVC Joint Cementing Pro edure
WARNING
DANGER OF EXPLOSION! Fumes from PVC glue
may ignite during system he k. Remove spark
plug wire from ignition ontrol before 120V power
is applied. Re onne t wire after two minutes.
1 - Measure and cut vent pipe to desired length.
2 - Debur and chamfer end of pipe, removing any ridges
or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
3 - Clean and dry surfaces to be joined.
4 - Test fit joint and mark depth of fitting on outside of
pipe.
5 - Uniformly apply liberal coat of PVC primer for PVC or
AB cleaner for AB for at least 5 to 15 seconds to inĆ
side socket surface of fitting and male end of pipe to
depth of fitting socket. Remove puddles of primer before
applying cement.
6 - Promptly apply solvent cement to end of pipe and inĆ
side socket surface of fitting. Cement should be apĆ
plied lightly but uniformly to inside of socket. Take
care to keep excess cement out of socket. Apply secĆ
ond coat to end of pipe.
NOTE-Time is critical at this stage. Do not allow primer
to dry before applying cement.
7 - Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn pipe 1/4 turn during
assembly (but not after pipe is fully inserted) to distribĆ
ute cement evenly. Once joint is made, PVC may
swell. Hold joint together until bonded (approximately
20 seconds).
NOTE-Assembly should be completed within 20 secĆ
onds after last application of cement. Hammer blows
should not be used when inserting pipe.
8 - After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made joint will show a
bead around its entire perimeter. Any gaps may indiĆ
cate a defective assembly due to insufficient solvent.
9 - Handle joints carefully and support properly until comĆ
pletely set.
B-Venting Considerations
The thickness of construction through which vent/air intake
pipes may be installed is 24" (610mm) maximum and 3"
(76mm) minimum. If a G26 furnace replaces a furnace which
was commonly vented with another gas appliance, the size
of the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue prodĆ
ucts, the existing vent pipe may be oversized for the single
water heater or other appliance. The vent should be checked
for proper draw with the remaining appliance.
CAUTION
Insuffi ient ombustion air an ause heada hes,
nausea, dizziness or asphyxiation. Ex essive exĆ
posure to ontaminated ombustion air will result
in safety and performan e related problems.
Avoid exposure to the following substan es in the
ombustion air supply:
Permanent wave solutions;
Chlorinated waxes and leaners;
Chlorine base swimming pool hemi als;
Water softening hemi als;
De-i ing salts or hemi als;
Carbon tetra hloride;
Halogen type refrigerants;
Cleaning solvents (su h as per hloroethylene);
Printing inks, paint removers, varnishes, et .;
Hydro hlori a id;
Cements and glues;
Antistati fabri softeners for lothes dryers; and
Masonry a id washing materials.