
Page 5
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units, it shall be in-
stalled in parallel with, or on the upstream side of, cooling
units to avoid condensation in the heating compartment.
With a parallel ow arrangement, a damper (or other
means to control the ow of air) must adequately prevent
chilled air from entering the furnace (gure 3). If the damp-
er is manually operated, it must be equipped to prevent
operation of either the heating or the cooling unit, unless it
is in the full HEAT or COOL setting.
AIR HANDLER
GAS UNIT
Dampers
(open
operation only)
Dampers
(open during heating
operation only)
FURNACE INSTALLED PARALLEL
WITH COOLING COIL
FIGURE 3
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Elec-
tric Code, ANSI/NFPA No. 70. The National Electric Code
(ANSI/NFPA No. 70) is available from the following ad-
dress:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
NOTE - This furnace is designed for a minimum continu-
ous return air temperature of 60°F (16°C) or an intermittent
operation down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of
the Canadian Electrical Code Part I (CSA Standard C22.1)
and/or local codes.
CAUTION
Do not set thermostat below 60F (16C) in heating mode.
Setting below 60F (16C) reduces the number of heating
cycles. Damage to the unit may occur that is not covered
by the warranty.
The SLP98DFV furnace may be installed in alcoves, clos-
ets, attics, basements, garages, and utility rooms.
This furnace is not designed for installation in mobile
homes, recreational vehicles, or outdoors.
Never use an open ame to test for gas leaks. Check all
connections using a commercially available soap solution
made specically for leak detection.
Use of Furnace as Construction Heater
Lennox does not recommend the use of SLP98DFV units
as a construction heater during any phase of construc-
tion. Very low return air temperatures, harmful vapors and
operation of the unit with clogged or misplaced lters will
damage the unit.
SLP98DFV units may be used for heating of buildings or
structures under construction, if the following conditions
are met:
• The vent system must be permanently installed per
these installation instructions.
• A room thermostat must control the furnace. The
use of xed jumpers that will provide continuous
heating is not allowed.
• The return air duct must be provided and sealed to
the furnace.
• Return air temperature range between 60°F (16°C)
and 80°F (27°C) must be maintained.
• Air lters must be installed in the system and must
be maintained during construction.
• Air lters must be replaced upon construction com-
pletion.
• The input rate and temperature rise must be set per
the furnace rating plate.
• One hundred percent (100%) outdoor air must be
provided for combustion air requirements during
construction. Temporary ducting may supply out-
door air to the furnace. Do not connect duct directly
to the furnace.
• The furnace heat exchanger, components, duct
system, air lters and evaporator coils must be
thoroughly cleaned following nal construction
clean-up.
• All furnace operating conditions (including ignition,
input rate, temperature rise and venting) must be
veried according to these installation instructions.