manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Lennox
  6. •
  7. I/O System
  8. •
  9. Lennox ECOLEAN KP06 User manual

Lennox ECOLEAN KP06 User manual

Providing indoor climate comfort
JBUS/BMS INTERFACE - ECOLEAN
MUL33E-0904 09-2006
User manual
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
1/13
1.- ¿How is the net configured? (How many units can be connected, which are the combination, what is needed by the
interface?)
The purpose of this net is connecting one or more units Ecolean to a BMS system. To get this we use the interface KP06. Up to 8
units can be connected (depending sizes and characteristics), to an interface KP06. We can connect up to 15 KP06 to the net.
In each Ecolean unit, is necessary to install a BUS adapter to convert the control (TTL) system in a signal RS-485.
We can connect in the net different controllers (as Climatic, Ecolean), but in a KP06 we can connect only controllers of the same
type.
2. - ¿What can be controlled by this net?
With this system, we can manage the following options in each of Ecolean units:
- Select between OFF/STAND-BY/COOL/HEAT.
- Modify the cooling / heating setpoint
- Read the limitations in the unit, as the functioning of the heat pump, the maximum setpoint, and minimum setpoint. .
- Read all the alarm status.
- Read inlet water temperature , outlet water temperature, condensing temperature and outdoor temperature ( this last one only
if the unit is fitted with the dynamic setpoint option)
- Read inlet signals status (pressostats, water flow switch, thermal relays motor protections).
- Read the outlet signal status (compressor, fan, water pump ...).
3. - Fitting instructions.
It is necessary to include in every installation:
One Bus Adapter by each of the units
One KP06 at least by every 8 units
Bus Adapter will be delivered installed inside the Ecolean unit (electrical board), with the power supply taken from the general
power supply of the unit, and the control connection made. KP06 is delivered loose, for later installation in the most adequate
place.
KP06 nº1 KP06 nº2 KP06 nº3 KP06 nº15
( . . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
Ctrol 1
Ctrol 2
Ctrol 3
Ctrol 8
( . . . )
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
2/13
4. - Connections
This sample could be the Standard connection of a KP06 net with a BMS system with a RS485 connection. It is also possible to
connect with a BMS net or a computer provided with a RS232 connection, but in this case there can be only one KP06 and the
connection cannot be longer than 15 meters (see KP06 details for further details)
Connections between KP06
KP06 configuration
- Connection between the BMS system and the KP06 must be done
according the figure besides, taking into account the following
indications :
- The wiring has to be done according local normatives.
- Every KP06 have to be supplied with 230 Vac/50 Hz + PE
(15%). Use a cable with a 1.5 mm2 section.
- Maximum length of the RS485 net (from the BMS system to the
last) is 1.000 m.
- BMS connection is RS 485. It has to be connected to the port
RS 485 of BMS with every KP06 in parallel.
- It is advisable to use screened cable with a 0.5 mm2 for this
type of connection.
- Jumpers J8 y J9 of the connected KP06 to the Ecolean units should
be connected in 1-2 position.
- Switch SW2-1 of every KP06 should be in ON-OFF position, except
the last one that has to be in ON position.
- Switches SW1-7 y 8 is used to configurate the transmission speed
according the following table.
Configurate the other switches SW1 as the figure resides.
KP06 nº1 KP06 nº2 KP06 nº15( . . . . . )
Bauds 1200 2400 4800 9600
SW1-7 ON ON OFF OFF
SW1-8 ON OFF ON OFF
RS 485
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
3/13
c) Connections between KP06 and Ecolean units.
- In every Ecolean unit there is a Bus Adapter. In this Bus Adapter a power supply connection has been done, as well
as the control connection in the Ecolean unit.
- Connection between KP06 and the Ecolean unit , has to be done as shows the figure taking into account the
following indications:
- Maximum length for the RS485 net (from the KP06 to the last ECOLEAN unit) is 2000 m.
- Wiring has to be done according the local normatives.
- Screened cable of 0.5 mm2 is advisable.
(for example cable model Belden 8762 with PVC isolation , cable plus metallic screen , 20 AWG, nominal capacity between cables of 89
pF, nominal capacity between a cable and the metallic screen of 161 pF)..
- Use the cables to connect + and - and the screen to connect GND.
- In each Bus Adapter of the last Ecolean, connect a 120 ohms resistance 1/4w between + and - .
- Each Ecolean unit connected to a KP06 has a different address between 1 and 8 .This address is introduced in the
controller.
Climatic 200
Units EAC 0091 to EAC 0812 and EAR 0091 to 0431
Parameter H26 protocol 1
Parameter H44 family address 0
Parameter H45 device address 1.8
Climatic 400
Units EAC 1003 to EAC 1303 and EAR 0472 to EAR 1303
Parameter H48 protocol 1
Parameter H65 family address 0
Parameter H66 device address 1.8.
- It is necessary configurate the KP06 to the RS485 net ( jumpers J14 and J16 in 1-2 position)
Ecolean nº1
Ecolean nº2
Ecolean nº8 ( . . . . . )
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
4/13
5.-Parameters
5. a Climatic 200
This controller is installed in EAC 0091 to EAC 0812 and EAR 0091 to 0431. This controller has the following map of standard
parameters.
/CHART 1/
/Logical parameters/
/Analogical parameters/
00H 2049 M/Pa_G01 G01-Cooling setpoint L/E
01H 2050 M/Pa_G02 G02-Heating setpoint L/E
02H 16468 M/MachineStatus Machine_Status L/E
80H 2052 Pa_H01 H01-Max setpoint in heating L
81H 2053 Pa_H02 H02-Min setpoint in heating L
82H 2054 Pa_H03 H03-Max setpoint in cooling L
83H 2055 Pa_H04 H04-Min setpoint in cooling L
84H 2079 Pa_H28 H28-HeatPump selecction L
85H 16415 ST1_MSB Inlet Temp : MSB L
86H 16416 ST1_LSB Inlet Temp : LSB L
87H 16417 ST2_MSB Oulet Temp : MSB L
88H 16418 ST2_LSB Outlet Temp : LSB L
89H 16419 ST3_MSB Piping : MSB L
8AH 16420 ST3_LSB Piping : LSB L
8BH 16421 ST4_MSB Outdoor temp : MSB L
8CH 16422 ST4_LSB Outdoor temp : LSB L
8DH 16483 Ana_Output Analog Output L
8EH 16404 Digit_Input Digit_Input L
8FH 16469 Digit_Output Digital Output L
90H 16492 Alarm_Auto_1 Alarm_Auto_1 L
91H 16493 Alarm_Auto_2 Alarm_Auto_2 L
92H 16494 Alarm_Auto_3 Alarm_Auto_3 L
93H 16495 Alarm_Manu_1 Alarm_Manu_1 L
94H 16496 Alarm_Manu_2 Alarm_Manu_2 L
95H 16497 Alarm_Manu_3 Alarm_Manu_3 L
96H 18433 Version VERSION L
5.b Detailed information about CLIMATIC 200 parameters
00H, 01H parameters (readable and writable)
This parameter defines the setpoint which the unit will function with , in cooling mode ( parameter 00 H ) or heating mode (
01H) .
¡Important : The value of the desired temperature has to be multiplied by 10!
Introduced values for this parameter have to be within the range between minimum setpoint ( Parameter 82 H cooling / 80 H
heating ) and the maximum setpoint ( Parameter 83 H cooling / 81 H heating ) .
¡Important: if the unit Works out of this range of temperatures , unit can work suffering critical damages !
If the unit is cooling only , there is no sense in using 01H parameter . This possibility can be restrained with the parameter 84 H
, which shows with the value 1 if the unit is heat pump version .
Example : H00=110 and H01=430 shows the cooling setpoint 11.0ºC and the heating setpoint 43.0ºC
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
5/13
02H parameter (readable and writable)
This parameter defines the functioning of the unit according the following :
Parameter 02H=00H ∧Stopped unit
Parameter 02H=04H ∧Stand- By mode
Parameter 02H=05H ∧Cooling only mode
Parameter 02H=06H ∧Heating pump mode
¡Important. If values different from 0 are used, they may appear wrong values!
To know if the unit can work as a heat pump , parameter 84 H has to be read.
¡Important : if in a cooling only unit , heat pump mode is demanded , unit can work suffering critical damages!
80H, 81H, 82H, 83H parameters (only readable)
Limits of cooling setpoint and heating setpoint:
80H ∧Maximum heating setpoint
81H ∧Minimum heating setpoint
82H ∧Maximum cooling setpoint
83H ∧Minimum cooling setpoint
Use these values to establish the limits values for the parameters 00H y 01H.
84H (only readable)
Shows a 0 value if the unit is cooling only , and a 1 value if the unit is heat pump .
Use these value to establish if it is posible to modif. The heating setpoint ( H01 parameter ) and it is more important to know if it
can be switched in heat pump mode ( H02 parameter)
85H, 86H, 87H, 88H, 89H, 8AH, 8BH, 8CH parameters (only readable)
In this parameters we can read the values measured by different temperature sensors of the unit.
85H ∧Water inlet temperature (MSB)
86H ∧Water inlet temperature (LSB)
87H ∧Water outlet temperature (MSB)
88H ∧Water outlet temperature (LSB)
89H ∧Refrigerant piping temperature (MSB)
8AH ∧Refrigerant piping temperature (LSB)
8BH ∧Outdoor temperature (MSB)
8CH ∧Outdoor temperature (LSB)
Nota: The outdoor temperature will only show the correct values if the outdoor temperature sensor is included. (dynamic
setpoint kit )
To calculate the value , we have to take into account the following value:
ºC·10= MSB·256 + LSB
Example : in 85H we can read value 1 and in 86H value 172. This means 1 * 256 + 172=428. The water indoor temperature
sensor is showing a value of 42.8ºC.
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
6/13
8DH, 8EH, 8FH Parameters (only readable)
In these parameters we can read the status of the different devices of the unit.
8DH ∧Analogical outputs (% fan speed)
8EH ∧Digital inputs ( pressostats, protections, remote on/off , remote cooling /heating )
8FH ∧Digital outputs (compressor , water pump, 4 way valve , antifreeze heater , alarm relay)
The correspondance with the different devices is as following :
In 8DH parameter fan speed ( in %) is shown .
0: fan stopped
100: maximum fan speed,
Intermediate values: fan in regulation
In FP2 version , this parameter only take values 0 and 10
Parameter 8EH shows the different digital inputs according the models as shown in the table below. ( 1 means closed contact
and 0 means open contact) .
EAC 0091 to 0431
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Low pressure
switch
High
pressure
switch
Remote
ON/OFF
Compressor
protection
Flor switch Not used Not used Not used
EAR 0091 to 0431
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Low pressure
switch
High
pressure
switch
Remote
ON/OFF
Compressor
protection
Flow switch Not used Not used Remote
cooling
/heating
EAC 0472 a 0812
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Low pressure
switch
High
pressure
switch
Remote
ON/OFF
Compressor
1 protection
Flow switch Not used Not used Compressor
protection 2
Example : in one unit EAC 0431 the value of 208 ( 1101 0000 in binary system) shows that the compressor protection , the high
pressure switch , and the low pressure switch are closed and that the remote ON/OFF plus the flow switch are opened.
With 8FH parameter we can see the functioning of the different components according models as shown in the following
table. ( 1 means functioning , 0 means stop, except the alarm relay that shows 1 when stopped or absence of alarm and shows 1
when the unit is functioning or there is an alarm)
EAC 0091 to 0431
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Not used Not used Not used Alarm relay Antifreeze
heater
Not used Water pump Compressor
EAR 0091 to 0431
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Not used Not used Not used Alarm relay Antifreeze
heater
4 way valve Water pump Compressor
EAC 0472 to 0812
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Not used Not used Not used Alarm relay Antifreeze
heater
Compressor
2
Water pump Compressor
1
Example : in a EAC 0431 unit , the value of 19 ( 0001 00 11 in binary system) shows that the compressor and the pump are
working , there is not alarm and the antifreeze heater is in off position.
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
7/13
90H, 91H, 92H, 93H, 94H, 95H parameters (only readable)
In these parameters the presence of an alarm is shown, and if it necessary , it can be restarted. 90H, 91H and 92H parameters,
show the alarm status ,and 93H, 94H and 95H show the necessity of restarting .
Alarm 90H restart 93H
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
E11 E43 E05 E04 E41 E02 E01 E00
Alarm 91H restart 94H
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
E46 E42 E07 E06 E40 E45 E44 E12
Alarm 92H restart 95H
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Not used Not used Not used Not used Not used Not used E13 E03
The meaning of these different alarm codes is the following :
• E00 ∧remote ON/OFF
• E01 ∧High pressure
• E02 ∧Low pressure
• E03 ∧Compressor overload relay
• E04 ∧Fan overload relay
• E05 ∧Antifreeze
• E06 ∧Error in outlet water sensor
• E07 ∧Error in refrigerant piping sensor
• E11 ∧Piping high temperature
• E12 ∧Piping low temperature
• E40 ∧Error in inlet water sensor
• E41 ∧Error in flow switch sensor
• E42 ∧Error in outdoor temperature sensor
• E43 ∧External antifreeze
• E44 ∧Unit without charge
• E45 ∧Configuration error
• E46 ∧High inlet water temperature
Some of these alarms may be not activated in your unit, or have slightly different meanings. In the unit manual you will see the
meaning of every of these alarms.
Example : if a high pressure alarm appears , 90H and 93H values will take then value 2 ( 0000 0000 in binary system) , when
the cause of the alarm is eliminated , ( restarting of the pressostat) , in 90H we will have then value 0 ( 0000 0000 in binary
system ) , but in 93H the value won´t change until we restart the alarm in the controller ( pressing reset button) .
96H parameter (readable only )
This parameter shows the current version of the control software.
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
8/13
5.c Standard Climatic 400 Chart
/CHART 1/
/Logical parameters/
80H 8193 I/ID1 Digital input I/ID1: L
81H 8194 I/ID2 Digital input I/ID2: L
82H 8195 I/ID3 Digital input I/ID3: L
83H 8196 I/ID4 Digital input I/ID4: L
84H 8197 I/ID5 Digital input I/ID5: L
85H 8198 I/ID6 Digital input I/ID6: L
86H 8199 I/ID7 Digital input I/ID7: L
87H 8200 I/ID8 Digital input I/ID8: L
88H 8201 I/ID9 Digital input I/ID9: L
89H 8202 I/ID10 Digital input I/ID10: L
8AH 8203 I/ID11 Digital input I/ID11: L
8BH 8204 I/ID12 Digital input I/ID12: L
8CH 8205 I/ID13 Digital input I/ID13: L
8DH 8206 I/ID14 Digital input I/ID14: L
8EH 8207 I/ID15 Digital input I/ID15: L
8FH 8208 I/IDST4 Digital input ST4: L
90H 10241 RL1 Relay1 - L
91H 10242 RL2 Relay2 - L
92H 10243 RL3 Relay3 - L
93H 10244 RL4 Relay4 - L
94H 10245 RL5 Relay5 - L
95H 10246 RL6 Relay6 - L
96H 10247 RL7 Relay7 - L
97H 10248 RL8 Relay8 - L
98H 10249 RL9 Relay9 - L
99H 10250 RL10 Relay10 - L
/Analogic parameters/
00H 2049 M/Pa_G01 G01-Cooling setpoint L/E
01H 2050 M/Pa_G02 G02-Heating setpoint L/E
02H 16495 M/MachineStatus Machine_Status L/E
80H 2051 Pa_H01 H01-Max setpoint in heating L
81H 2052 Pa_H02 H02-Min setpoint in heating L
82H 2053 Pa_H03 H03-Max setpoint in cooling L
83H 2054 Pa_H04 H04-Min setpoint in cooling L
84H 2060 Pa_H10 H10-HeatPump selecction L
85H 4097 I/ST1 Inlet temp L
86H 4098 I/ST2 Outlet Temp L
87H 4099 I/ST3 Piping circuit 1 L
88H 4100 I/ST4 Outdoor temp L
89H 4102 I/ST6 Piping circuit 2 L
8AH 16497 Hour_funct,[1]MSB Hours funct. Compresseur 1 x 256 h L
8BH 16498 Hour_funct,[1]LSB Hours funct. Compresseur 1 x 1h L
8CH 16499 Hour_funct,[2]MSB Hours funct. Compresseur 2 x 256 h L
8DH 16500 Hour_funct,[2]LSB Hours funct. Compresseur 2 x 1h L
8EH 16501 Hour_funct,[3]MSB Hours funct. Compresseur 3 x 256 h L
8FH 16502 Hour_funct,[3]LSB Hours funct. Compresseur 3 x 1h L
90H 16503 Hour_funct,[4]MSB Hours funct. Compresseur 4 x 256 h L
91H 16504 Hour_funct,[4]LSB Hours funct. Compresseur 4 x 1h L
92H 16505 Hour_funct,[PUMP]MSB Hours funct. Pump x 256 h L
93H 16506 Hour_funct,[PUMP]LSB Hours funct. Pump x 1h L
94H 14337 Ana_Output_1 Analog Output 1 L
95H 14338 Ana_Output_2 Analog Output 2 L
96H 16473 Digit_Input_MSB Digit_Input L
97H 16474 Digit_Input_LSB Digit_Input L
98H 16731 Digit_Output_MSB Digital Output L
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
9/13
99H 16732 Digit_Output_LSB Digital Output L
9AH 16879 Alarm_Auto_1 Alarm_Auto_1 L
9BH 16880 Alarm_Auto_2 Alarm_Auto_2 L
9CH 16881 Alarm_Auto_3 Alarm_Auto_3 L
9DH 16882 Alarm_Auto_4 Alarm_Auto_4 L
9EH 16883 Alarm_Manu_1 Alarm_Manu_1 L
9FH 16884 Alarm_Manu_2 Alarm_Manu_2 L
A0H 16885 Alarm_Manu_3 Alarm_Manu_3 L
A1H 16886 Alarm_Manu_4 Alarm_Manu_4 L
A2H 18433 I/Ver VERSION L
5.d Detailed explanation of the CLIMATIC 400 parameters
5.d.1 /Logical parameters
In the zone of logical parameters , we can read the different status of the controller digital outlets and inlets . Correspondence
between these inlets , depending the model of unit are the following :
EAR 0472 to 0812
80H 81H 82H 83H 84H 85H 86H 87H
High
pressure
switch 1
Low pressure
switch 1
Fan +
compressor
protection 1
Defrosting
switch 1
Flow switch
High
pressure
switch 2
Low pressure
switch 2
Fan+
compressor
protection 2
88H 89H 8AH 8BH 8CH 8DH 8EH 8FH
Defrosting
switch 2
Remote
on/off
Remote
cooling /
heating
Not used Not used Not used Not used Not used
90H 91H 92AH 92H 94H 95H 96H 97H
Compressor
1 4 way valve 1 Compressor
2 4 way valve 2 Water pump Electrical
heater
Electrical
heater Alarm
98H 99H
Not used Not used
EAC 1003 to 1303
80H 81H 82H 83H 84H 85H 86H 87H
High
pressure
switch
Low pressure
switch 1
Fan
protection 1
Defrosting
pressostat 1
Flow switch
High
pressure
switch 2
Low pressure
switch 2
Fan
protection 2
88H 89H 8AH 8BH 8CH 8DH 8EH 8FH
Defrosting
pressostat 2
Remote
ON/OFF
Remote
cooling
/heating
Compressor
protection 1
Compressor
protection 2
Compressor
protection 3
Compressor
protection 4 Not used
0H 91H 92AH 92H 94H 95H 96H 97H
Compressor
1 Fan 1 Compressor
2 Fan 2 Water pump Electrical
heater
Electrical
heater Alarm
98H 99H
Compressor
3
Compressor
4
EAR 1003 to 1303
80H 81H 82H 83H 84H 85H 86H 87H
High
pressure
switch 1
Low pressure
switch 1
Fan+
compressor
protection 1
Defrosting
pressostat 1
Flow switch
High
pressure
switch
Low pressure
switch 2
Fan
+compressor
protection
88H 89H 8AH 8BH 8CH 8DH 8EH 8FH
Defrosting
switch 2
Remote
ON/OFF
Remote
cooling/
heating
Compressor
protection 1
Compressor
protection 2
Compressor
protection 3
Compressor
protection 4 Not used
90H 91H 92AH 92H 94H 95H 96H 97H
Compressor
1 4 way valve 1 Compressor
2 4 way valve 2 Water pump Electrical
heater
Electrical
heater Alarm
98H 99H
Compressor
3
Compressor
4
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
10/13
5.d.2 /Analogical parameters/
00H, 01H (readable and writable)
This parameter defines the setpoint which the unit will function with in cooling ( 00H parameter) or in heating ( 01H parameter)
¡Important: Value of the required temperature has to be multiplied by 10!
Values included in this parameter must be within the range from the minimum setpoint ( 82H parameter for cooling / 80H for
heating) and the maximum setpoint ( Parameter 83H for cooling / 81 H for heating) .
¡Important: if the unit Works out of this range of temperatures, the unit may work with critical damages!
If the unit is a cooling only unit , there is not sense in using 01H parameter. We can limit this possibility with the 84 H parameter
which with the value 1 shows that the unit is heating pump version .
Example: H00=110 and H01=430 shows cooling setpoint 11.0ºC and heating setpoint 43.0ºC
02H parameter (readable and writable)
This parameter defines the function of the unit as following :
Parameter 02H=00H ∧Stopped unit
Parameter 02H=80H ∧Stand-By mode
Parameter 02H=81H ∧Cooling only mode
Parameter 02H=82H ∧Heat pump mode
¡Important: If different values are used , the result obtained maybe wrong!
To know if the unit can work in heat pump mode , read the value of the 84 H parameter.
¡Important: If in a cooling only unit , heat pump mode is demanded , the unit may work with critical damages!
80H, 81H, 82H, 83H parameters(only readable)
Cooling and heating setpoint limits, in detail :
80H ∧Maximum heating setpoint
81H ∧Minimum heating setpoint
82H ∧Maximum cooling setpoint
83H ∧Minimum cooling setpoint
Use these values to establish the limit values of the parameters 00 H and 01 H.
84H (only readable)
Shows with a value 0 if the unit is cooling only or with a value 1 if the unit is heat pump mode.
Using this value can establish if it is possible to modify the heating setpoint (H01 parameter) and more important also if we can
change to heat pump mode (H02 parameter)
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
11/13
85H, 86H, 87H, 88H, 89H parameters ( only readable)
In these parameters we can read the values measured by the temperature sensors in the unit. The values shown are ºC x 10.
85H ∧Outlet water temperature
86H ∧Outlet water temperature
87H ∧Refrigerant piping temperature 1
88H ∧Outdoor temperature
89H ∧Outdoor temperature circuit 2
Note: Outdoor temperature will only show correct values if the unit is fitted with the outdoor temperature sensor (dynamic
setpoint kit)
Example: in 85H we will read the value 428, so the inlet water sensor is showing the value 42.8ºC.
8AH, 8BH, 8CH, 8DH, 8EH, 8FH, 90H, 91H, 92H, 93H parameters (only readable)
In these parameters we can read the hours of functioning of different components, in detail:
8AH ∧Hours of functioning of compressor 1 (MSB)
8BH ∧Hours of functioning of compressor 1 (LSB)
8CH ∧Hours of functioning of compressor 2 (MSB)
8DH ∧Hours of functioning of compressor 2 (LSB)
8EH ∧Hours of functioning of compressor 3 (MSB)
8FH ∧Hours of functioning of compressor 3 (LSB)
90H ∧Hours of functioning of compressor 4 (MSB)
91H ∧Hours of functioning of compressor 4 (LSB)
92H ∧Hours of functioning of water pump (MSB)
93H ∧Hours of functioning of water pump (LSB)
To calculate the value, the following formula has to be taken into account:
HR= MSB·256 + LSB
Example: in 8AH we can read the value 2 and in 8 BH a value of 48. This means 2 * 256 + 48=560. This shows that
compressor 1 has worked 560 hours.
94H, 95H, 95H, 96H, 97H, 98H, 99H parameters (only readable)
In these parameters we can read the status of the different devices of the unit:
94H, 95H ∧Analogical outputs (% fan speed)
96H, 97H ∧Digital inputs (pressostats, protections, remote on/ off, remote cooling/ heating)
98H, 99H ∧Digital outputs (compressor, water pump, 4 way valve, antifreeze heater, alarm relay)
Correspondence with the different devices is the following:
94H and 95H parameters show the speed (in %) of fans 1 and 2 :
0: fan stopped
100: maximum fan speed
Intermediate values: fan in regulation
This value is valid for:
- EAR 0472 to 0812 standard and FP1.
- EAR 1003 to 1303 but only taking 0 and 100 values.
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
12/13
96H y 97H parameters show the different digital inlets, according the models as following (1 means closed contact and 0 open
contact)
EAR 0472 to 0812
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
96H Not used Not used
High
pressure
switch 1
Low pressure
switch 1
Fan + comp
protection 1 Not used Not used
Remote
cooling /
heating
97H
Defrosting
switch 2
Fan +
compressor 2
protection
Remote
ON/OFF Not used
Low pressure
switch 2
Flow switch
Defrosting
switch
High
pressure
switch 2
EAC 1003 to 1303
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
96H Compressor
protection 4
Compressor
protection 3
High
pressure
switch 1
Low pressure
switch 1
Fan
protection 1 Not used Compressor
protection 2 Not used
97H Not used Fan
protection 2
Remote
on/off
Compressor
protection 1
Low pressure
switch 2
Flow switch Not used
High
pressure
switch 2
EAR 1003 to 1303
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
96H Compressor
protection 4
Compressor
protection 3
High
pressure
switch 1
Low pressure
switch 1
Fan
protection 1 Not used Compressor
protection 1 Not used
97H
Defrosting
pressostat 2
Fan
protection 2
Remote
ON/OFF
Compressor
protection 2
Low pressure
switch 2
Flow switch
Defrost swicth
1
High
pressure
switch 2
Example : in a unit EAC 1103 the value of 96H is 208 (1111 1010 in binary) shows that the protections of the compressors 4,3
and 2 , the protection of the fan 1 , the high pressure switch 1 and the low pressure switch 1 are closed.
98H y 99H will show the functioning of the following devices, according the models (1 means functioning, 0 means stop)
EAR 0472 to 0812
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
98H Electrical
heater
Electrical
heater Water pump 4 way valve 2 Compressor
2 4 way valve 1 Compressor
1 Alarm
99H Fan 1 ( only
FP2 version)
Fan 2 ( only
FP2 version) Not used Not used Not used Not used Not used Not used
EAC 1003 to 1303
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
98H Electrical
heater
Electrical
heater Water pump Fan 2 Compresso 2 Fan 1 Compressor
1 Alarm
99H Compressor
3
Compressor
4 Not used Not used Not used Not used Not used Not used
EAR 1003 to 1303
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
98H Electrical
heater
Electrical
heater Water pump 4 way valve 2 Compressor
2 4 way valve 1 Compressor
1 Alarm
99H Compresor 3 Compresor 4 N/U N/U N/U N/U N/U N/U
Example : in one unit EAC 0472 the value of 34 (0010 0010 in binary) show that there are only functioning compressor 1 and
water pump .
TECHNICAL DATA
USING OF THE INTERFACE KP06 FOR ECOLEAN UNITS
13/13
9AH, 9BH, 9CH, 9DH, 9EH, 9FH, A0H, A1H parameters (only readable)
In these parameters it is shown the presence of an alarm , and if it is neccessary the restarting. 90H, 91H and 92H parameters
shown the status of the alarm and 93H, 94H and 95H the necessity of restarting .
Alarm 9AH restart 9EH
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
E07 E06 E05 E04 E03 E02 E01 E00
Alarm 9BH restart 9FH
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
E23 E22 E21 E19 E13 E12 E11 E09
Alarm 9CH restart A0H
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
E33 E32 E31 E29 E27 E26 E25 E24
Alarm 9DH restart A1H
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
E46 E45 E44 E43 E42 E41 E40 E39
The meaning of the alarms is the following:
• E00 ∧remote ON/ OFF
• E01 ∧High pressure circuit 1
• E02 ∧Low pressure circuit 1
• E03 ∧Compresso overload relay 1
• E04 ∧Fan overload relay 1
• E05 ∧Antifreeze circuit 1
• E06 ∧Error water outlet sensor
• E07 ∧Error refrigerant piping sensor circuit 1
• E09 ∧High pressure compressor 1
• E11 ∧High pressure piping circuit 1
• E12 ∧Low pressure piping circuit 1
• E13 ∧Overload protection compressor 2
• E19 ∧High pressure compressor 2
• E21 ∧High pressure circuit 2
• E22 ∧Low pressure circuit 2
• E23 ∧Overload protection compressor3
• E24 ∧Fan overload protection 2
• E25 ∧Antifreeze protection 2
• E26 ∧Error sensor ST5
• E27 ∧Error refrigerant piping sensor 2
• E29 ∧High pressure compressor 3
• E31 ∧High piping temperature circuit 2
• E32 ∧Low piping temperature circuit 2
• E33 ∧Overload protection compressor 4
• E39 ∧High pressure compressor 4
• E40 ∧Error water inlet sensor
• E41 ∧Error flow switch sensor
• E42 ∧Error outdoor temperature sensor
• E43 ∧External antifreeze
• E44 ∧Unit without charge
• E45 ∧Error in configuration
• E46 ∧High inlet water temperature
Some of these units may be not available in the unit, or have slightly different meanings. See the manual of the unit to know the
detailed meaning of each alarm
Example : if appear one alarm by high pressure , the parameters 9AH and 9EH will take value 2 2 (0000 0010 in binary),
when the cause of the alarm is settled ( pressostat restarted) , parameter 9AH will show the value 0 (0000 0000 in binary) but
in the parameter 9EH nothing will change until we do not reset the alarm in the controller ( pressing the reset button) .
A2H parameter (only readable)
This parameter shows the current version of the software control.
www.lennoxeurope.com
www.lennoxbelgium.com
www.lennoxczech.com
www.lennoxfrance.com
www.lennoxdeutschland.com
www.lennoxnederland.com
www.lennoxpolska.com
www.lennoxportugal.com
www.lennoxrussia.com
www.lennoxdistribution.com
www.lennoxspain.com
www.lennoxukraine.com
www.lennoxuk.com
www.lennoxdistribution.com
MUL33E-0904 09-2006
BELGIUM, LUXEMBOURG
CZECH REPUBLIC
FRANCE
GERMANY
NETHERLANDS
POLAND
PORTUGAL
RUSSIA
SLOVAKIA
SPAIN
UKRAINE
UNITED KINGDOM AND IRELAND
OTHER COUNTRIES
Due to Lennox’s ongoing commitment to quality,
the Specifications, Ratings and Dimensions are
subject to change without notice and without
incurring liability.
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage or personal injury.
Installation and service must be performed by a
qualified installer and servicing agency.

Popular I/O System manuals by other brands

NI SCB-8 manual

NI

NI SCB-8 manual

Acromag 948 Series user manual

Acromag

Acromag 948 Series user manual

Easy Controls MC231 user manual

Easy Controls

Easy Controls MC231 user manual

Siemens SIMOTICS CONNECT 400 operating instructions

Siemens

Siemens SIMOTICS CONNECT 400 operating instructions

M-system R7L-DC16A-R instruction manual

M-system

M-system R7L-DC16A-R instruction manual

Real Time Devices DM5854HR user manual

Real Time Devices

Real Time Devices DM5854HR user manual

Pilz PSSu H FS2 SN SD operating manual

Pilz

Pilz PSSu H FS2 SN SD operating manual

Belden lumberg automation LioN-P 0980 ESL 300... Technical manual

Belden

Belden lumberg automation LioN-P 0980 ESL 300... Technical manual

Lucent Technologies ATM Module 8-Port DS3/E3 Specifications

Lucent Technologies

Lucent Technologies ATM Module 8-Port DS3/E3 Specifications

Sony DVS-7300 user guide

Sony

Sony DVS-7300 user guide

Axis F44 installation guide

Axis

Axis F44 installation guide

RME Audio Digiface AES user guide

RME Audio

RME Audio Digiface AES user guide

Cosel TUNS300 Applications manual

Cosel

Cosel TUNS300 Applications manual

Siemens SIMATIC SM 335 manual

Siemens

Siemens SIMATIC SM 335 manual

Delta DVP06XA-S instruction sheet

Delta

Delta DVP06XA-S instruction sheet

Contec PO-128L(PCI)H quick start guide

Contec

Contec PO-128L(PCI)H quick start guide

Contec COM-1PDH-LPE user guide

Contec

Contec COM-1PDH-LPE user guide

SIGMA TEK DI 080 instruction manual

SIGMA TEK

SIGMA TEK DI 080 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.