Operation
13
GA 01.202/10.02 - 08/01
The maximum throughput of the pump is equivalent to
the pumping speed of the pump (see Section 1.6).
The cross-section of the intake and exhaust
lines should be at least the same size as
the connection ports of the pump.If the inta-
ke line is too narrow, it reduces the pumping
speed. If the exhaust line is too narrow,
overpressures may occur in the pump; this
might damage the shaft seals and cause oil
leaks. The maximum pressure in the oil
case must not exceed 1.5 bar (absolute).
When pumping vapours, it is advisable to
install condensate traps on the intake and
exhaust sides.
Install the exhaust line with a downward
slope (lower than the pump) so as to pre-
vent condensate from flowing back into the
pump. If this is not possible, insert a con-
densate trap.
The exhaust gases from the vacuum pump
must be safely led away and subjected to
post-treatment as required.In order to redu-
ce the emission of oil vapours we recom-
mend the installation of an additional
exhaust filter (Leybold accessory).
Depending on the type of application or the
kind of pumped media, the corresponding
regulations and information sheets must be
observed.
The pumps may be operated with an inert gas ballast via
a connection which is provided for this purpose. The
cover plate (7/8) can be removed to gain access to this
M 16 x 1.5 threaded port (7/6). Matching connectors are
available (see Section 1.3).
In inlet pressure for the gas ballast should be about 1000
mbar (absolute) and sufficient quantities of gas must be
available (about 1/10 of the pumping speed).
Never operate the pump with a sealed
exhaust line.There is the danger of injury.
Before starting any work on the pump, the
personnel must be informed about possible
dangers first. All safety regulations must be
observed.
2.3 Electrical Connections
Before wiring the motor or altering the
wiring, ensure that mains supply for the
pump is off and that it can not be applied
inadvertently.
In order to prevent the pump from running
up unexpectedly after a mains power failu-
re, the pump must be integrated in the con-
trol system in such a way that the pump can
only be switched on again manually. This
applies equally to emergency cut-out arran-
gements.
Electrical connections must be done by a
qualified electrician as defined by VDE
0105 in accordance with the VDE 0100 gui-
delines.
Observe all safety regulations.
TRIVAC-B pumps are available with a single-phase or a
three-phase AC motor.
2.3.1 Pump with Single-Phase AC Motor
Pumps equipped with a single-phase AC motor may be
connected directly to the mains via the mains cord and
the mains plug.
At 230 V use an at least a 6 A slow-blow or a 10 A fast-
blow fuse.
The direction of rotation need not be checked as it is
fixed.
The motor is protected against overloading by a thermal
overload switch with automatic resetting.
If the thermal overload protector shuts off
the pump, the motor will restart itself as
soon as it cools.That’s why the mains plug
should be disconnected from the mains
before starting with any work on the pump.
2.3.2 Pump with Three-Phase AC Motor
TRIVAC-B pumps with a three-phase motor are supplied
without accessories for electrical connection. They must
be connected via the appropriate cable, and a suitable
motor protection switch. Set the switch in accordance
with the rating on the motor nameplate.
Fig. 8 shows the connection for pumps with 230/400 V,
50 Hz motors. Please also observe the motor wiring dia-
gram in the junction box and the information given on the
nameplate of the motor.
Warning
Warning
Caution
Warning