Loup Electronics II Use and care manual

LOUP II DRILL MONITOR
OPERATION AND CALIBRATION MANUAL
Issue 3.0
01/15/10

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
2
Service and Technical Support
Contact: Loup Electronics Inc.
Address: 2960 N. 38th Street
Lincoln, NE 68504
Phone: 877-489-LOUP(5687)
402-464-7131
Fax: 402-464-7104

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 3
Table of Contents
1.0 OPERATION................................................................................................................... 5
1.1 NORMAL START-UP.......................................................................................................... 5
1.2 NORMAL OPERATE SCREEN ............................................................................................. 6
1.3 CHANGING DISPLAY SIZE................................................................................................. 7
1.4CHANGING DISPLAYED FUNCTIONS................................................................................ 7
1.5 ALARMS.......................................................................................................................... 9
1.5.1 Should be Seeding.................................................................................................. 10
1.5.2Low Seed Rate....................................................................................................... 10
1.5.3 Empty Bin............................................................................................................... 11
1.5.4 Blockage Module ................................................................................................... 11
1.5.5Communication Error........................................................................................... 12
1.6 SPECIAL START-UP......................................................................................................... 13
1.6.1 Learn New System.................................................................................................. 13
2.0 SYSTEM SETTINGS.................................................................................................... 15
2.1 INSTALLATION ............................................................................................................... 16
2.1.1 Install New System................................................................................................. 16
2.1.2Replace a Sensor................................................................................................... 16
2.1.3 Add a Sensor.......................................................................................................... 16
2.1.4 Remove a Sensor.................................................................................................... 16
2.2 IMPLEMENT SETUP......................................................................................................... 16
2.2.1 Units...................................................................................................................... 16
2.2.2Implement Width................................................................................................... 16
2.2.3Clear Field Area................................................................................................... 16
2.2.4 Clear Total Area.................................................................................................... 16
2.3 SPEED SETTINGS ............................................................................................................ 17
2.3.1 Pulses Per Rev ....................................................................................................... 17
2.3.2Wheel Pulses Per 400Ft........................................................................................ 17
2.3.3 Radar Pulses Per 400 Ft........................................................................................ 17
2.3.4 Lift Switch .............................................................................................................. 17
2.3.5Speed Calibration ................................................................................................. 17
2.4 FAN SETTINGS................................................................................................................ 19
2.4.1 Pulses per Rev........................................................................................................ 19
2.4.2 Low Alarm Point.................................................................................................... 19
2.4.3 High Alarm Point................................................................................................... 19
2.5 BIN SETTINGS ................................................................................................................ 20
2.6 SHAFT SETTINGS............................................................................................................ 20
2.6.1 Pulses per Rev........................................................................................................ 20
2.6.2 Low Alarm Point.................................................................................................... 20
2.7 SEED SETTINGS.............................................................................................................. 21
2.7.1 Low Alarm Point.................................................................................................... 21

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
4
2.7.2 High Alarm Point................................................................................................... 21
2.7.3 Row Spacing........................................................................................................... 21
2.7.4 Machine Type......................................................................................................... 21
2.7.5 Population Adjust................................................................................................... 21
2.8 BLOCKAGE MODULE SETTINGS...................................................................................... 22
2.8.1 Runs per Module Setup.......................................................................................... 22
2.8.2 Individual Runs Setup............................................................................................ 22
2.8.3 Blockage Module Test............................................................................................ 22
2.8.4 Blockage Calibration............................................................................................. 22
2.9 WEIGHT SETTINGS ......................................................................................................... 24
2.9.1 Seeds/Lb................................................................................................................. 24
2.9.2 Min Area Before Calc Pop Start............................................................................ 24
2.9.2 Reset Weight Calculations..................................................................................... 24
2.10 GLOBAL SETTINGS....................................................................................................... 25
2.10.1 Volume/Pitch........................................................................................................ 25
2.10.2 Backlight.............................................................................................................. 25
2.10.3 Contrast................................................................................................................ 25
3.0 GENERAL INSTALLATION....................................................................................... 25
3.1 CONSOLE ....................................................................................................................... 25
3.2 SENSORS ........................................................................................................................ 25
3.3 WIRE CONNECTIONS (LOUP II DM ONLY)..................................................................... 26
3.3.1 Radar Connection.................................................................................................. 26
3.3.2 Power Connection.................................................................................................. 26
3.3.3 Harness Connections............................................................................................. 27
3.4 BASIC WIRE DIAGRAM................................................................................................... 28

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 5
1.0 Operation
The Loup II Drill Monitor is a full featured monitor designed to provide accurate population
and seed flow information for conventional and air drills. This manual will familiarize you
with operation, calibration and technical information. All aspects and features are detailed
but may not be applicable to your system configuration.
The LOUP ELECTRONICS Drill Monitor is capable of monitoring and displaying:
Ground speed (Implemented Mounted Speed Sensor or optional Radar)
Population in Seeds/Acre (up to 24 sensors can be connected)
Spacing between seeds or Seeds per Foot (S/FT or IN/S)
Three shaft speed RPM’s (Left, Center & Right)
Seed Flow (up to 112 sensors can be connected)
Field Area
Total area
Three Hoppers (displayed as bargraph display)
Weight (Measured Weight in Hoppers)
Calc Pop (Calculated Population )
Area Left (Calculated Value of Area to be covered with remaining seed)
Weight/Area (Calculated Value of Area covered and seed used)
1.1 Normal Start-up
For everyday operation the Loup II monitor will remember all settings that have been saved
from the previous use. Press the power button in the lower right hand corner as shown in the
picture below.
The display will read “Wait for Sensors
to Complete Calibration”. During this
time the monitor is checking all
connected sensors to ensure they are
working properly. Once this “self-test” is
complete the monitor will display the
normal operate screen.

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
6
Sample of the Normal Operate Screen
1.2 Normal Operate Screen
The Normal Operating Screen is divided into the following areas:
2 – Display Sections or 1 enlarged Display Section (User Chosen)
1 – Active alarm window or, if there are no active alarms, the current ground speed is
displayed
1 – Bin level icon window
2 – Soft-key label windows
Below is a sample screen shot:
In the Sample Normal Operate Screen above, the different areas are as follows:
The Top Display Section is the window with “Field Area” in it.
The Bottom Display Section is the “Average Seed Rate” window.
The active alarm window has the Ground Speed “88.8 MPH” displayed on it.
The Bin Level Window is shown as 3 graphics:
1 shows a full hopper
2 shows an empty hopper
3 shows no hopper sensor present
The soft key windows are displaying “Menu” and “Enlarge”.
Top Display
Bottom Display
Active Alarm
Display Bin Level
Display
Soft Key Windows

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 7
1.3 Changing Display Size
Depending on the preference of the operator, the Bottom display of the Loup II can be
enlarged to make viewing easier. To change the display size press the bottom button labeled
ENLARGE. Notice the button label now reads SMALLER. To return to the smaller screen
press the bottom button labeled SMALLER.
1.4 Changing Displayed Functions
The display of the Loup II monitor can be changed to show any of the available functions the
operator chooses. Pressing either the UP arrow or the DOWN arrow button while at the
normal operate screen will allow you pick from a list of the available functions. Pressing the
UP arrow will change the Top Display, pressing the DOWN arrow will change the Bottom
Display.
-OR-
Note: The sample procedure on the next page is based on the UP arrow being pressed. The
procedure is the same when the DOWN arrow is pressed.
Small Operate Screen Enlarged Operate Screen

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
8
In this sample we will change the top display from reading Field Area to Seeds per
Distance (Seeds/Ft).
Having pressed the UP arrow in the Normal
Operate screen, a menu screen titled “Top
Display Section” is now shown. The
current displayed function will be
highlighted. In this sample Field Area was
shown in the top display thus Area is
highlighted.
Press the UP arrow until “Seeds per
Distance” is highlighted. (Depending on
your system set-up, some of the options
shown may not be available.)
Press the “Select” button when “Seeds per
Distance” is highlighted.
The “Seeds per Distance” menu is now
displayed.
The “Seeds per Distance” menu provides several options to choose from.
Auto Scrolling – Automatically
scans all rows with population
sensors
Min – Displays the row that is
planting the least amount of seed
Max – Displays the row that is
planting the most amount of seed
Average – Displays the average
seed spacing for all rows
1 – Row #1 ; 2 – Row #2 ; ect.
Manual – Allows the Operator to
manually scroll through all rows

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 9
For this example use the DOWN arrow button to highlight Average.
Press SELECT
The display now returns to the Normal Operate
screen. Notice that the Top Display now reads
Seeds per Foot.
1.5 Alarms
The alarm display will become active when any conditions fall below the set alarm points.
For example: High or Low population, Low hopper level, No Ground Speed, Low seed flow.
All alarms operate in a similar fashion: An audible alarm will sound and an alarm message
will appear on the display. This alarm display will only become active when the monitor is
at its normal operating screen.
Pressing “OK” will silence all alarms. All acknowledged alarms are displayed on the normal
operating screen’s active alarm window until the alarm condition is fixed.
Sample alarm screens are shown on the following page.

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
10
1.5.1 Should be Seeding
Should be Seeding alarms indicates that the implement has been out of motion for more than
30 seconds.
1.5.2 Low Seed Rate
A Low Seed Rate alarm occurs when the seed rate has fallen below the set alarm point. A
row number will be displayed indicating which sensor is that is in alarm. In this example
Row 2 has fallen below the low alarm point.
Acknowledged Should be Seeding
alarm displayed in active alarm
window
Acknowledged Low Seed Rate
displayed in active alarm window

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 11
1.5.3 Empty Bin
An Empty Bin alarm occurs when the grain in the hopper has fallen below the hopper sensor
indicating that the hopper is near empty. An Empty Bin alarm only occurs if your system is
equipped with hopper level sensors.
1.5.4 Blockage Module
Two different Blockage Module alarms may occur.
Blocked: Blockage Module Run 1 is Blocked indicates the displayed row has stopped
seeding and should be cleaned.
Acknowledged Empty Bin displayed
in active alarm window
Acknowledged Run Blocked alarm
displayed in active alarm window

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
12
Bad: Blockage Module Run 1 is Bad indicates the displayed row has stopped has failed
the self test. This does not mean the sensor is bad! Run a blockage calibration as shown in
Section 2.7.4. If the indicated sensor will not calibrate, the sensor should be replaced.
1.5.5 Communication Error
A Communication Error occurs any time the monitor loses communication with a learned
sensor. This includes Ground Speed, Shaft, Population, Hopper sensors and Blockage
Modules.
If a communication error is received:
Check that all harness connections are securely connected.
If no loose connections are found, check all wiring to ensure the wires have not been
broken
If any of the listed alarms persist or if an alarm is displayed that is not listed contact
Loup Electronics.
Acknowledged Communication Error
displayed in active alarm window
Acknowledged Run Bad alarm
displayed in active alarm window

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 13
1.6 Special Start-up
A special start-up screen will appear when the monitor is turned on in the following
circumstances:
1) The monitor has been learned but is unplugged from the drill.
2) The monitor has been learned but has lost its memory
3) The monitor has not been learned
System Start-up: Selected for “Normal
Operation”. The last used system
configuration and settings will be loaded
Learn New System: Special start-up used
to learn all new sensors while keeping the
previous system settings.
Default Settings: Special start-up used to
rest set all sensor settings to their default
setting
Learn New System and Default Settings:
Complete reset of the monitor. Removes all
learned sensors and restores all the default
sensor settings
If this screen appears and you are unsure of what to do contact Loup Electronics.
1.6.1 Learn New System
The learn mode is a onetime process that identifies each sensor with the monitor.
Before entering the Learn Mode, be sure to unplug all the sensors that have a 3-pin
connector, i.e. Ground Speed Sensor, Fan Sensor, Shaft Sensors, Hopper Sensors, Population
Sensors & Blockage Modules. (Blockage Sensors have a 2-pin connector and can be plugged
into their appropriate connection on the blockage harness.)
Procedure:
1. Press the Power Button to turn the monitor on.
2. Press the DOWN arrow to highlight Learn New System and Default Settings
3. Press SELECT

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
14
The first sensor the monitor will look for is a Speed sensor. This is an implement-mounted
sensor monitoring a shaft. Plug it in now. If no speed sensor is mounted on the drill, press
SELECT to Skip this Sensor.
Once the speed sensor has been accepted or skipped, the monitor will move to the next
sensor. The order the monitor will ask for sensors is shown below.
Speed
Shaft 1
Bin 1
Shaft 2
Bin 2
Shaft 3
Bin 3
Seed 1 through 24 (population sensors)
Blockage Module 1 through 8
Note: If during the Learn Mode you receive a
Wrong Sensor Type for: message, the
monitor is “seeing” a type of sensor other
than what is required for this function. For
example: This message would appear if
monitor asks for Shaft 1 but a hopper
sensor is plugged in.
4. A warning message now appears
asking Are you Sure? Press
SELECT to proceed or press
CANCEL to exit.
5. Install New System – Plug your
sensors in as the monitor asks for
them. For sensors that are
unavailable, press SELECT to
Skip this Sensor.

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 15
6. When all sensors have been plugged in or
skipped the monitor will display Installation
Complete.
7. Press SELECT. The monitor will display the
Normal Operate Screen.
Note: It is recommended that you turn the monitor off and back on to ensure the Learn Mode
was completed properly. If the Startup Menu appears when the monitor is turned on,
check that the monitor has not been disconnected from the harness. If a sensor Missed
or Wrong Sensor Type for message appears, check that all harness connections are
secure. If no connections are unplugged it may be necessary to Re-Learn the system.
If problems persist, contact Loup Electronics
2.0 System Settings
Pressing the MENU button on the Normal
Operate Screen will access your system
settings.
Use the DOWN arrow to highlight the
desired menu. Press the SELECT button to
enter the selected menu item.
Theses settings should be reviewed and
changed as necessary.
Important: All new systems must have to proper Row Spacing, Implement width and
ground speed to give accurate population readings. A Ground Speed Calibration
must be done on all new systems (See section 2.3.5). Systems that including
blockage sensors must perform a Blockage Calibration (See Section 2.7.4)

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
16
2.1 Installation
2.1.1 Install New System
Install New System allows you to overwrite the
existing Sensor setup. Refer to Section 1.6.1 for
information on Learning a new system.
2.1.2 Replace a Sensor
Replace a Sensor allows you to replace a bad
sensor without re-learning the system. This
refers only to Learned Sensors; i.e. Shaft
Sensors, hopper sensors, population sensors and
blockage modules.
2.1.3 Add a Sensor
Add a Sensor allows you to add a new sensor without re-learning the system. This refers
only to Learned Sensors; i.e. Shaft Sensors, hopper sensors, population sensors and blockage
modules.
2.1.4 Remove a Sensor
Remove a Sensor allows you to remove a sensor from your existing system without re-
learning the system. This refers only to Learned Sensors; i.e. Shaft Sensors, hopper sensors,
population sensors and blockage modules.
2.2 Implement Setup
2.2.1 Units
The Units setting changes the units of measure
that the monitor displays
Imperial = Acres/Feet/Miles per Hour
Metric = Hectares/Meters/ Kilometers per Hour
2.2.2 Implement Width
Adjust accordingly to the size of your drill
(i.e. 15ft, 20ft, 30ft, 40ft)
2.2.3 Clear Field Area
Use to zero or clear your Field Acres
2.2.4 Clear Total Area
Use to zero or clear your Total Acres

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 17
2.3 Speed Settings
2.3.1 Pulses Per Rev
Pulses per Rev (revolution) are the number of
magnets the implement mounted speed sensor
sees in one revolution of the shaft being
monitored. For most applications this number
will remain 4.
2.3.2 Wheel Pulses Per 400Ft
This is the ground speed calibration number for a
implement mounted speed sensor. Refer to
section 2.3.5 for calibration instructions.
The default number is 175
2.3.3 Radar Pulses Per 400 Ft
This is the ground speed calibration number for a radar speed sensor. Refer to section 2.3.5
for calibration instructions. The default number is 15151
2.3.4 Lift Switch
Lift Switch is used to tell the monitor if a lift sensor is being used to determine when you are
seeding and when you are not. The Lift Sensor is used when shaft rotation cannot be used or
a variable rate drive, common on air seeders, is being used.
If a Lift switch is to be used, a clutch activated shaft sensor must be learned as Shaft 1 and
this setting must be set to ENABLED.
2.3.5 Speed Calibration
All new systems require a ground speed calibration to ensure accurate population readings,
accurate area totals and accurate ground speed readings. To complete the calibration,
measure a course 400 feet long preferably on level ground with a start and finish point. The
drill must be in the down position throughout this procedure.
Note: During the calibration the monitor is looking for the number of pulses produced from
the drill mounted sensor or in the case of radar, the number of radar pulses. The monitor will
not display 400 when the speed calibration is complete rather it will display the pulses
counted in 400 feet.

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
18
Procedure:
1. From the Speed Settings menu
Highlight Speed Calibration and
press SELECT
2. Press SELECT again on
Continue Calibration
3. The display will now say Start
Driving. With the drill in the
down position, drive the 400-foot
course. As you drive the pulses
receive will begin counting up.
4. Press SELECT at the end of the
400-foot course to Exit and Save
Note: The 235 under Wheel
Pulses Received is for
illustration purposes only.

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687 19
5. The display is now back at the Speed Settings
menu. Notice the Wheel Pulses Per 400 feet
has changed to the calibrated number.
(The number shown is for illustration purposes
only).
2.4 Fan Settings
2.4.1 Pulses per Rev
This is the number of pulses produced by
the fan sensor in one revolution. The pulse
setting is equal to the number of targets
presented to the fan sensor in one
revolution.
2.4.2 Low Alarm Point
The Low Alarm Limit is set by the user for
low rpm notification. Default is 1500 RPM
2.4.3 High Alarm Point
The High Alarm Limit is set by the user for high rpm notification. Default is 5500 RPM.
**Fan RPM above the High Alarm Point or Below the Low Alarm Point will cause an alarm
condition that cannot be acknowledged.

Loup Electronics 2960 North 38th Street Lincoln NE, 68504 (877)489-5687
20
2.5 Bin Settings
Bin Settings allow the operator to Enable and
Disable the alarms for Hopper Level Sensor.
By default, these will be set to Enable when
Hopper Sensors are Learned.
If your system does not include hopper sensors,
this menu will not be available
2.6 Shaft Settings
2.6.1 Pulses per Rev
Pulses per Rev (revolution) are the number of magnets the associated sensor sees in one
revolution of the shaft being monitored. For most applications this number will remain 2.
Changing this number to 0 will turn the sensor OFF.
2.6.2 Low Alarm Point
The Low Alarm Point is set as a reference point for the alarm. If the shaft turns slower than
this designated point, an alarm will sound.
Table of contents
Other Loup Electronics Monitor manuals