manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Mandik
  6. •
  7. Fan
  8. •
  9. Mandik DM-S User manual

Mandik DM-S User manual

Other Mandik Fan manuals

Mandik VBM-V Series User manual

Mandik

Mandik VBM-V Series User manual

Popular Fan manuals by other brands

Minka Group minkaAire Wave F843 instruction manual

Minka Group

Minka Group minkaAire Wave F843 instruction manual

Airflow Adroit DV50 instruction manual

Airflow

Airflow Adroit DV50 instruction manual

Vornado 270 Series owner's guide

Vornado

Vornado 270 Series owner's guide

comfort air TH-10D instruction manual

comfort air

comfort air TH-10D instruction manual

Livoo DOM386 instruction manual

Livoo

Livoo DOM386 instruction manual

Holmes BLIZZARD HAOF-90 owner's guide

Holmes

Holmes BLIZZARD HAOF-90 owner's guide

Taurus GRECO 16 ELEGANCE manual

Taurus

Taurus GRECO 16 ELEGANCE manual

Quorum PINNACLE installation instructions

Quorum

Quorum PINNACLE installation instructions

Monte Carlo Fan Company 3DIR58RBD-V1 Owner's guide and installation manual

Monte Carlo Fan Company

Monte Carlo Fan Company 3DIR58RBD-V1 Owner's guide and installation manual

Craftmade UH52 installation guide

Craftmade

Craftmade UH52 installation guide

Jocel JVA030658 instruction manual

Jocel

Jocel JVA030658 instruction manual

MIKA MFB1211/GR user manual

MIKA

MIKA MFB1211/GR user manual

Harbor Breeze RLG52NWZ5L manual

Harbor Breeze

Harbor Breeze RLG52NWZ5L manual

Allen + Roth L1405 instruction manual

Allen + Roth

Allen + Roth L1405 instruction manual

ViM KUBAIR F400 ECOWATT Technical manual

ViM

ViM KUBAIR F400 ECOWATT Technical manual

HIDRIA R10R-56LPS-ES50B-04C10 user guide

HIDRIA

HIDRIA R10R-56LPS-ES50B-04C10 user guide

BLAUBERG Ventilatoren CENTRO-M 100 L user manual

BLAUBERG Ventilatoren

BLAUBERG Ventilatoren CENTRO-M 100 L user manual

Triangle Engineering HEAT BUSTER SPL Series owner's manual

Triangle Engineering

Triangle Engineering HEAT BUSTER SPL Series owner's manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

2
These technical specifications state a row of manufactured sizes and models of smoke dampers (further only dampers)
DM-S. It is valid for production, designing, ordering, delivery, assembly and operation.
1. Description.........................................................................................................................
3
2. Design................................................................................................................................
4
3. Dimensions, weights...........................................................................................................
4
4. Placement and Assembly....................................................................................................
6
5. Statement of installations....................................................................................................
7
6. Pressure loss and Noise data..............................................................................................
15
7. Electrical Components, Connection Diagrams....................................................................
16
8. Material............................................................................................................................. 17
9. Inspection, testing............................................................................................................. 17
10. Logistic terms....................................................................................................................
17
11. Assembly..........................................................................................................................
17
12. Entry into service and revisions.........................................................................................
18
13. Ordering key.....................................................................................................................
18
3
Smoke dampers are installed in duct served for smoke outlet. Damper closes the smoke duct.
Dampers are installed in the position "OPEN". Dampers blade automatically closes air duct using
an actuating mechanism back spring. The back spring of the actuating mechanism is started
when the thermoelectrical starting mechanism BAT is activated, when a reset button on BAT is
pushed or when a power supply of the actuating mechanism is stopped.
Working conditions
Right damper function is secured under the following conditions:
a) Maximum air circulation speed: 12 m/s
Maximum pressure difference: 1200 Pa
b) Dampers could be displaced into position “CLOSED” only in case that ventilator is
switched off. The goal is the securing of proper closing and safe function of Smoke
Damper in case of Fire.
c) The air circulation in the whole damper section must be secured as steady on whole
surface.
Damper characteristics
• Tested in accordance with EN 1366-2
• Classified acc. to EN 13501-3+A1 as E 30 ve, ho (i↔o) S or E 90 (ho i→o) or E 60 (ho i→o) S or
E 90 (ve i→o) S
• Fire resistance ES 30 (ES 60, E 90)
• ES Certificate of conformity No. 1391-CPR-2016/0083
• Declaration of Performance No. PM/DM-S/01/20/1
• Hygienic assessment of fire dampers - Report No. 1.6/pos/19/19b
Operation of the dampers does not depend on the direction of air circulation. The dampers can
be located in an arbitrary position.
Dampers are suitable for systems without abrasive, chemical and adhesive particles.
Dampers are designed for macroclimatic areas with mild climate according to EN 60 721-3-3.
Temperature in the place of installation is permitted to range from - 30°C to + 50°C.
4
DM-S is always equipped by actuating mechanism BFL (BFN, BF) 24-T (further only "actuating
mechanism"). After being connected to power supply AC/DC 24V, the actuating mechanism
displaces the damper blade into operation position "OPEN" and at the same time it pre-stretches
its back spring. When the actuating mechanism is under voltage, the damper blade is in the
position "OPEN" and the back spring is pre-stretched. Time needed for full opening of the flap
blade from the position "CLOSED" to the position "OPEN" is maximum 140s. If the actuating
power supply is cut off (due to loss of supply voltage, activation of thermoelectrical actuating
mechanism or pushing the reset button on the thermoelectrical starting mechanism BAT), the
back spring displaces the damper blade into the breakdown position "CLOSED". The time of
displacing the blade from the position "OPEN" to the position "CLOSED" takes maximum 16 s. In
case that the power supply is restored again (the blade can be in any position), the actuating
mechanism starts to re-displace the damper blade into the position "OPEN". A thermoelectrical
starting mechanism BAT, which contains two thermal fuses Tf1 and Tf2, is a part of the actuating
mechanism. These fuses are activated when temperature +72 °C has been exceeded (the fuse
Tf1 when the temperature around the damper and the fuses Tf2 when the temperature inside the
air-conditioning piping has been exceeded). After the thermal fuse Tf1 or Tf2 has been activated,
the power supply is permanently and irreversibly cut off and the actuating mechanism, by means
of the pre-stretched spring, displaces the damper blade into the breakdown position "CLOSED".
1 Damper body 3 Actuating mechanism
2 Damper blade 4 Inspection hole for camera
Dimensions
5
Weight and effective area
- - 2,6 0,0057 BFL
- - 2,8 0,0097 BFL
- - 2,9 0,0125 BFL
- - 3,2 0,0168 BFL
- - 3,3 0,0217 BFL
- - 3,5 0,0273 BFL
- 5 4,0 0,0440 BFL
28 38 4,6 0,0715 BFN
45,5 55,5 4,9 0,0886 BFN
48 58 5,0 0,0918 BFN
70 80 5,5 0,1176 BFN
120 130 6,6 0,1863 BFN
185 195 14,0 0,2138 BF
For round smoke damper the open damper blade overlaps the damper body from dimension
250 by the “c” or “a” and “c” values. These values are specified in the Tab. 3.2.1.
Value has to be respected when projecting related air-conditioning piping.
6
Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
The distance between the smoke damper and the construction (wall, ceiling) must be min. 75mm.
In case that two or more dampers are supposed to be installed in one fire separating construction,
the distance between the adjacent dampers must be min. 200 mm according to EN 1366-2
paragraph 13.5.
The control mechanism has to be protected (covered) against damage and pollution during
installation process.
All smoke dampers have to be closed during installation process. The damper body should not
be deformed in the course of bricking in. Once the damper is built in, its blade should not grind
on the damper body during opening or closing.
Installation opening dimensions
Dampers are with rubber tightness and glued all the way around.
7
Statement of installations
Examples of smoke damper installing
The smoke damper can be installed into a solid wall construction made e.g. of normal
concrete/masonry, porous concrete with minimum thickness 100 mm or into solid ceiling
construction made e.g. of normal concrete/porous concrete with minimum thickness 150 mm.
Recommended installation openings are specified in Fig. 5.
The smoke damper can be installed into a gypsum wall construction with minimum thickness
100 mm
The smoke damper can also be installed outside of wall (ceiling) construction.
Damper installed in a solid wall construction. Space between damper and wall is filled
by mortar, gypsum or another approved fire sealing system for damper installation. ES 30 6
Damper installed in a solid wall construction. Space between damper and wall is
filled by mineral stone wool (min. density 140 kg/m³) or another approved fire
insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness 1 mm.
ES 30 7
Damper installed in a gypsum wall construction. Space between damper and wall is
filled by mortar, gypsum or another approved fire sealing system for damper
installation.
ES 30 8
Damper installed in a gypsum wall construction. Space between damper and wall is
filled by mineral stone wool (min. density 140 kg/m³) or another approved fire
insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness 1 mm.
ES 30 9
Damper installed in a solid ceiling construction. Space between damper and ceiling
is filled by mortar, gypsum or another approved fire sealing system for damper
installation.
ES 30 10
Damper installed in a solid ceiling construction. Space between damper and wall is
filled by mineral stone wool (min. density 140 kg/m³) or another approved fire
insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness 1 mm.
ES 30 11
Damper installed outside of a solid wall construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system for damper
installation.
ES 30 12
Damper installed outside of a solid wall construction. Space between damper and
wall is filled by mineral stone wool (min. density 140 kg/m³) or another approved fire
insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness 1 mm.
ES 30 13
Damper installed outside of a gypsum wall construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system for damper
installation.
ES 30 14
Damper installed outside of a gypsum wall construction. Space between damper and
wall is filled by mineral stone wool (min. density 140 kg/m³) or another approved fire
insulation system. Surface is covered by fire protection mastic (Promastop P,K) or
equal min. thickness 1 mm.
ES 30 15
Damper installed outside of a solid ceiling construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system for damper
installation.
ES 30 16
Damper installed outside of a solid ceiling construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system for damper
installation.
ES 30 17
Damper installed outside of a solid ceiling construction. Space between damper and
wall is filled by mortar, gypsum or another approved fire sealing system for damper
installation. BEWARE OF FIRE SIDE!
E 90, ES 60 18
Damper installed outside of a gypsum wall construction. Space between damper and
wall is filled by mortar and gypsum or another approved fire sealing system for
damper installation. BEWARE OF FIRE SIDE!
ES 90 19
8
1 Smoke damper DM-S
2 Mortar or gypsum
1 Smoke damper DM-S
3
Fire protection mastic Promastop P,K or equal min.
2Stuffing box (mineral stone wool min. density 140 kg/m³)
or another approved fire sealing system for damper
installation
thickness 1 mm
9
1 Smoke damper DM-S
2 Mortar or gypsum
1 Smoke damper DM-S
3
Fire protection mastic Promastop P,K or equal min.
2Stuffing box (mineral stone wool min. density 140 kg/m³)
or another approved fire sealing system for damper
installation
thickness 1 mm
10
1 Smoke damper DM-S
2 Mortar or gypsum
1 Smoke damper DM-S
3
Fire protection mastic Promastop P,K or equal min.
2Stuffing box (mineral stone wool min. density 140 kg/m³)
or another approved fire sealing system for damper
installation
thickness 1 mm