Maple Systems IO-SD3200I User manual

USER MANUAL
MAPLE
MODULAR
PLC
Digital IO Modules
•
IO-
SD3200I
•
IO-
SD0032PI
•
IO-
SD1616PI
•
IO-
SD0808R
•
IO-
SD0016R
•
IO-
SD0032PPWM

- 2 -
Contents
Module List............................................................ 7
General Specifications............................................. 8
Technical Specifications.......................................... 9
Wiring
....................................................................
10
Input/Output
Type
...............................................
14
Appearance and Dimensions ................................. 15
Product Warranty .................................................. 19

- 3 -
Before You Start
This manual contains important information on the use and operation of this device. Please
read all the information carefully for optimal performance and to prevent any damage or misuse
of the device.
To keep products safe, all activities including product installation, wiring operation, and
maintenance are required to be treated by trained personnel.
Reproduction of contents, in whole or part of this manual, without written permission from
MAPLE SYSTEMS Inc. is prohibited.
Safety symbols are classified into two categories, “WARNING” and “CAUTION”.
Warning: This symbol describes situations that could cause major or fatal injury to the
user.
Caution: This symbol describes situations that may cause minor injury or damage to the
device.
SAFETY SYMBOLS USED IN THIS PRODUCT MEAN:
This symbol warns the user of potential hazards.
This symbol warns the user of uninsulated voltage within the unit that can cause
dangerous electric shock.
Keep this manual near the operating devices so it can be easily checked.

- 4 -
Design Precautions ( Warning)
Please install a safety circuit to protect the entire control system in case of an unexpected
power shutdown or PLC module malfunction. Such anomalies may severely compromise the
integrity of the overall system.
External to the PLC, please install circuits and switches to safeguard the system from
mechanical damages (ex. emergency stop, upper/lower limit switches, forward/reverse
direction interlocking circuits, etc)
When the PLC detects either of the following failure conditions, it may stop operation and turn
off all outputs.
-The overcurrent protection or overvoltage protection of the power supply module is
activated.
-The PLC CPU detected a failure, such as the watchdog timer error or module
installation failure, with its self-diagnostic function.
In addition, all outputs may be turned on when there is a failure that the PLC CPU cannot
detect, such as in the relay or TR terminal. Build an extra monitoring circuit that will monitor any
output signal that could cause serious accidents.
A greater than normal current passed through the PLC for an extended period of time, or a
short-circuited load flowing through the output module may cause a fire.
Build a circuit that turns on the external power supply after the PLC power supply is turned on.
If the external power supply is turned on first, it could result in output failure or malfunction.
In order to ensure that the system operates safely, please configure an interlock circuit in the
scan program for the following situations:
-When exchanging data with a computer or other devices.
-When operated by a computer or other devices.
Not doing so could result in output failure or malfunction.
Precautions for design ( Caution)
Do not bundle the input/output signal or communication cables with the main circuit and power
cables. They should be installed at least more than 100 mm (3.94 inches) apart. Not doing so
could result in output failure or malfunction.

- 5 -
Precautions for mounting ( Caution)
Use the PLC in an environment that meets the general specifications given in this manual.
Using this PLC in any environment outside the range of the general specifications could result
in electric shock, fire, malfunction, or damage to or deterioration of the product.
Please ensure that each module is installed correctly in its place. Loosely or incorrectly
installed pieces may result in malfunction, failure, or free-fall.
The PLC power supply should be turned off before mounting the module. Not doing so could
cause an electric shock or damage to the device.
Install I/O devices or extension connectors correctly. If they are installed incorrectly, it may
result in an input or output failure.
Do not convey direct vibration into the PLC. Doing so could cause electric shock, fire or
malfunctions.
After wiring work, please make sure to close the terminal cover before turning on the power for
the PLC system.
Precautions for wiring ( Warning)
Make sure to check the device’s rated voltage and circuit arrangement before wiring. Failure to
do so may cause electric shock or damage to the device.
Make sure to close the terminal cover before turning on the power of the PLC system after
wiring work. Failure to do so may cause electric shock.
Precautions for wiring ( Caution)
Make sure to check the device’s regular voltage and sequence of terminals. Failure to do so
may cause fire, electric shock and malfunctions.
When grounding the FG ground terminals, be sure to conduct the product with at least D type
(Class 3) grounding. Not doing so could result in electric shock or malfunctions.
When wiring, make sure that wiring debris does not enter the module. Failure to do so may
cause fire, equipment damage or malfunctions.

- 6 -
Precautions for wiring of Digital Input/Output Module ( Caution)
Select a cable considering ambient temperature and allowable current AWG 22 (0.3 mm2) or
more is recommended.
If the wiring is too close to a heat-generating device or directly contacted with oil for long
periods of time it may cause a short circuit, breakdown or malfunction.
Precautions for test run and repair ( Warning)
Please do not touch the terminals when the power is on. Doing so could cause an electric
shock or malfunctions.
When cleaning or tightening the screws, turn off the power of the PLC and all other systems.
Failure to do so could cause an electric shock or malfunctions.
Do not charge, disassemble, heat up, short, or solder the battery. Doing so could cause the
battery to heat up, rupture, or ignite, thereby harming the user.
Precautions for test run and repair ( Caution)
Do not dissociate the PCB from the module’s casing or make any modifications to the device.
Doing so may cause fire, electric shock, or malfunction.
When mounting or separating the module, make sure to turn off power to the PLC and all other
devices. Failure to do so could cause an electric shock or malfunctions.
Use radio, walkie-talkie, or cellphone devices at least 30cm away from the PLC. Not doing so
could result in malfunction.
Precautions for disposal ( Caution)
When the product is disposed of, it should be done according to your country’s regulations for
similar types of industrial waste. Not doing so may cause an occurrence of toxic substances or
explosions.

Digital IO Module List
- 7 -
Category Model Name
I/O Points
Detail
Input Module IO-SD3200I DI-32 DI 32 points, DC 24 V, Sink/Source
(Terminal Block Type)
Output Module
IO-SD0032PI DO-32 DO 32 points, DC 24 V, TR Source
(Terminal Block Type)
IO-SD0016R DO-16 DO, Relay Output 16pts, 2A
Input/Output
Module
IO-SD0808R DI-8, DO8 DI 8pts, Relay Output 8pts, 2A
IO-SD1616PI DI-16, DO-16 DI 16 points, DO 16 points, (TR
Source, Terminal Block Type)
PWM
Output Module IO-SD0032PPWM
DO-32
(Including
PWM)
DO 32 points. DC 24 V
(TR Source)
PWM Output 12 points
(Duty Cycle Guarantee:
1~4000 Hz
Max. output frequency:
65 kHz
Duty Cycle Resolution: 1/1000)

General Specifications
- 8 -
Items Specification Standards
Ambient Temp. -10℃–65℃-
Storage
Temp. -25℃–80℃-
Ambient
Humidity 5–95% RH, Not Condensed -
Storage
Humidity 5–95% RH, Not Condensed -
Vibration
For Discontinuous Vibration
IEC 61131-2
Frequency Acceleration Amplitude Times
5 ≤f < 9 Hz - 3.5 mm X, Y, Z Each direction,
10 times
9
≤
f
≤
150
Hz
9.8
m/s
2
(1G)
-
Continuous
Vibration
Frequency Acceleration Amplitude Times
5 ≤f < 9 Hz - 1.75 mm X, Y, Z Each direction,
10 times
9
≤
f
≤
150
Hz
4.9
m/s
2
(0.5G)
-
Shock
Max. impact acceleration: 147 m/s2(15G)
Authorized time: 11 ms
Pulse wave: Sign half-wave pulse (3 times each in X, Y, Z)
IEC 61131-2
Noise
Square Wave
Impulse Noise ±2 kV -
Electrostatic
Discharge Voltage: ±4 kV (contact), ±8 kV (air) IEC 61131-2
IEC 61000-4-2
Radiated
Electromagnetic
Field Noise
80–1000 MHz, 10 V/m IEC 61131-2
IEC 61000-4-3
Fast Transient
Burst Noise
Unit Power
Module
Digital I/O
(24 V or
more)
Digital I/O
(less than 24V)
Analog I/O
Comm. interface
IEC61131-2
IEC61000-4-4
Voltage 2 kV 2 kV 1 kV
Ambient
Conditions No corrosive gas or dust
Altitude
2,000
m
or
less
Pollution
Pollution
Degree
2
or
less
Cooling
Type
Natural
air
cooling

Technical Specifications
- 9 -
Technical Specifications – PWM Module
Items DC Input Relay Output TR Output
Rated I/O Voltage DC 24 V AC 220 V / DC 24 V DC 12V / 24 V
Rated I/O Current 4mA 1 point 2 A
COM 5 A
1 point 0.2 A
COM 2 A
On Voltage/Current DC 19 V/3 mA
- -
Off Voltage/Current DC 6 V/1 mA
- -
Response
Time
Off →On 3 ms or less 10 ms or less 1 ms or less
On →Off 3 ms or less 5 ms or less 1 ms or less
Operation Indication LED will be ON when the input is ON
Insulation Type Photocoupler
insulation Relay insulation Photocoupler
insulation
Input Type Sink/Source
- -
Output Type
-
Relay Source
Diagram
※The relay output must be less than 64 points per station.
※Maximum expansion number of IO-SD0016R is up to 2 modules.
※Maximum expansion number of IO-SD0808R is up to 4 modules.
Items
PWM Output
Frequency
Range
(Guarantee DUTY Ratio)
1 Hz
–
4000 Hz
Max Frequency
65 kHz
DUTY Ratio Resolution 0.0–100.0% (resolution 1/1000)
RAMP Control Frequency RAMP, DUTY ratio RAMP control

Wiring
- 10 -
IO-SD0016R

Wiring
- 11 -
IO-SD0808R

Wiring
- 12 -
IO-SD3200I IO-SD0032PI
IO-SD1616PI

Wiring
- 13 -
IO-SD0032PPWM
PWM Output Points
* All the other points can be used as a normal output points.

Input / Output Type
- 14 -
Sink Type
Source Type

Appearance
- 15 -
▶IO-SD0032PPWM
▶IO-SD0808R ▶IO-SD0016R

Appearance
- 16 -
▶
IO
-
SD0032PI
▶
IO
-
SD3200I
▶IO-SD1616PI

Dimensions
- 17 -
▶MODULES (IO-SD3200I, IO-SD0032PI, IO-SD0032PPWM) (Unit: mm)

Dimensions
- 18 -
▶MODULES (IO-SD1616PI, IO-SD0808R, IO-SD0016R) (Unit: mm)

Product Warranty
- 19 -
Warranty Statements are included with each unit at the time
of purchase and are available at www.maplesystems.com.

MAPLE
SYSTEMS
INC.
Everett, WA 98204
Web: www.maplesystems.com
This manual suits for next models
5
Table of contents
Other Maple Systems I/O System manuals

Maple Systems
Maple Systems MLE-A0800 User manual

Maple Systems
Maple Systems IO-SA0400 User manual

Maple Systems
Maple Systems HMC3-M0808P0401T User manual

Maple Systems
Maple Systems HMC7-MIO-08 Operating and maintenance instructions

Maple Systems
Maple Systems HMC7000 Series User manual

Maple Systems
Maple Systems IO-SA0400Y User manual