
Rev: June 10, 2023 12:10 PM
Max-Air Technology, Inc. • 114 Resource Drive • Wentzville, MO 63385 • United States of America
Tel
+1.636.272.4934
•
Toll
Free
888.842.9998
•
Fax
636.272.4937
•
www.maxairtech.com
•
[email protected]11
File Name: Max-Electric_IOM_EFS550_650-HVLV-MOD.pdf
Website
After completing all mounting and wiring procedures, main power is available and battery has been connected per instructions found on page 2,
it is now possible to commission the EFS.
1. Apply power to the unit, the green LINE IN indicator is illuminated.
2. Measure (for your unit) xxx vac on terminals H & N on the EFS panel face.
2.01 EFS 120V & 24V units, measure 100-125vac on terminals H & N on the EFS panel face.
3. Press the START button on the battery unit (see item 8 page 2).
4. Wait for 30 seconds, then the LED on the battery unit itself will turn green and stay on solid.
5. Measure (for your unit) xxx vac on terminals A1 & B2 on the EFS panel face.
5.01 EFS 120V units, measure 100-125vac on terminals A1 & B2 on the EFS panel face.
5.02 EFS 24V units, measure 22.5-26.0vac on terminals A1 & B2 on the EFS panel face.
6. The yellow CHARGE indicator is illuminated.
7. The blue BAT POWER indicator is NOT illuminated.
8. Select CLOSE actuator at the FIELD CONTROL DEVICE. The actuator will drive CLOSED.
9. Measure (for your unit) xxx vac on terminals B2 & D4 on the EFS panel face.
9.01 EFS 120V units, measure 100-125vac on terminals B2 & D4.
9.02 EFS 24V units, measure 22.5-26.0vac on terminals B2 & D4.
10. Select OPEN actuator at the FIELD CONTROL DEVICE. The actuator will drive OPEN.
11. Measure (for your unit) xxx vac on terminals B2 & F6.
11.01 EFS 120V units, measure 100-125vac on terminals B2 & F6.
11.02 EFS 24V units, measure 22.5-26.0vac on terminals B2 & F6.
12. Move the Fail Position Selector switch to the OPEN position, and the green FAIL OPEN indicator is illuminated. This will have no eect on the position of
the ACTUATOR.
13. Move the Fail Position Selector switch to the CLOSE position, and the red FAIL CLOSED indicator is illuminated. This will have no eect on the position of
the ACTUATOR.
14. Disconnect MAIN power from the EFS.
15. The ALARM will start beeping on the battery unit, once every 30 seconds until power is restored.
16. The green LINE IN indicator will turn o.
17. The yellow BAT CHARGE indicator will turn o.
18. The blue BAT POWER indicator will be illuminated.
19. The commands received from the FIELD CONTROL DEVICE will have no eect on the positioning of the actuator.
20. Measure 0 vac on terminals H & N (all models).
21. Measure 0 vac on terminals A1 & B2 (all models).
22. Move the Fail Position Selector switch to the CLOSE position, the red FAIL CLOSE indicator is illuminated and the actuator will drive CLOSED. The FIELD
CONTROL DEVICE will have no eect on the position of the actuator in this mode.
23. Measure (for your unit) xxx vac on terminals B2 & D4.
23.01 EFS 120V units, measure 100-125vac on terminals B2 & D4.
23.02 EFS 24V units, measure 22.5-26.0vac on terminals B2 & D4.
24. Move the Fail Position Selector switch to the OPEN position, the green FAIL OPEN indicator is illuminated and the actuator will drive OPEN. The FIELD
CONTROL DEVICE will have no eect on the position of the actuator in this mode.
25. Measure (for your unit) xxx vac on terminals B2 & F6.
25.01 EFS 120V units, measure 100-125vac on terminals B2 & F6.
25.02 EFS 24V units, measure 22.5-26.0vac on terminals B2 & F6.
26. Re-establish Main power, whereupon the unit will automatically return to normal operating mode.
27. Unit is now ready for automatic operation.
Commissioning
EFS 550/650 Series | Mod
Installation, Operation and Maintenance Instructions