
PAGE 1
I - Shipping And Packing List
Package 1 of 2 contains:
1 - Energy Recovery Ventilator Assembly
1 - Outdoor Fresh Air Hood w/ Filter
1 - Outdoor Exhaust Hood w/ Barometric Dampers
Package 2 of 2 contains:
1 - Balancing Damper Assembly
1 - Platform Support Rail
2 - Door Panels
1 - Bag Assembly
1 - Roll of ¾" x 1 ¼" gasket
1 - 272" of 18" x ½" gasket
1 - Field Wiring Harness
1 - Adapter Wiring Harness
10 - #14 Screws
30 - #10 x ½" Gold Screws
1 - Installation Instructions
II - Shipping Damage
Check unit for shipping damage. Receiving party should
contact last carrier immediately if shipping damage is
found.
III - General
Theseinstructionsareintendedasageneralguideanddo
not supersede local codes in any way. Authorities having
jurisdiction should be consulted before installation.
IV - Requirements
When installed, the unit must be electrically wired and
grounded in accordance with local codes or, in absence of
local codes, with the current National Electric Code,
ANSI/NFPA No. 70.
V - Application
Unitary Energy Recovery Ventilator (UERV)are used with
3 to 6 ton rooftop units equipped with a balancing
damper assembly. These wheels conserve energy by
mixing warmer air with cooler air in the following manner:
Recovery Wheel Mode
The Recovery Wheel mode is accomplished by two
blowers providing continuous exhaust of stale indoor air
and replacement by equal amount of outdoor air. Energy
recovery is achieved by slowly rotating the energy
recovery wheel within the cassette frame work. In winter,
the UERV adsorbs heat and moisture from the exhaust air
stream during one half of a complete rotation and gives
them back to the cold,drier intake air supply during the
otherhalfrotation.Insummer,theprocessisautomatically
reversed. Heat and moisture are absorbed from incoming
fresh air supply and transferred to the exhaust air stream.
This process allows outdoor air ventilation rates to be
increased by factors of three or more without additional
energy penalty or increase in size of heating or air
conditioning systems.
VI - Rigging Unit For Lifting
1. Maximum weight of unit is —- 750 Lbs. (Crated)
2. Remove crating. Then remove access panel to
retrieve bag assembly. Replace access panel.
3. All panels must be in place for rigging.
4. Liftinglugsaresuppliedwiththe unit.Loosenmachine
bolts and rotate lifting lug.
CAUTION
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.
WARNING
Electric shock hazard. Can cause injury
or death. Before attempting to perform
any service or maintenance, turn the
electrical power to unit OFF at
disconnect switch(es). Unit may have
multiple power supplies.
MAXA-MI$ERÔ
UNITARY ENERGY RECOVERY VENTILATOR
MODEL VR028A15M/H & VR028A25H (STATIONARY)
INSTALLATION
INSTRUCTIONS 035-19268-002-A-0709 / R28A-18YDW
VII - Installation
1. Disconnect all power to rooftop unit.
2. Remove the rooftop unit horizontal and return air
access panels. Also remove any hoods and/or power
exhaust equipment. Discard hoods, power exhaust
equipment horizontal supply and return air access
panels. See Figure 1.
3. Remove return duct cover in the floor of rooftop unit.
ETL Certified per UL 1995
and CSA 22.2
Energy recovery COMPONENT
certifiedto the AHRIAir-to-Air Energy
Recovery Ventilation Equipment
Certification Program in accordance
with AHRI Standard 1060-2000.
Actual performance in packaged
equipment may vary.