1.2.3 Evaporator Sections
The evaporator section includes the evaporator coil,
two (2) blower motor assemblies, thermostatic
expansion valve, heater coil assembly, heater valve,
filter/drier, service valves and condensate drain
connections.
The evaporator coil provides heat transfer surface
for transferring heat from air circulating over the
outside of the coil to refrigerant circulating inside the
tubes; thus providing cooling. The heating coils
provide a heat transfer surface for transferring heat
from engine coolant water circulating inside the
tubes to air circulating over the outside surface of the
tubes, thus providing heating. The fans circulate the
air over the coils. The air filters (OEM supplied)
remove dirt particles from the air before it passes
over the coils. The thermostatic expansion valve
meters the flow of refrigerant entering the
evaporator coils. The heat valve controls the flow of
engine coolant to the heating coils upon receipt of a
signal from the controller. The condensate drain
connections provide a means for connecting tubing
for disposing of condensate collected on the
evaporator coils during cooling operation.
1.2.4 MCC Microprocessor
The MCC controller maintains desired temperature
set point by controlling compressor capacity, fan
speeds and heat valve operation. Refer to Section 2,
for operational sequences.
1.3 REFRIGERATION SYSTEM COMPONENT SPECIFI-
CATIONS
a.System Capacity: Cooling - 120,000 Btu/Hr (35 kW)
Heating - 126,000 Btu/Hr (37 kW)
b. Refrigerant Charge R-134a (Approximate)
NOTE
Refrigerant charge will depend on hose
lengths and diameters; or if there is an In-
Dash unit (front evaporator). The following
should only be used as a guideline.
50-2104 with 05G Compressor
13 ± 0.5 Pounds (5.9 ± 0.23 kg)
c. Compressor
Compressor 05G
No. Of Cylinders 6
Weight, (Dry) With Clutch 145 Lbs. (66 kg)
Oil Charge 5.5 pints
(2.6 liters)
d. Thermostatic Expansion Valve:
7 Ton Capacity- Adjustable
e. High Pressure Switch (HPS)
Normally Closed
Opens at: 360 ±10 psig (24.82 ±0.68bar)
Closes at: 285 ±15 psig (19.65 ±0.68bar)
f. Low Pressure Switch (LPS)
Normally Open
Opens at: 6 ±3psig (0.41 ±0.20 bar)
Closes at: 25 ±3psig(1.7±0.20 bar)
g. Water Temperature Switch (WTS) (If Equipped)
[Bus Manufacturer Supplied - Suggested close on tempera
ture rise at 105°F(41°C)]
1.4 ELECTRICAL SPECIFICATIONS - MOTORS
a. Evaporator Blower/Motor
Evaporator Motor Brushless
24 VDC
Full Load Amps (FLA) ~25
Bearing Lubrication Factory Lubricated
(additional grease not required)
b. Condenser Fan Motor
Condenser Motor Brushless
24 VDC
Full Load Amps (FLA) ~7
Bearing Lubrication Factory Lubricated
(additional grease not required)
c. Temperature Sensors (All)
Input Range: -40 to 167°F(-40to75°C)
Output: NTC 10K ohms at 77°F(25°C)
d. Ambient Sensor (Controls Compressor Outputs)
Opens at: 43°F(6.1°C)
Closes at: 47°F(8.3°C)