14 IM 865
5Turn fan switch to “AUTO.” Turn system switch to
“COOL” and turn temperature setting below room tem-
perature. Unit should run in cooling mode.
6Is outdoor fan operating correctly in the right direction?
7Is compressor running correctly?
8Check the refrigerant charge using the instructions
located on compressor access panel. Replace service
port caps. Service port cores are for system access only
and will leak if not tightly capped.
9Turn thermostat system switch to proper mode “HEAT”
or “COOL” and set thermostat to proper temperature
setting. Record the following after the unit has run some
time.
aOperating Mode _____________________________
bDischarge Pressure (High) _________________PSIG
cVapor Pressure at Compressor (Low) ________PSIG
dVapor Line Temperature at Compressor ________°F.
eIndoor Dry Bulb___________________________°F.
fIndoor Wet Bulb __________________________°F.
gOutdoor Dry Bulb _________________________°F.
hOutdoor Wet Bulb _________________________°F.
iVoltage at Contactor _____________________Volts
jCurrent at Contactor _____________________Amps
kModel Number ______________________________
lSerial Number_______________________________
mLocation ___________________________________
nOwner _____________________________________
oDate_______________________________________
10 Adjust discharge air grilles and balance system.
11 Check ducts for condensation and air leaks.
12 Check unit for tubing and sheet metal rattles.
13 Instruct the owner on operation and maintenance.
14 Leave “INSTALLATION” and ”USE AND CARE“
instructions with owner.
Operation
Most single phase units are operated PSC (no start relay or
start capacitor). It is important that such systems be off for a
minimum of 5 minutes before restarting to allow equalization of
pressures. The thermostat should not be moved to cycle unit
without waiting five minutes. To do so may cause the compres-
sor to stop on an automatic open overload device or blow a
fuse. Poor electrical service can cause nuisance tripping in
overloads or blow fuses.
IMPORTANT: The compressor has an internal overload protec-
tor. Under some conditions, it can take up to 2 hours for this
overload to reset. Make sure overload has had time to reset
before condemning the compressor.
Some units are equipped with a time delay control (TDC1). The
control allows the blower to operate for up to 60 seconds after
the thermostat is satisfied.
Auxiliary Heat
Control System Operation
1In the cooling mode, the thermostat will, on a call for
cooling, energize the compressor contactors and the
indoor blower relay. The indoor blower can be operat-
ed continuously by setting the thermostat fan switch at
the “ON” position.
2In the heating mode, the thermostat will energize one
or more supplementary resistance heaters, if included.
Replacement Parts
To find your local McQuay Certified Parts Distributor, go to
www.mcquay.com and select Parts Locator.
Charge Information
Refer to the appropriate charge chart included in this manual.
Troubleshooting
Refer to the troubleshooting chart included in this manual.
Wiring Diagrams
Refer to the appropriate wiring diagram included in this manual.
Only electric heater kits supplied by this manufacturer as
described in this publication have been designed, tested,
and evaluated by a nationally recognized safety testing
agency for use with this unit. Use of any other manufactured
electric heaters installed within this unit may cause haz-
ardous conditions resulting in property damage, fire, bodily
injury or death.
▲▲DANGER
!
Figure 13: Heater Kit Installation
ILL I312