EM-7032 Rev.1 P. 1 / 5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
NPN TRANSISTOR OUTPUT MODULE, 16 points
(Tension clamp terminal block) MODEL
R80DCT16A2
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
NPN transistor output module...........................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside a panel.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■GENERAL PRECAUTIONS
• Before you remove or mount the unit, turn off the power
supply and input signal for safety.
• Switches on the side of the module can be set for mainte-
nance only while the power supply is off. Do not access
them while the power is supplied.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■EXCITATION SUPPLY
• Output connector: Rated current 3 A DC (rated current 3
A for internal fuse (slow blow fuse i2t (A2sec) max. 5.04).
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
INSTALLATION
■HOW TO MOUNT THE MODULE ON DIN RAIL
A
B
• I/O Module
Confirm that the locking clamps of the I/O module are set.
Insert the module in parallel to the next one while aligning the grooves of
both modules (A & B in the above figure).
Maintain it perpendicularly to the rail.
More I/O modules can be added in the same manner.

R80DCT16A2
EM-7032 Rev.1 P. 2 / 5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
• Protective Cover
Hook
Groove
When removing the cover, pull it out while squeezing the hooks inward.
The protective cover is to be attached over the connected I/O module
at the right end.
Align the hooks on the cover with the grooves of the module and slide it
straight until the hooks are latched.
■HOW TO UNMOUNT THE MODULE FROM DIN RAIL
• Release the locking clamps and pull out straight the module.
• Removing an intermediate module
Note 1: Be careful not to hurt your hand by pointed edges of the internal
bus connector.
Note 2: I/O modules cannot hold tightly on the DIN rail by themselves
without power/network module.
Secure them to the position if necessary by using DIN rail end
plates.

R80DCT16A2
EM-7032 Rev.1 P. 3 / 5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
Module Address
Setting DIP SW
■FRONT VIEW ■SIDE VIEW
Discrete Output
Satus Indicator LEDs
Status Insicator LED
Internal Bus Connector
Output Connector
RUN
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
SW1
On
8
7
6
5
4
3
2
1
Terminator
DIP SW
SW2
On
■INDICATOR LED
LED
OPERATION
FUNCTION
Status OFF
Upper communication: Stopping
or abnormal
Internal communication: Normal
Red ON
Upper communication: Stopping or
abnormal
Internal communication: Abnormal
Green ON
Upper communication: Normal
Internal communication: Normal
Orange ON
Upper communication: Normal
Internal communication: Abnormal
Orange Blinking Circuit abnormality
(blinking in 400 msec. cycle)
Input
Status
OFF Discrete input is OFF.
Green ON Discrete input is ON.
■INPUT CONNECTOR ASSIGNMENT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
PIN NO.ID FUNCTION
1 Do1 Output 1
2 Do2 Output 2
3 Do3 Output 3
4 Do4 Output 4
5 Do5 Output 5
6 Do6 Output 6
7 Do7 Output 7
8 Do8 Output 8
9 Do9 Output 9
10 Do10 Output 10
11 Do11 Output 11
12 Do12 Output 12
13 Do13 Output 13
14 Do14 Output 14
15 Do15 Output 15
16 Do16 Output 16
17 0V Exc. supply 0V
18 24V Exc. supply 24V
■OPERATING MODE SETTING
(*) Factory setting
Note) Be sure to set unused SW 1-5 through 1-8 to OFF.
• MODULE ADDRESS
Selectable between 0 and 15, with DIP switch 1-1 to 4.
Set the module addresses consecutively starting at 0 such that
there is no duplicate or vacant address.
MODULE ADDRESS SW1
1234
0 OFF OFF OFF OFF
1 ON OFF OFF OFF
2 OFF ON OFF OFF
3 ON ON OFF OFF
4 OFF OFF ON OFF
5 ON OFF ON OFF
6 OFF ON ON OFF
7 ON ON ON OFF
8 OFF OFF OFF ON
9 ON OFF OFF ON
10 OFF ON OFF ON
11 ON ON OFF ON
12 OFF OFF ON ON
13 ON OFF ON ON
14 OFF ON ON ON
15 ON ON ON ON
■TERMINATOR DIP SW
TERMINATOR SW2
Without (*) OFF
With ON

R80DCT16A2
EM-7032 Rev.1 P. 4 / 5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
PC CONFIGURATOR
The following parameters can be set using PC Configurator Software (model: R80CFG)
Refer to the users manual for the R80CFG for detailed operation of the software program.
ITEM SETTING RANGE DEAULT VALUE
Output at time of communication disconnection Output hold
Output clear
Output hold
Note) Settings are programmed by the PC Configurator via the Power/Network Module.
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm [inch]
115 [4.53]6 [.24]7 [.28] 6 [.24] 7 [.28]
DIN rail
(35 mm wide)
(3 [.12]) (4 [.16])
24 [.94] 72 [2.83]
55 [2.17]
.

R80DCT16A2
EM-7032 Rev.1 P. 5 / 5
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
■CONNECTION DIAGRAM
INTERNAL POWER
INTERNAL BUS
EXC. SUPPLY
1
5
2
3
6
4
7
8
10
16
17
0V
Do 1
Do 2
Do 3
Do 4
Do 5
Do 6
Do 7
Do 8
Do 16
9
Do 15
L
L
L
L
L
L
L
L
Output Connector
■OUTPUT CIRCUIT
Control
Circuit
1Do 1
16
10
Do 16
0V
+24V
18
12
13
14
15
11
Do 9
Do 10
Do 14
Do 12
Do 13
Do 11
L
L
L
L
L
L
L
L
18
CONNECTOR
WIRING INSTRUCTIONS
■• INPUT CONNECTOR
Unit side connector: MC1,5/18-GF-3,5 (Phoenix Contact)
Cable side connector: FMC1,5/18-STF-3,5 (Phoenix Contact)
(included in the package)
Applicable wire size: 0.2 − 1.5 mm2
Stripped length: 10 mm
Recommended solderless terminal
• AI0,25−10YE 0.25 mm2(Phoenix Contact)
• AI0,34−10TQ 0.34 mm2(Phoenix Contact)
• AI0,5−10WH 0.5 mm2(Phoenix Contact)
• AI0,75−10GY 0.75 mm² (Phoenix Contact)
• A1−10 1.0 mm² (Phoenix Contact)
• A1,5−10 1.5 mm² (Phoenix Contact)