
MM600 MICRO AIR®
CLEAN AIR SYSTEMS
ELECTRICAL INSTALLATION:
All Electrical work must be done by a
qualified electrician according to local, state
and national codes.
CAUTION: Installation can cause
exposure to live components. Disconnect
electrical power befor proceeding with
installation. Proper lockout/tag out
procedures should be used.
Determine the location for the Motor Control Box.
Make electrical connections as shown in the wiring
diagram to the wires protruding from the conduit
on the side of the air cleaner.
Connect supply power to the Motor Control Box
as shown in the wiring diagram (pg #4).
Check blower for proper rotation direction. If the
blower rotates backwards, interchange two of the
motor supply connections (L1 and L2).
Check current draw of motor. Do not exceed
specified amprage (pg #2).
GAUGE INSTALLATION:
1. Mount the gauges in the gauge bracket (Fig 3).
2. Drill 3/8” dia. holes in the cabinet (Fig. 4) and
insert P1050 gromet.
3. Connect P2806 tubing from the hole labeled “A”
(Fig 4) to the port labeled “LOW” on the 0-5”
minihelic.
4. Connect P2806 tubing from the hole labeled
“B” (Fig 4) to the port labeled “HI” on the 0-5”
minihelic
5. Connect P2806 tubing from the hole labeled “C”
(Fig 4) to the port labeled “LOW” on the 0-10”
minihelic.
6. Connect P2806 tubing from the hole labeled
“D” (Fig 4) to the port labeled “HI” on the 0-10”
minihelic.
OPERATION:
1. To start air cleaner, turn the knob to the position
labeled “ON”. To stop the unit turn the knob to
the position labeled “OFF”.
1.
2.
3.
4.
5. GENERAL MAINTENANCE:
1. No lubrication is required for the motor because it
is a permanent pre-lube design. Excessive dirt / oil
should be periodically removed.
CHANGING FILTERS:
CAUTION: Always turn the air cleaner
off before changing filters.
1. The MM600 is equipped with dual filter gauges
(0-5” for pre-filter and 0-10” for main filters).
The pre-filter should be removed, cleaned and
inspected when the gauge labeled pre-filter reads
2” W.C. The main filter should be removed and
replaced when the gauge labeled main filter reads
between 6” W.C. and 8” W.C. (depending on
desired air flow).
2. The pre-filters should be cleaned in a detergent
solution to remove dirt and oil residue.
3. Rinse the pre-filters thoroughly with water, shake
dry and replace in the unit.
4. Re-start the air cleaner.
!
!
Figure 3
Figure 4
!