Minco CT224 Manual

Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com
CT224 SetupTutorial
Table of Contents
1. Introduction
2. Configuring Controller for Operation
A. Example1–OverTempOperationwithHysteresis@5ºF.
B. Example2–UnderTempOperationwithHysteresis@5ºF.
C. Example3–OverTempOperationwithAlarmandOutputTripping
Separately
D. Example4–UnderTempOperationwithAlarmandOutputTripping
Separately
E. Example5–OverTempOperationwithPressingEnter
F. Example6–OverTempOperationwithManualReset
E. Example7–OverTempOperationwithOffset
F. Example8–HowtoRenameZones
G. Example9–HowtoExerciseRelays
H. Example10–How toFreezeOutputs
3. Definition of Terms / Use forOperation
A.Menu
B.Program

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 2
1. Introduction
Thissetuptutorialwill stepthroughsomeofthe mainwaysthattheCT224 canbe
used. Aftercompletion,the user willhaveagoodunderstandingofthefeaturesand
howtousethem. Eachsectionwillbuildoffoftheonebeforeit.S
ButtonsScrolling through Zones Main Menu Sub Menu
Back Returns to
monitor zones Returns to
previous step
Forward Up Changes
current value
in step
Back Down Scrolls through
current step
Forward Enters into
selected menu
option
Goes to next
step
Table1QuickReferenceGuide
Note: Holdingdownanybuttonfor 3secondsandyouwillbeputintothemain
menu.
2. ConfiguringController forOperation
Example1:OverTemp Operation with Hysteresis @ 5ºF
1. BeginbyplacingtheCT224onadeskortable.
2. Connectonesenortothe unit,notewhichtypeofsensor you haveconnected.
3. ApplypowertotheCT224. Thedisplayshouldlightandthemessage“Initializing
Inputs”willbedisplayed. Afewsecondslatertheunitwilldisplay“Zone1Off”.
4. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed. Thiswilltakeabout3seconds.
5. Movethecursor to2.“Configuration”,thenpressEnter.
6. Select1.“ChangePasswords”and press Enter.
7. Select“Yes”bypressingtheuparrow,thenEnter.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 3
8. Select“ProgramPassword”,andpressEnter.
9. Enter1111forpasswordbyusingtheuparrowandrightarrow. Thiswillenable
passwordprotectionfor the“Configuration Menu”option,inthemainmenu.
10. PressBacktoexitonemenulevel.
11. Select2.“Configuration”,andthenEnter.
12. Youwillseethepromptto enterthepassword. Enter1111andpressenter. You
willthenenter the configurationmenu.
13. Select2.“ChangeProgram”,and thenEnter.
14. LeavealloutputssettoN for“ReverseActingoutputs?”,thiswillcausealloutputs
tobedirectacting. PressEnter.
15. Set“Temperature Scale” to“F”fordegreesFahrenheit,byusingtheuparrow,then
pressEnter.
16. Set“Zoneto bedisplayedduringnormaloperation”to “Any”,thenpressEnter.
ThiswillallowtheusertochoosethezonethatwillbedisplayedontheCT224.
17. Set“Minutes ofAlarmSilencewhenakeyispressed” to1minute,thenpressEnter.
Thiswillcausethe alarmtoresound1minute aftertheoutputhasbeen tripped,if
thecurrentreadingisstillabovethetripsetting.
18. Set“Ifaninputfails” to“SoundAlarm”,thenpressEnter. Thiswillcausethealarm
tosoundiftheinputfails.
19. Set“Zone1Chooseinputtype:” tothe inputtype thathas beenconnected to
Zone1onthecontroller,thenpressEnter.
20. Set“Zone1Trip1:” to 85ºF, thenpressEnter.
21. Set“Zone1Trip1:Trip Over or Under”to“Over”,then press Enter.
22. Set“Zone1Trip1:Sound Alarmon trip” to“Yes”, thenpressEnter.
23. Set“Zone1Trip1:Outputs to trip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
24. Set“Zone1Trip1: UntripOutputsby”to“UsingHysteresis”,thenpressEnter.
25. Set“Zone1Trip1:SetHysteresis:” to “5”,thenpressEnter.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 4
26. Thedisplaywillread“Zone1Trip2:Off”. Press&holdEnteruntilCT224re-
initializesthecontroller(about3seconds).
27. Thecurrenttempreadingwillnow be displayedonthecontrollerforZone1.
28. Heatthe sensor until thealarmandoutputtrip. (Hold onto thesensortoincrease
thetemperatureofthesensororplaceinsideofaplasticbagandthenplacethe
bagandsensorintoacupofwarmwater).
29. PressEnter to silencethe alarm. (Note:With theconfigurationsettingsabove, the
alarmwillcontinueturningoneveryminuteuntilthetemperature fallsbelowthe
trippointandhysteresisband).
30. Maintainthesensorabove85ºF. After1minutethealarmwillresound. Press
Entertoturnthealarmoff.To preventthealarmfromresoundingallow
temperaturetofallbelowhysteresislevelforalarmtrippoint.
31. Allowthesensortocool so thatOutput1willuntrip. Output1 willturnoffat80º F,
duetothehysteresissetting of5.
32. WiththeCT224operating,removeawirefromthesensorononeoftheterminals
ontheCT224.
33. Thealarm willsoundbecause theCT224 is configuredto soundthealarm ona
failedsensor.
34. Reconnectthewirethatwasremoved.
35. TheCT224willresumereadingtheinputandturnoffthealarm.
YouhavenowconfiguredZone1totriponanovertemp condition using hysteresisto
untrip. Thismeansthe controllerwilltrip the outputs when the sensor reads a value of
75ºForhigherandwillnotuntripuntilbelow80ºF.
Example2:UnderTemp Operation with Hysteresis @ 5ºF
Note:ProcedureissimilartoExample1, expect needtoconfigurecontrollerfor“Under
Tempinsteadof“OverTemp”. Followtheguidelinesbelowforcompleteinstructions
onconfiguringthecontroller
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Movethecursortooption2.Configuration,thenpressEnter.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 5
3. Youwill be promptedforapassword. Thepasswordwassetinexample,tobe
1111. Enter1111andpressEnter. Ifanyotherpasswordisentered,exceptthe
MasterPassword,theConfigurationmenuwillnotbeaccessed
4. Select2.“Configuration”,andthenEnter.
5. Youwillseetheprompttoenterthepassword. Enter1111andpressenter. You
willthenenter the configurationmenu.
6. Select2.“ChangeProgram”,and thenEnter.
7. Change“Output1”to“Y”,soOutput1willnowbereverse acting. Then press
Enter.
8. Changefrom“C”to“F”,thenpressEnter.
9. SetZoneto“Any”,thenpressEnter.
10. Set“Alarm Silence” to1 minute, thenpress Enter.
11. Set“Ifaninputfails”to“SoundAlarm”,thenpressEnter.
12. Set“Zone1”totheinput type thathasbeenconnectedtoZone1onthe
controller,thenpressEnter.
13. Set“Zone1Trip1:” to65ºF,then pressEnter.
14. Set“Zone1Trip 1:TripOverorUnder”to“Under”,thenpressEnter.
15. Set“Zone1Trip1:Sound Alarm ontrip”to“Yes”,thenpressEnter.
16. Set“Zone1Trip1:Outputstotrip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
17. Set“Zone1Trip1:UntripOutputsby”to“UsingHysteresis”,thenpressEnter.
18. Set“Zone1Trip1:SetHysteresis:”to“5”, then press Enter.
19. Thedisplaywillread“Zone1Trip2:Off”. Press&holdEnteruntilCT224re-
initializes.
20. Thecurrenttempreadingwillnow be displayedonthecontrollerforZone1.
21. Coolsensoruntilalarmandoutputtrip. (Put sensorinafreezerorplace sensor ina
bagandplaceincoldwater).

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 6
22. PressEntertosilencethealarm. (Note: Withconfigurationsetabovealarmwill
continueturningoneveryminuteuntiltempisabovetrippointandhysteresis
band).
23. Thecontactsorlogicoutputwillnowbeinitsnormalstate,duetotheoutput
configuredforreverseacting.
24. Allowsensorto heat upsothatOutput 1willuntrip. Output1 willturn off at70ºF,
duetothehysteresissetting of5º.
25. Thecontactsorlogicoutputwillnowbeinitsenergizedstateorhighstate,dueto
Output1 setforreverseacting. Settingtheoutputforreverseactingcanbea
goodwaytoprotectequipmentincaseofpowerinterruptstotheCT224.
Youhavenow configuredZone1totriponanundertempconditionusinghysteresis
tountrip. Thismeansthecontrollerwilltriptheoutputswhen the sensorreadsavalue
of65ºForlowerandwillnotuntripuntilabove70ºF. Toenter programmingthe
passwordmustbeentered.Thisshowshowthepasswordprotectioncanprevent
unauthorizedusersfrom changing thesettings.
Example3:OverTempOperationwithAlarmandOutputTrippingSeparately
1. EnterConfigurationmenu. The password1111willbeusedtogainentry. Choose
1.“ChangePassword”andpressEnter. Select “ProgramPassword”andenter0000,
thepressEnter. Thiswilldisablethepasswordprotectionforenteringthe
“ConfigurationMenu”.
2. Setalloutputsto“N”for“ReverseActingOutputs”.
3. Continuetosetthesettings from“TemperatureScale”to“Zone1Choose Input
Type”asappropriate.
4. ThefollowingsettingsbelowwillbeusetosetTrip1foranalarmat85ºFand set
Trip2foranOutputtripat90ºF.
5. Set“Zone1Trip1:” to85ºF,then pressEnter.
6. Set“Zone1Trip1:Trip Over orUnder”to“Over”,thenpressEnter.
7. Set“Zone1Trip1:Sound Alarmon trip” to“Yes”, thenpressEnter.
8. Set“Zone1Trip1:Outputstotrip:”Setalloutputsto“N”.
9. Set“Zone1Trip1:UntripOutputsby”to“UsingHysteresis”,thenpressEnter.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 7
10. Set“Zone1Trip1:SetHysteresis:”to“5”, then press Enter.
11. Set“Zone1Trip2:” to 90ºF, thenpressEnter.
12. Set“Zone1Trip2:Trip Over orUnder”to“Over”,thenpressEnter.
13. Set“Zone1Trip2:SoundAlarmontrip”to“No”,thenpressEnter.
14. Set“Zone1Trip2:Outputstotrip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
15. Set“Zone1Trip2:UntripOutputsby”to “UsingHysteresis”,thenpressEnter.
16. Set“Zone1Trip2: Set Hysteresis:”to“5”,thenpressEnter.
17. Thedisplaywillread“Zone2ChooseInputType: NoInputConnected”. Press &
holdEnteruntilCT224re-initializes.
18. Thecurrenttempreadingwillnow be displayedonthecontrollerforZone1.
19. Heatthesensor untilthe alarm trips.
20. Continuetoheatthe sensor furtheruntilOutput1 trips at90ºF. Thealarmand
outputshouldbothbetrippednow.
21. PressEntertoclearthe alarm.
22. AllowthesensortocoolsothatOutput1willuntrip. Output1willturnoffat85º F
andAlarmwillturnoffat80ºF,duetothehysteresissettingsof5.
YouhavenowconfiguredZone1Trip1onanovertempconditionusinghysteresisto
untripandZone 1Trip2 onanover tempconditionusing hysteresis tountrip. This
typeofconfigurationiscommonwhendoingovertempprotection. Thealarmgives
warningtooperatorandhighertrip willshutdownequipmentbeforeseriousdamage
results.
Example4: Under TempOperationwith Alarm andOutputTripping Separately
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Continuetoset the settingsfrom“ReverseActingOutputs”to“Zone1Choose
InputType”asappropriate.
3. Set“Zone1Trip1:” to70ºF,then pressEnter.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 8
4. Set“Zone1Trip 1:TripOverorUnder”to“Under”,thenpressEnter.
5. Set“Zone1Trip1: SoundAlarmontrip”to“Yes”, then pressEnter.
6. Set“Zone1Trip1: Outputs totrip:”Setalloutputsto“N”.
7. Set“Zone1Trip1:UntripOutputsby”to “Using Hysteresis”,thenpressEnter.
8. Set“Zone1Trip1:SetHysteresis:”to“5”, then press Enter.
9. Set“Zone1Trip2:” to60ºF, thenpressEnter.
10. Set“Zone1Trip 2:TripOverorUnder”to“Under”,thenpressEnter.
11. Set“Zone1Trip2:SoundAlarmontrip”to“No”,thenpressEnter.
12. Set“Zone1Trip2:Outputstotrip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
13. Set“Zone1Trip2:UntripOutputsby”to “UsingHysteresis”,thenpressEnter.
14. Set“Zone1Trip2: Set Hysteresis:”to“5”,thenpressEnter.
15. Thedisplaywillread“Zone2ChooseInputType: NoInputConnected”. Press &
holdEnteruntilCT224re-initializes.
16. Thecurrenttempreadingwillnow be displayedonthecontrollerforZone1.
17. Coolthesensoruntil the alarmtrips. (Putsensorinafreezerorplacesensorina
bagandplaceincoldwater.)
18. Continue tocoolthesensorfurtheruntilOutput1 tripsat 60ºF. Thealarmand
outputshouldbothbetrippednow.
19. PressEntertoclearthe alarm.
20. Allowthesensortowarmup sothatOutput1willuntrip. Output1willturnoffat
65ºFandAlarmwillturnoffat75ºF,duetothe hysteresis setting of 5.
YouhavenowconfiguredZone1Trip1onanundertempconditionusinghysteresis
tountripandZone1Trip2onanunder tempcondition using hysteresisto untrip.
Thistypeofconfigurationis common whendoingundertemperatureprotection.
Alarmgives warning tooperator and coolertemperaturewillshutdownequipment
beforeseriousdamageresults.
Example5: Over TempOperationwith Pressing Enter

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 9
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Continuetosetthesettingsfrom“ReverseActingOutputs”to“Zone1Choose
InputType”asappropriate.
3. Set“Zone1 Trip 1:”to85ºF, thenpressEnter.
4. Set“Zone1Trip2:Trip Over orUnder”to“Over”,thenpressEnter.
5. Set“Zone1Trip1:SoundAlarmon trip”to “Yes”,then pressEnter.
6. Set“Zone1Trip1:Outputstotrip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
7. Set“UntripOutputs by”to“Pressing Enter”, thenpressEnter.
8. Set“Zone1Trip1:SetHysteresis:”to“5”,then pressEnter.
9. Thedisplaywillread“Zone1Trip2:” setto“Off”.
10. Press&holdEnteruntilCT224re-initializes.
11. Thecurrenttempreadingwillnow be displayedonthecontrollerforZone1.
12. Heatsensoruntilalarmandoutputtrip.
13. PressanybuttonbutEnter tosilencethealarm.
14. PressEnterandoutputwilluntrip. If the output temperatureafter pressingEnteris
stillhighalarmwillnotresoundorretripuntiltempfallsbelow set hysteresis band.
Theoutput will alsountripregardless ofpressingEnteriftemp fallsbelow80ºF,
thehysteresisbandisstillineffectwiththe “Pressing Enter” selection.
.
YouhavenowconfiguredZone1totriponanovertempconditionusing“Enter” to
untrip. Thismeansthe controller willtriptheoutputs when the sensor reads a value of
85ºForhigherandwillnotuntrip unlessEnterispressedorthe temp fallsbelow80ºF.
Example6: Over TempOperationwith Manual Reset
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Continuetosetthe settingsfrom“ReverseActingOutputs”to“Zone1Choose
InputType”asappropriate.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 10
3. Set“Zone1 Trip 1:”to85ºF, thenpressEnter.
4. Set“Zone1Trip2:Trip Over orUnder”to“Over”,thenpressEnter.
5. Set“Zone1Trip1:Sound Alarmon trip” to“Yes”, thenpressEnter.
6. Set“Zone1Trip1:Outputstotrip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
7. Set“UntripOutputs by” to“ManualResetOnly”,thenpressEnter.
8. Set“Zone1Trip1:SetHysteresis:” to “5”, thenpressEnter.
9. Thedisplaywillread“Zone1Trip2:Off”. Press&holdEnteruntilCT224re-
initializes.
10. Thecurrenttempreadingwillnow be displayedonthecontrollerforZone1.
11. Heatsensoruntilalarmandoutputtrip.
12. Pressanybutton to silencethealarm.
13. Tountripoutput hold downanyofthebuttonsforatleast3secand move cursor
to3. “Manual Reset”,then pressEnter.
14. Thisistheonlywaytoresetthisoutput. The changeintemperaturewillhaveno
effectonthecontrolleroncetheoutput has beentripped,untilthe CT244has
beenmanuallyreset.
Youhavenow configuredZone1totriponanovertempconditionusing“Manual
ResetOnly”tountrip. This meansthecontrollerwilltriptheoutputswhen thesensor
readsavalueof85ºForhigherandwill not untripunlessthe“ManualReset”option
hasbeenselectedinthe mainmenu.
Example7: Over TempOperationwith Offset
1. Configure CT224 according tovalues inExample 1,then continue below.
2. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
3. Movethecursorto2.“Configuration”,thenpressEnter.
4. Select3.“ModifyOffsets”,andthenEnter.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 11
5. Set“OffsetforZone1:100Tenths”.
6. Press&holdEnteruntilCT224re-initializesandtheCT224will display Zone1with
currenttempreading10ºF abovetheactualtemperature.
YouhavenowconfiguredZone1withanoffsetof10ºF.Theoffsetwillallowyouto
improveaccuracyofthereadingsandallowyoutominimizetheerrorpresent.
Example8 –How to Rename Zones
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Movethe cursor to4. “Options”, thenpress Enter.
3. Select1.“RenameZones”,and thenEnter.
4. Set“NameforZone1is:”set “MINCO”,usetheuparrowforchangingthe
letters/numbers,andtherightarrowformovingtothenextletter/number.
5. AfterZonenameischanged,press&holdEnteruntilCT224re-initializesandthe
CT224willdisplaythenewZonename.
Example9 –How toExerciseRelays
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Movethe cursor to4. “Options”, thenpress Enter.
3. Select2. “ExerciseOutputs”,andthen Enter.
4. PressanykeytoExerciseOutputs. Lightsonalloutputs except thealarmshould
beon.
5. Pressanykeytoturnoffalltheoutputs.
6. Press&holdEnteruntilCT224re-initializestothenormaloperatingmode.
Youhavenow testedalltherelayoutputsexceptthealarmoutput. Exercisingthe
relayoutputsallowsyoutoquicklydetermineiftherelaysareworkingandhowyour
attachedapplicationisrespondingto therelays.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 12
Example10 –How toFreezeOutputs
1. Pressandholdanyoneofthekeysonthefrontpaneluntilthemainmenuis
displayed.
2. Movethe cursor to4. “Options”, thenpress Enter.
3. Select3.“Freeze Outputs”,andthenEnter.
4. TheCT224 will thenreturn backtothe MainMenuwiththecursorat“Monitor
Zones”,pressEnteragain.
5. TheCT224willre-initializeandreturntoitsnormaloperating mode,displaying
“OutputsAreFrozen”.
6. Toremovethe“FrozenOutputs”repeatexample10.
Youhavenowlearnedhow tofreezeandunfreeze theoutputs onthe CT224. Freezing
theoutputswilldisabletheprogramfromchangingthestateofanyoutputas long as
“OutputsAreFrozen”isdisplaythescreenoftheCT224.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 13
3. Definition of Terms / Use for Operation
A) Menu
1. MonitorZones
Selectthisoptiontoreturn to MonitoringModetoreadandevaluate
theinputsandoutputs.
2. ConfigurationMenu
TheConfigurationMenumayrequireapasswordtoenter,bydefaultnopasswordis
required. TheConfigurationMenucontainsthefollowingoptions.
1. ChangePasswords
2. Setup
3. ModifyOffsets
4. CommSettings
1. ChangePasswords -Select the password tochange. A message
askingifyouwouldliketochangeapasswordwillbeshown. Choose
‘Yes’tochangeapasswordor‘No’toexittheChangePasswordsoption.
Bysettinga passwordto0000, thepasswordwill be deactivated. The
validrangeforapasswordis 0000to9999. If apassword isalready
entered,the user willbe required toenter theexistingpassword in
ordertochangeit. If youforgetyourpassword,themasterpassword
canbeused, itisfoundonthelastpageofthismanual. Available
selectionsare:
1. ProgramPassword
2. UnlatchPassword
1. ProgramPassword –Changes thepasswordthatisused
toprotectthe Change Programoption.
2. Unlatch Password–Changesthepassword that isused
toprotectManualResetoftheOutputs.
2.Setup -Thissectionis used to configure all inputs and outputs. (May
bepasswordprotected.) When thissectionis exited,eitherdue to the
60-secondtimeoutorexited by theuser,theCT224 will automatically
resetandstartscanningwiththenewprogramsettings. The CT224 will
alsoresetwhenprogramsettingsarechangedviathecommunications
linkusingMincoSoft’sCT224Software. Thisisthemainsectionofthe
CT224configurationprocessandhasafullsectionbelow covering its
use. Seesection4B,EnteringtheProgramSettings,formore
information.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 14
3. Modify Offsets-Adjust theoffsetforeachinput zone. Theoffsets
areusedto improveaccuracyofthereadings. Thiscouldbeusefulifa
2-wireRTDisusedoraparticularvalueiscrucialinaprocess. Theoffset
canbeusedsothatlesserrorispresent. Theunitsfortheoffsetare
Tenths. So,ifthe readingisoff by-1degree(or1unit in anyother
measurement),thenumberthat should beenteredforthe offset value
is10,becausethiswillraisethevalueby10tenthsor+1degree.
4.Comm Settings –Thisselectionstepsthroughsettingthemonitor
addressandthebaudrate for theserialcommunications. Thesettings
chosen must match the settings selected by the master device that will
becommunicating with the CT224. The first screen requests the user to
entertheModbus address. Thevalidrangeof addressesisfrom1 to
247. If0is selected,theCT224 willnotmonitor the communication
lines. EachCT224isfactorysettoadefaultModbusaddress of1. If
communicationsarenotused,itisacceptabletoleavethedefault
addressat1. If multipleCT224aretobeused,theaddressesshouldbe
changedtopreventcommunicationerrors. Thenextscreenwillrequest
settingthebaudrate. Valid baud rates are:600, 1200,2400, 4800,9600,
and19200.
3. ManualReset -Usethisoptiontoresettheoutputsifatriphasoccurredand
ManualResetOnlywasselectedwhenconfiguringtheoutputs.(Maybepassword
protected.)
4. Options–OptionsMenuallowstheusertopersonalizethezone
namesandexercisetherelays.
1. RenameZones
2. ExerciseRelays
3. FreezeOutputs
1.Rename Zones –This optionis usedto personalize the display. Up to
16characterscanbeenteredtodescribetheinputlocation. Capital
letters(A-Z),numbers(0-9),andspacesareallowed.
2.Exercise Relays –Thisoption canbeused totripthe outputsfor test
purposes. Thiscanbehelpfultoverifythat wiring iscorrectandthat
connectionsaresecure. Whenselectedandrelays areintripped
condition,theunitwillkeeptheoutputstrippeduntilanotherkeyis
pressed.
3.FreezeOutputs –Selectingthisoptionwilldisabletheprogramfrom
changingthestateofanyoutput. Themessage“Outputsare Frozen”is
displayedon the screen when this selection is active and the CT224 is in
MonitorMode. Tounfreezetheoutputs,choosethisoptionagainand
theFreezeOutputsoptionwillbedisabled.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 15
B) Program
Usingthekeypad to configuretheCT224,use theSetupWorksheetprovideinthe
manualtospeed uptheprocess andreduceerrors. Due to the60-second timeoutin
theCT224,itisbesttofillouttheSetupWorksheetbeforeconfiguringtheunit. This
willalsoallowyoutohaverecordofthesettingsthatareprogrammedinto theunit for
futurereference.
Adescriptionforeachoftheconfigurationoptionsisgiveonthefollowingpages.
Reverseacting outputs? -Choosetheoutputsyouwouldliketoconfigureforreverse
action.
N–Relay:NormallyOpen(NO)contactwill be openandtheNormallyClosed(NC)
contactwillbeclosed.
Logic:Outputwillbelow(0V)inuntrippedstate.
Y–Relay:NOcontactwillbeclosedandtheNCcontactwillbeopenintheuntripped
state. TheLogic:Outputwillbehigh(+5V)inuntrippedstate.
TemperatureScale: -ChoosethetemperaturescalethattheCT224shoulduse. RTDs
andthermocoupleswillusethistemperature scale fordisplay. OptionsareF,
FahrenheitandC,Celsius.
Zoneto be displayed during normaloperation:-Choosehowtheinputreadings
shouldbedisplayed.
Theusercanalwaysadjustthedisplayedreadingby pressing keys, after5secondsthe
CT224willresumeit’s processofdisplayingtheHigh,LoworScanningthroughinputs.
High–Highestinputreadingisdisplayed,regardlessofinputtype.
Low–Lowestinputreadingisdisplayed,regardlessofinputtype.
Any–Display willstayonthezonethatthe user hassetitto.
Minutesofalarmsilencewhenakeyis pressed: -Settheamountoftime to wait
untilthealarmwillresound,if the alarm conditionisstillpresent. Validrangeis1to
100minutesor Stays Off. Thissettingonlyresounds thealarm,itwill notre-trip an
output. Itisdesignedtoremindpersonnelthatthereisstillatrip condition in affect.
If an input fails:-ThissettingallowstheusertodeterminewhatactiontheCT224
shouldtakeifabrokensensorisdetected.
Soundalarm–Alarmwillsoundifinputfails. Alarmwillresoundaccordingtothe
“Minutesofalarmsilencewhen akeyispressed”setinthepreviousstep.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 16
Tripoutput(s)associatedwithfailedinput–Alloutputsconfiguredtotriponthe
channelthathasafailedinputwilltrip.
Ignore–Continueoperatingliketheinputisstillfunctioningproperly.
Chooseinput type: -Select the input type for this zone.
4-20mATransmitters –Output proportional to process variable for PSI, BAR, %
RelativeHumidity,mm/sec,in/sec,G,ºC,ºF.
Enter Low End of Transmitter Range:-Thissettingwillonlybedisplayedifa4-20mA
inputisselected inthepreviousstep. AllrangesforRTDsandthermocouplesare
fixed. Thevalidinput range isbetween -999and9999.
EnterHigh End ofTransmitterRange: -This setting is also onlyavailable when a4-
20mAinputisselected. Thevalid inputrangeis between–999 and9999. The high
endofthetransmitterrangemustbehigherthanthelowend.
ZoneX Trip 1:-Setthetripvalueforthiszone. WhenTrip2isdisplayedit will
correspondtothesecondtripvalueforthezone. Valid temperature ranges are shown
inthechartsfoundunder“Chooseinputtype:”. Ifavaluenotwithintherangeforthe
sensorisentered,awarningwillbedisplayedandanew,validsettingshouldbe
entered.
TripOver or Under?–Thissettingdetermineswhentheoutputswilltrip.
Over–Outputsforthezonewilltripwhenthereadingishigherthan thetripvalue.
Under–Outputs for thezonewilltripwhenthereadingislowerthanthe trip value.
SoundAlarm on Trip?–Yeswill causethealarmtosoundandalarmoutputtotrip
whenthereadingpasses thetripvalue. SelectingNowill notsoundthealarmwhen
theoutputsaretripped.
Outputsto trip:
Output1__Output2__
Output3__Output4__ -A Y after the output indicates to trip the output when the
readingpassedthetripvalue. AnNaftertheoutputindicatestheoutput should not
betripped.
UntripOutputs by: -Thissettingwilldeterminehowtheoutputsassociatedwiththis
tripwillbeuntripped.
ManualResetOnly–Thissettingcauses theoutputstolatch. Theoutputs canonlybe
resetbyenteringtheMainMenuandselectingManualReset. (Apasswordmaybe
necessaryto reset therelays.)
PressingEnter–TheoutputswilluntripwhenEnterispressed.

Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 17
UsingHysteresis–Theoutputswilluntripwhentheinputvalueexitsthehysteresis
(deadband)limit.
Note:TheorderofprecedenceforthemethodsofuntripisManualResetOnly,
PressingEnter,andthenUsingHysteresis. Thismeansthatifatanytimeanoutputis
trippedandconfiguredbyanzonetountripusingManualResetOnly,theonlywayto
untripthatzoneisusingtheManualReset.
Note:Whenanyzonecausesatripforanoutput,allzonesthathavecausedatripon
thatoutputwillberefreshed. Thismeansthatifan output has been tripped and then
clearedbypressingEnterandanotherzonecausesthatoutputtoretrip,theoutput
willactasthoughbothtripshavereoccurredatthesametimetocausetheoutputto
trip. So,ifthesecondtripweretoresetby dropping belowthe programmed
hysteresisvalue,theoutput willstillbetripped,due tothefirstzone,which causedthe
trip. Toresetthe output again,Enterwouldneedtobepressed.
SetHysteresis: -Hysteresisistheamountthatthereadingmustmovepastthetrip
valuebeforetheoutputs willreset. Forexample,thesystem isconfiguredtotripat
100ºF,hasa10ºFhysteresisandwilltripOutput1onan over temperature reading.
Thereadingincreases to100ºF,so Output1trips. The reading willneed to gobelow
90ºFbeforeOutput 1 willreset.
Minco (MainOffice)
7300 Commerce Lane
Minneapolis, MN
55432
USA
Tel: 1.763.571.3121
Fax: 1.763.571.0927
Customer Service/
Order Desk:
Tel: 1.763.571.3123
Fax: 1.763.571.0942
www.minco.com
MincoS.A.
Usine et Service
Commercial, Z.I.
09310Aston,France
Tel: (33) 5 61 03 24 01
Fax: (33) 5 61 03 24 09
Minco EC
Hirzenstrasse 2
CH-9244 Niederuzwil
Switzerland
Tel:(41)71 9527989
Fax: (41)71 952 79 90
ISO 9001:2000
www.minco.com
Minco 2005
F:\MOD\CT224\LIT\1038MN.DOC
5/26/
0
5