18
Error Code
Abnormal points and detection method
Case Judgment and action
U5
Temperature of heatsink
Abnormal if heatsink thermistor (TH8)
detects temperature indicated below.
SW40/50··········································· 84:
1The outdoor fan motor is
locked.
2Failure of outdoor fan motor
3Air flow path is clogged.
4Rise of ambient temperature
5Defective thermistor
6Defective input circuit of
outdoor power circuit board
7Failure of outdoor fan drive
circuit
12 Check outdoor fan.
3Check air flow path for cooling.
4Check if there is something which causes
temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46:.)
Turn off power, and on again to check if U5 is
displayed within 30 minutes.
If U4 is displayed instead of U5, follow the
action to be taken for U4.
5Check resistance value of thermistor (TH8)
or temperature by microcomputer.
(Thermistor/TH8: Refer to 10-6.)
(SW2 on A-Control Service Tool: Refer to 10-10.)
6Replace outdoor power circuit board.
7Replace outdoor controller circuit board.
U4
Open/short of outdoor unit thermistors
(TH3, TH6, TH7, and TH8)
Abnormal if open or short is detected
during compressor operation.
Open detection of thermistors TH3 and
TH6 is inoperative for 10 seconds to 10
minutes after compressor starting and 10
minutes after and during defrosting.
* Check which unit has abnormality in its
thermistor by switching the mode of SW2.
(PAC-SK52ST)
(Refer to 10-10.)
1Check connection of connector (TH3,TH6/
TH7) on the outdoor controller circuit board.
Check connection of connector (CN3) on the
outdoor power circuit board.
Check breaking of the lead wire for thermistor
(TH3,TH6,TH7,TH8). Refer to 10-9.
2Check resistance value of thermistor
(TH3,TH6,TH7,TH8) or check temperature by
microcomputer.
(Thermistor/TH3,TH6,TH7,TH8: Refer to 10-6.)
(SW2 on A-Control Service Tool: Refer to
10-10.)
3Replace outdoor controller circuit board.
1Disconnection or contact failure
of connectors
Outdoor controller circuit
board: TH3, TH6/TH7
Outdoor power circuit board:
CN3
2Defective thermistor
3Defective outdoor controller
circuit board
()
U6
Power module
Check abnormality by driving power module
in case overcurrent is detected.
(UF or UP error condition)
1Outdoor stop valve is closed.
2Decrease of power supply voltage
3Looseness, disconnection or
converse of compressor wiring
connection
4Defective compressor
5Defective outdoor power circuit
board
1Open stop valve.
2Check facility of power supply.
3Correct the wiring (U•V•W phase) to
compressor. Refer to 10-9 (Outdoor power
circuit board).
4Check compressor referring to 10-6.
5Replace outdoor power circuit board.
U7
Too low superheat due to low discharge
temperature
Abnormal if discharge superheat is
continuously detected less than or equal
to -15:for 3 minutes even though linear
expansion valve has minimum open pulse
after compressor starts operating for 10
minutes.
1Disconnection or loose
connection of discharge
temperature thermistor (TH4)
2Defective holder of discharge
temperature thermistor
3Disconnection or loose connection
of linear expansion valve’s coil
4Disconnection or loose
connection of linear expansion
valve’s connector
5Defective linear expansion valve
12 Check the installation conditions of
discharge temperature thermistor (TH4).
3Check the coil of linear expansion valve.
Refer to 10-8.
4Check the connection or contact of LEV-A and
LEV-B on outdoor controller circuit board.
5Check linear expansion valve.
Refer to 10-6.
Thermistors Open detection Short detection
Symbol Name
TH3 Thermistor <Liquid> - 40 °C or below 90 °C or above
TH6 Thermistor <2-phase pipe> - 40 °C or below 90 °C or above
TH7 Thermistor <Amibient> - 40 °C or below 90 °C or above
TH8 Thermistor <Heatsink> - 27 °C or below 102 °C or above
U8
Outdoor fan motor
Abnormal if rotational frequency of the fan
motor is not detected during DC fan motor
operation.
Fan motor rotational frequency is abnormal
if;• 100 rpm or below detected continuously
for 15 seconds at 20:or more outside
air temperature.
• 50 rpm or below or 1500 rpm or more
detected continuously for 1 minute.
1Failure in the operation of the
DC fan motor
2Failure in the outdoor circuit
controller board
1Check or replace the DC fan motor.
2Check the voltage of the outdoor circuit
controller board during operation.
3Replace the outdoor circuit controller board.
(when the failure is still indicated even after
performing the action 1above.)