
Foundation
Site Installation
Installation
Structure-borne noise
Vibrations
Clearances
1. The condenser air is blown out vertically or horizontally.
2. Do not install the device close to heat sources. Heated air intake must be
avoided.
3. The condenser fans are rated for ZERO external static pressure. The fan
do not have the capacity to push air through ducting, which means that
NO DUCTS OR MUFFLERS may be used on the inlet ot outlet of the
chillers.
4. No air short-circuit is permitted, i.e. the heated discharge air from the
condenser fans must never be drawn back into the condenser inlet. This
will occur if the chiller is too close to a wall, or a low ceiling or other
obstructions.
5. In the case of shaft or trench mounting, contact the manufacturer for
advice on the installation site.
It ispossible thatnoise or vibration may betransmitted through the ground,
or building structure. If this occurs, it may benecessary toinstall a vibration
elimination device. The construction specifications ofthe
customer/engineering contractor regarding structure transmitted noise or
vibration must be observed.
May betransmitted through the chilled water piping. This can beavoided by
the use of flexible piping connections.
Must bemaintained for servicing and ventilation purposes. All removable
side panels must be available service.
*See CLEARANCE REQUIREMENTS section under MOTIVAIR INSTALLATION
ENGINEERING BULLETIN
CHILLER INSTALLATION
All chillers must be mounted ona solid, horizontal surface,suitable for the
weight of the chiller.* Note the chiller weight is incresed byfillingwith
glycol/water mixture.
Observe all local regulations.
Compliance with the following basic rules for the erection ofdevices with
radial fans will ensure problem-free operation andthe rated refrigeration
capacity.
Basic rules: