- 5 - -2-
Press the button " " for one second to turn on UPS
Press the button " " for one second to turn off UPS.
Bypass indicator shining indicates that the load power is
supplied from main through bypass.
Inverter indicator shining indicates that UPS output power
to load from inverter.
Battery indicator shining indicates that UPS output power
to load from battery.
Fault indicator shining indicates that UPS is in abnormal
condition.
Load indicator (Battery capacity indicator) indicates bar-type show,
load value and battery capacity percentage.
Main button:
Load Capacity Percentage
LED
LED 5
LED 4
LED 3
LED 2
LED 1
More than 100%
76~100%
56~75%
36~55%
1~35%
Battery Capacity Percentage
LED
LED 5
LED 4
LED 3
LED 2
LED 1
0~35%
36~55%
56~75%
76~100%
100%
Indicator explanation as follow: (from bottom to top)
Main Mode
Battery Mode
6.Operation
After connecting the main, press “turn-on button” for over one
second to turn on UPS.
Warnings
The UPS is qualified as class-A product. The product may lead to
radio Jamming in the living environment. With such a condition,
users need to adopt some workable measures for distraction.
1.To connect UPS input cable to the main, while output socket connects
the load. The total output power should not be more than
1KVA/0.8KW,2KVA/1.6KW,3KVA/2.4KW.
2.Besides a socket output, C3k(s) also provides a terminal-strip output.
The procures of cable matching is as follows:
1) Take off the small cover of strip.
2
2) Adopt AWG14or 2.1mm
3) After matching the cable, please check if the connecting cable is firm.
4) Replace the small cover back where it lies.
terminal
4.Operating procedures of connecting
external batteries to extended-time model
1.Use voltage of battery group/bank correctly according to different
types of ups,C1KS:36VDC,C2KS:72VDC,C3KS:96VDC,otherwise
malfunction might happen.
2.One end of the charging cable is to connect with UPS, the other with 3
open-type cables with battery group/bank. Red cable
connects positive pole”+”, black cable connects negative pole”-”,
yellow-green cable connects the ground.
is to connect