Napoleon HDX52NT-1 User manual

EN
FR
PG
65
W415-1371 / 09.15.14
INSTALLER: LEAVE THIS MANUAL WITH THE APPLIANCE.
CONSUMER: RETAIN THIS MANUAL FOR FUTURE REFERENCE.
NEVER LEAVE CHILDREN OR OTHER AT RISK INDIVIDUALS ALONE WITH THE APPLIANCE
INSTALLATION AND
OPERATING INSTRUCTIONS
Wolf Steel Ltd., 24 Napoleon Rd., Barrie, ON, L4M 0G8 Canada /
103 Miller Drive, Crittenden, Kentucky, USA, 41030
1.28E
$10.00
HOT GLASS WILL CAUSE
BURNS.
DO NOT TOUCH GLASS UNTIL
COOLED.
NEVER ALLOW CHILDREN TO
TOUCH GLASS.
!
WARNING
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with the appliance and
shall be installed.
SAFETY INFORMATION
!WARNING
- Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
- WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbour’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
- Installation and service must be performed by a
qualified installer, service agency or the supplier.
This appliance may be installed in an aftermarket,
permanently located, manufactured home (USA
only) or mobile home, where not prohibited by
local codes.
This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is
not convertible for use with other gases, unless a
certified kit is used.
If the information in these instructions
are not followed exactly, a fire or
explosion may result causing property
damage, personal injury or loss of life.
CERTIFIED FOR CANADA AND UNITED STATES USING ANSI/CSA METHODS.
Decorative Product: Not for use as a heating appliance.
BARRIER
SAFETY BARRIER
HDX52NT-1
NATURAL GAS
HDX52PT-1
PROPANE
CONFORMS TO AMERICAN NATIONAL STANDARDS: ANSI Z21.50, CERTIFIED TO CANADIAN CSA 2.22 FOR VENTED GAS FIREPLACES.

2
W415-1371 / 09.15.14
EN
NOTE: Changes, other than editorial, are denoted by a vertical line in the margin.
TABLE OF CONTENTS
1.0 INSTALLATION OVERVIEW 3
2.0 INTRODUCTION 4
2.1 DIMENSIONS 5
2.2 GENERAL INSTRUCTIONS 5
2.3 GENERAL INFORMATION 6
2.4 RATING PLATE INFORMATION 7
3.0 VENTING 8
3.1 VENTING LENGTHS AND COMPONENTS 8
3.2 TYPICAL VENT INSTALLATION 9
3.3 VENT TERMINAL CLEARANCES 10
3.4 VENT APPLICATION FLOW CHART 11
3.5 DEFINITIONS 11
3.6 ELBOW VENT LENGTH VALUES 11
3.7 HORIZONTAL TERMINATION 12
3.8 VERTICAL TERMINATION 14
4.0 INSTALLATION 16
4.1 WALL AND CEILING PROTECTION 16
4.1.1 HORIZONTAL INSTALLATION 17
4.1.2 VERTICAL INSTALLATION 17
4.2 USING FLEXIBLE VENT COMPONENTS 18
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION 18
4.2.2 VERTICAL AIR TERMINAL INSTALLATION 19
4.2.3 APPLIANCE VENT CONNECTION 20
4.3 MOBILE HOME INSTALLATION 20
4.4 GAS INSTALLATION 21
5.0 FRAMING 22
5.1 INSTALLING NON-COMBUSTIBLE BOARD 25
5.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES 27
5.3 MINIMUM COMBUSTIBLE MANTEL CLEARANCES 29
5.4 NON-COMBUSTIBLE FACING MATERIAL 30
6.0 FINISHING 31
6.1 SAFETY SCREEN REMOVAL / INSTALLATION 31
6.2 LATCH DOOR ENGAGING / DISENGAGING 32
6.3 GLASS DOOR REMOVAL / INSTALLATION 33
6.4 BURNER INSTALLATION 34
6.5 LOGO PLACEMENT 34
7.0 ELECTRICAL INFORMATION 35
7.1 HARD WIRING CONNECTION 35
7.2 RECEPTACLE WIRING DIAGRAM 35
7.3 BATTERY HOLDER INSTALLATION 36
7.4 WIRING DIAGRAM 37
8.0 OPERATION 38
8.1 GENERAL TRANSMITTER LAYOUT 38
8.2 INITIALIZING THE TRANSMITTER/BATTERY HOLDER FOR THE FIRST TIME 38
8.3 TEMPERATURE DISPLAY 39
8.4 FLAME HEIGHT 39
8.5 NIGHT LIGHT DIMMER CONTROL 39
8.6 CONTINUOUS PILOT / INTERMITTENT PILOT (CPI / IPI) SELECTION 40
8.7 KEY LOCK 40
8.8 LOW BATTERY / MANUAL BYPASS 40
9.0 OPERATING INSTRUCTIONS 41
9.1 RESTRICTING VERTICAL VENTS 42
9.2 PILOT BURNER ADJUSTMENT 42
9.3 VENTURI ADJUSTMENT 43
9.4 FLAME CHARACTERISTICS 43
10.0 MAINTENANCE 44
10.1 ANNUAL MAINTENANCE 45
10.2 CONTROL ACCESS 46
10.3 BURNER REMOVAL 47
10.4 BRICK PANEL REMOVAL 47
10.5 PORCELAIN PANEL REMOVAL 47
10.6 MEDIA TRAY REMOVAL (GLASS ONLY) 47
10.7 NIGHT LIGHT REPLACEMENT 48
10.8 GLASS / DOOR REPLACEMENT 49
10.9 CARE OF GLASS 49
10.10 CARE OF PLATED PARTS 49
11.0 REPLACEMENTS 50
12.0 OVERVIEW 51
13.0 ACCESSORIES 52
14.0 LOG BURNER 54
15.0 GLASS BURNER 55
16.0 TROUBLESHOOTING 58
17.0 WARRANTY 61
18.0 SERVICE HISTORY 62
19.0 NOTES 63
The camera icon indicates video tutorials are available as additional reference,
visit http://www.napoleonfireplaces.com/category/product-support/support-centre/

3
W415-1371 / 09.15.14
EN
1.0 INSTALLATION OVERVIEW
See the section
“FRAMING -
MINIMUM MANTEL
CLEARANCES”
See the section
“FRAMING - MINIMUM
CLEARANCE TO
COMBUSTIBLE
ENCLOSURES” for
drywall (or other
combustible material)”
See the section
“FRAMING”
Side
Wall
See the section
“VENTING - VENTING
LENGTHS AND AIR TERMINAL
LOCATIONS”
See the section
“FRAMING”
See the section
“FRAMING - MINIMUM
CLEARANCE TO
COMBUSTIBLE
ENSLOSURES” for
non-combustible
materials such as tile,
marble, granite, etc.
IMPORTANT: Extra
support may be
required.
See the section
“CONTROLACCESS”
for the control box.
See the section
“BATTERY HOLDER”
See the section
“BURNER INSTALLATION”
SAFETY BARRIER
Batteries must be disposed of according to the local laws and regulations. Some batteries may be recycled,
and may be accepted for disposal at your local recycling center. Check with your municipality for recycling
instructions.

4
W415-1371 / 09.15.14
EN
3.2C
!
WARNING
• THIS APPLIANCE IS HOT WHEN OPERATED AND CAN CAUSE SEVERE BURNS IF CONTACTED.
• ANY CHANGES OR ALTERATIONS TO THIS APPLIANCE OR ITS CONTROLS CAN BE DANGEROUS AND IS
PROHIBITED.
• Do not operate appliance before reading and understanding operating instructions. Failure to operate appliance
according to operating instructions could cause fire or injury.
• Risk of fire or asphyxiation do not operate appliance with fixed glass removed.
• Do not connect 110 volts to the control valve.
• Risk of burns. The appliance should be turned off and cooled before servicing.
• Do not install damaged, incomplete or substitute components.
• Risk of cuts and abrasions. Wear protective gloves and safety glasses during installation. Sheet metal edges may
be sharp.
• Do not burn wood or other materials in this appliance.
• Children and adults should be alerted to the hazards of high surface temperature and should stay away to
avoid burns or clothing ignition.
• Young children should be carefully supervised when they are in the same room as the appliance.
Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier
is recommended if there are at risk individuals in the house. To restrict access to an appliance, install an
adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and
away from hot surfaces.
• Clothing or other flammable material should not be placed on or near the appliance.
• Due to high temperatures, the appliance should be located out of traffic and away from furniture and
draperies.
• Ensure you have incorporated adequate safety measure to protect infants/toddlers from touching hot surfaces.
• Even after the appliance is out, the glass and/or screen will remain hot for an extended period of time.
• Check with your local hearth specialty dealer for safety screens and hearth guards to protect children from hot
surfaces. These screens and guards must be fastened to the floor.
• Any safety screen, guard or barrier removed for servicing the appliance, must be replaced prior to operating
the appliance.
• The appliance is a vented gas-fired appliance. Do not burn wood or other materials in the appliance
• It is imperative that the control compartments, burners and circulating blower and its passageway in the appliance
and venting system are kept clean. The appliance and its venting system should be inspected before use and at
least annually by a qualified service person. More frequent cleaning may be required due to excessive lint from
carpeting, bedding material, etc. The appliance area must be kept clear and free from combustible materials,
gasoline and other flammable vapors and liquids.
• Under no circumstances should this appliance be modified.
• This appliance must not be connected to a chimney flue pipe serving a separate solid fuel burning appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system and any gas control which has been under water.
• Do not operate the appliance with the glass door removed, cracked or broken. Replacement of the glass should be
done by a licensed or qualified service person.
• Do not strike or slam shut the appliance glass door.
• When equipped with pressure relief doors, they must be kept closed while the appliance is operating to prevent
exhaust fumes containing carbon monoxide, from entering into the home. Temperatures of the exhaust escaping
through these openings can also cause the surrounding combustible materials to overheat and catch fire.
• Only doors / optional fronts certified with the appliance are to be installed on the appliance.
• Keep the packaging material out of reach of children and dispose of the material in a safe manner. As with all plastic
bags, these are not toys and should be kept away from children and infants.
• As with any combustion appliance, we recommend having your appliance regularly inspected and serviced as well
as having a Carbon Monoxide Detector installed in the same area to defend you and your family against Carbon
Monoxide.
• Ensure clearances to combustibles are maintained when building a mantel or shelves above the appliance.
Elevated temperatures on the wall or in the air above the appliance can cause melting, discolouration or damage of
decorations, a T.V. or other electronic components.
• A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and
shall be installed.
• If the barrier becomes damaged, the barrier shall be replaced with the manufacturer’s barrier for this
appliance.
• Installation and repair should be done by a qualified service person. The appliance should be inspected
before use and at least annually by a professional service person. More frequent cleaning may be required
due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments,
burners and circulating air passageways of the appliance be kept clean.
2.0 INTRODUCTION

5
W415-1371 / 09.15.14
EN
56 7/8"
1445mm
54 13/16"
1392mm 50 3/8"
1280mm
41 7/8"
1064mm
27 1/8"
689mm
29 1/8"
740mm
47 17/32"
1207mm
44 3/4" 1137mm
2"
51mm
38 7/8"
987mm
Ø 10 7/8"
276mm
Ø 7 7/8"
200mm
9 3/16"
233mm
SAFETY BARRIER
2.1 DIMENSIONS
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifics that apply to your area, for example in Massachusetts State:
• This product must be installed by a licensed plumber or gas fitter when installed within the commonwealth
of Massachusetts.
• The appliance damper must be removed or welded in the open position prior to installation of an appliance
insert or gas log.
• The appliance off valve must be a “T” handle gas cock.
• The flexible connector must not be longer than 36 inches (914mm).
• A Carbon Monoxide detector is required in all rooms containing gas fired appliances.
• The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48” (1219mm) FROM
THE FRONT FACE OF THE APPLIANCE.
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35 mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
!
WARNING
2.2 GENERAL INSTRUCTIONS

6
W415-1371 / 09.15.14
EN
This appliance is approved for bathroom, bedroom and bed-sitting room installations and is certified for mobile
home installation.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified kit is used.
When the appliance is installed at elevations above 4,500ft (1371m), and in the absence of specific
recommendations from the local authority having jurisdiction, the certified high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000ft (305m).
Expansion / contraction noises during heating up and cooling down cycles are normal and are to be expected.
Change in flame appearance from “HI” to “LO” is more evident in natural gas than in propane.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the
appliance and shall be installed.
2.3 GENERAL INFORMATION
4.1B
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
A
NSI Z223.1 and NFPA 54 in the United States.
A
s long as the required clearance to combustibles is
maintained, the most desirable and beneficial location
for an appliance is in the center of a building, thereby
allowing the most efficient use of the heat created. The location of windows, doors and the traffic flow in the
room where the appliance is to be located should be considered. If possible, you should choose a location
where the vent will pass through the house without cutting a floor or roof joist.
If the appliance is installed directly on carpeting, vinyl tile or other combustible material other than wood
flooring, the appliance shall be installed on a metal or wood panel extending the full width and depth.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certied in the U.S.
by the National Fireplace
Institute
®
(NFI) as NFI Gas
Specialists
www.ncertied.org
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
HDX52-1
NG LP
Altitude (FT) 0-4,500 0-4500
Max. Input (BTU/HR) 55,000 55,000
Max. Output Steady State (BTU/HR) 37,391 36,500
Efficiency (w/the fan on) 64% 68%
Min. Inlet Gas Supply Pressure 4.5" w.c. (11mb) 11" w.c. (27mb)
Max. Inlet Gas Supply Pressure 7" w.c. (17mb) 13" w.c. (32mb)
Manifold Pressure (Under Flow Conditions) 3.5" w.c. (9mb) 10" w.c. (25mb)

7
W415-1371 / 09.15.14
EN
2.4 RATING PLATE INFORMATION
NOTE: The protective wrap on plated parts is best removed when
the assembly is at room temperature but this can be improved if
the assembly is warmed, using a hair dryer or similar heat source.
This appliance is equipped with a remote control system, which
requires batteries (supplied) to be installed. The transmitter takes 1
9V battery and in the case of a power failure the receiver takes 4 “AA”
batteries.
INSTALLER: It is your responsibility to check off the appropriate box on the rating plate according to
the model, venting and gas type of the appliance.
The illustration is for reference only. Refer to the rating plate on the appliance for accurate information.
NOTE: The rating plate must remain with the appliance at all times. It must not be removed.
65%
HDX52
SAMPLE
Both the rating plate and lighting instructions are attached to a cable and inserted along the left side of the ap-
pliance.
!
WARNING
ALLOW APPLIANCE TO COOL BEFORE PERFORMING ANY MAINTANCE OR CLEANING.
W385-1928 / C
CHDX52N CHDX52P
CONFORMS TO / CONFORMEAUX: ANSI Z21.50-2014, CERTIFIED TO / CERTIFIE CSA2.22-2014 VENTED GAS FIREPLACE / FOYER À GAZ VENTILÉ.
DIRECT VENT GAS FIREPLACE.
NOT FOR USE WITH SOLID FUEL.
FOR USE WITH GLASS DOORS
CERTIFIED WITH THIS UNIT ONLY.
WARNING: DO NOT ADD ANY MATERIAL
TO THE APPLIANCE, WHICH WILLCOME IN
CONTACT WITH THE FLAMES, OTHER THAN
THAT SUPPLIED BY THE MANUFACTURER
WITH THE APPLIANCE
DECORATIVE PRODUCT: NOT FOR USE AS A
HEATING APPLIANCE.
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS:
TOP 0"
FLOOR 0"
RECESSED DEPTH 29"
SIDES 0"
BACK 0"
VENT TOP 3"
VENT SIDES & BOTTOM 2"
VERTICAL VENT 1"
MANTEL 6"*
TOP SIDES & BACK: PER STAND OFF SPACERS FOR FRAMING
MATERIALS. FOR FINISHING MATERIALS SEE OWNER’S MANUAL
*MAXIMUM HORIZONTAL EXTENSION 2". SEE INSTRUCTION MANUAL FOR GREATER
EXTENSIONS. SEE OWNER’S INSTRUCTION MANUAL FOR MINIMUMAND
MAXIMUM LENGTHS.
ELECTRICAL RATING: 115V.60HZ. LESS THAN 12 AMPERES
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
SPÉCIFICATIONS ÉLECTRIQUES : 115 V,
60HZ. MOINS DE 12 AMPÈRES.
HDX52N HDX52P
MODEL PROPANE /
PROPANE MODÈLE FOYER À D'ÉVENT DIRECT. UN
COMBUSTIBLE SOLIDE NE PAS
ÊTRÉ UTILISÉ AVEC CET
APPAREIL. UTILISER AVEC LES
PORTE VITRÉES HOMOLOGUÉES
SEULEMENT AVEC CETTE UNITÉ.
ADVERTISSEMENT : N’AJOUTEZ PAS
A CETAPPAREIL AUCUN MATÉRIAU DEVANT
ENTRER EN CONTACT AVEC LES FLAMMES
AUTRE QUE CELUI QUI EST FOURNI AVECT
CET APPAREIL PAR LE FABRICANT.
PRODUIT DÉCORATIF: NE PAS UTILISER
COMME APPAREIL DE CHAUFFAGE
DÉGAGEMENTS MINIMAUX DES MATÉRIAUX
COMBUSTIBLES :
DESSUS 0"
PLANCHER 0"
PROFONDEUR DE L’ENCLAVE FACE 29"
CÔTÉS 0"
ARRIÈRE 0"
DESSUS DU CONDUIT D’EVENT 3"
CÔTÉS ET DESSOUS DU CONDUIT
D’EVENT 2"
CONDUIT D’EVENT VERTICAL 1"
TABLETTE 6"*
DESSUS, CÔTÉS & ARRIÈRE : SELON LES ESPACEURS DE
DÉGAGEMENT POUR LES MATERIAUX D’OSSATURE SELON
LA MANUELDE PROPRIÉTAIRE POUR LES MATÉRIAUX DE
FINITION. *L’EXTENSION HORIZONTALE MAXIMALE : 2".
RÉFÉRER AU MANUALD’INSTRUCTION POUR DES
EXTENSIONS PLUS GRANDES. RÉFÉRER AU MANUEL
D’INSTALLATION DE PROPRIÉTAIRE.
MODEL NATURAL GAS /
GAZ NATURAL
0-4500FT (0-1370M) ALTITUDE / ÉLÉVATION 0-4500FT (0-1370M)
55,000 BTU/H
INPUT / ALIMENTATION 55,000 BTU/H
37,000 BTU/H REDUCED INPUT / ALIMENTATION RÉDUITE 36,500 BTU/H
3.5"WATER COLUMN/D’UNE COLONNE D’EAU MANIFOLD PRESSURE / 10"WATER COLUMN/D’UNE COLONNE D’EAU
PRESSION AU COLLECTEUR
4.5"WATER COLUMN/D’UNE COLONNE D’EAU MINIMUM SUPPLY PRESSURE / 11"WATER COLUMN/D’UNE COLONNE D’EAU
PRESSION D’ALIMENTATION MINIMALE
7.0"WATER COLUMN/D’UNE COLONNE D’EAU MAXIMUM SUPPLY PRESSURE 13"WATER COLUMN/D’UNE COLONNE D’EAU
PRESSION D’ALIMENTATION MAXIMALE
65.2% P.4 FE 65.2%
SERIAL NUMBER/ NO. DE SÉRIE: HDX52
L’APPAREIL DOIT ÉVACUER SES GAZ EN UTILISANT
L’ENSEMBLE D’ÉVACUATION PROPRE ANAPOLEON. RÉFÉRER
AU MANUEL D’INSTALLATION DE PROPRIÉTAIRE POUR
L’EVACUATION PRECISE. IL EST IMPORTANT DE BIEN
RÉINSTALLER ET RESCELLER L’EVENT APRÉSAVOIR ASSURÉ
LE MAINTIEN DU SYSTÉME DE PRISE D’AIR.
THE APPLIANCE MUST BE VENTED USING THEAPPROPRIATE
NAPOLEON VENT KITS. SEE OWNERS INSTALLATION MANUAL
FOR VENTING SPECIFICS. PROPER REINSTALLATIONAND
RESEALING IS NECESSARYAFTER SERVICING THE VENT-AIR
INTAKE SYSTEM.
THIS APPLIANCE MUSTBE INSTALLED IN ACCORDANCE WITH LOCALCODES, IFANY; IF NONE, FOLLOW THE
CURRENTANSI Z223.1 OR CSAB149, INSTALLATION CODES. VENTED GAS FIREPLACE.APPROVED FOR
BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME
INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES
GAS EQUIPPED MOBILE HOMES, IN CANADA OR INTHE UNITED STATES THE MANUFACTURED HOME
CONSTRUCTION AND SAFETYSTANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS NOT
APPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLA-
TIONS, SITES AND COMMUNITIES,ANSI/NFPA 501A. FOR USE WITH BARRIER W565-0148. FOLLOW THE
INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL
INSTALLER L’APPAREIL SELON LES CODES D’INSTALLATION ANSI Z223.1 OU CSA-B149 EN VIGUER.
FOYER À GAZ VENTILÉ. HOMOLOGUÉ POUR INSTALLATION DANS UNE CHAMBRE À COUCHER, UNE SALLE DE
BAIN ET UN STUDIO.APPROPRIÉ POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION
CONFORME AUX EXIGENCES DE LANORME CAN/CSA Z240MH SÉRIE DE MAISONS MOBILES ÉQUIPÉESAU
GAZ EN VIGEUR AU CANADAOU AUX ÉTATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE
MAISONS MANUFACTUREE,TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D’ÉTATS-UNIS NE
PEUT ETREAPPLIQUÉE, SE REFERER ALA NORME RELATIVE AU CRITÈRE DE MESURES DE SÉCURITÉ
CONTRE L’INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURÉS, LES SITES ET LES
COMMUNAUTÉS, ANSI/NFPA 501A. POUR UNE UTILISERAVEC BARRIÈRE W565-0148. SUIVEZ LES
INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION.
9700539 (WSL)
4001658 (NAC) 4001657 (NGZ)
4001659 (WUSA)
OPTIONAL FAN KIT: NZ64 ENSEMBLE DE VENTILATEUR FACULTATIF: NZ64

8
W415-1371 / 09.15.14
EN
3.0 VENTING
3.1 VENTING LENGTHS AND COMPONENTS
This fireplaces uses 8" (203mm) exhaust / 11" (280mm) air intake vent pipe system.
Refer to the section applicable to your installation.
For safe and proper operation of the fireplace follow the venting instruction exactly. Deviation from the minimum
vertical vent length can create difficulty in burner start-up and/or carboning. Under extreme vent configurations,
allow several minutes (5-15) for the flame to stabilize after ignition. Provide a means for visually checking the vent
connection to the fireplace after the fireplace is installed. Use a firestop, vent pipe shield or attic insulation shield
when penetrating interior walls, floor or ceiling.
NOTE: If for any reason the vent air intake system is disassembled; reinstall per the instructions provided
for the initial installation. 7.7
!
WARNING
RISK OF FIRE, MAINTAIN SPECIFIED AIR SPACE CLEARANCES TO VENT PIPE AND APPLIANCE.
IF VENTING IS INCLUDED WITH SPACERS THE VENT SYSTEM MUST BE SUPPORTED EVERY 3FT
(0.9m) FOR BOTH VERTICAL AND HORIZONTAL RUNS. USE SUPPORTS OR EQUIVALENT
NON-COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM
COMBUSTIBLES. SPACERS ARE ATTACHED TO THE INNER PIPE AT PREDETERMINED INTERVALS
TO MAINTAIN AN EVEN AIR GAP TO THE OUTER PIPE. THIS GAP IS REQUIRED FOR SAFE
OPERATION. A SPACER IS REQUIRED AT THE START, MIDDLE AND END OF EACH ELBOW TO
ENSURE THIS GAP IS MAINTAINED. THESE SPACERS MUST NOT BE REMOVED.
For vent systems that provide seals on the inner exhaust flue, only the outer air intake joints must be sealed
using a red high temperature silicone (RTV). This same sealant may be used on both the inner exhaust and
outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the
fireplace flue collar which must be sealed using the black high temperature sealant Mill Pac.
When using Wolf Steel venting components, use only approved Wolf Steel flexible components with the
following termination kits: wall terminal kit GD622R, or 1/12 to 7/12 pitch roof terminal kit GD610, 8/12 to 12/12
roof terminal kit GD611 or flat roof terminal kit GD612. With flexible venting, in conjunction with the various
terminations, use either the 5 foot (1.5m) vent kit GD620 or the 10 foot (3m) vent kit GD630.
For optimum flame appearance and fireplace performance, keep the vent length and number of elbows to
a minimum.
The air terminal must remain unobstructed at all times. Examine the air terminal at least once a year to
verify that it is unobstructed and undamaged.
The minimum allowable vertical vent length is 3 feet (0.9m) maximum allowable vertical vent length is 40 feet
(12m). The maximum number of allowable 8” (203mm) vent connections is three horizontally or vertically
(excluding the fireplace and the air terminal connections).
When venting, the horizontal run must be kept to a minimum of 36” (914mm) or a maximum of 20 feet (6m).
If a 20 foot (6m) horizontal run is required, the fireplace must have a minimum vertical rise immediately off
the fireplace of 57” (1448mm). When terminating vertically, the vertical rise is a minimum 36” (914mm) and a
maximum 40 feet (12m) above the fireplace.
For optimum performance, it is recommended that all horizontal runs have a minimum 1/4” (6mm) rise
per foot/meter. Provide a means for visually checking the vent connection to the fireplace after the
fireplace is installed. Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows.
Keep it pulled tight. A 3/4” (19mm) air gap between the inner and outer liner all around is required for saf
e
operation. Use a firestop when penetrating interior walls, floor or ceiling.
8.4A
vertical rise is
GD822R GD810
GD811 GD812
GD820 GD830
18" (457mm)

9
W415-1371 / 09.15.14
EN
45.8
18" (457mm)
MAXIMUM
24″(610mm)
MIN.
71 1/2"
(1816mm)
PLUS RISE *
16″(406mm)
MINIMUM
40 FEET
(12m)
MAXIMUM
3 FEET (0.9m)
MINIMUM
47 1/2"
(1207mm)
3.2 TYPICAL VENT INSTALLATION
Refer to “VENTING” section.
47 1/2"
(1207mm)

10
W415-1371 / 09.15.14
EN
3.3 VENT TERMINAL CLEARANCES
INSTALLATIONS
CANADA U.S.A.
A12” (305mm) 12” (305mm) Clearance above grade, veranda porch, deck or balcony.
B12” (305mm)Δ9”
(229mm)ΔClearance to windows or doors that open.
C12” (305mm)* 12” (305mm) * Clearance to permanently closed windows.
D18”
(457mm)** 18” (457mm)** Vertical clearance to ventilated soffits located above the terminal within a horizontal distance of 2’
(0.6m) from the center line of the terminal.
E12” (305mm)** 12” (305mm)** Clearance to unventilated soffit.
F0” (0mm) 0” (0mm) Clearance to an outside corner wall.
G
0” (0mm)*** 0”
(0mm)***
Clearance to an inside non-combustible corner wall or protruding non-combustible obstructions (chimney,
etc.).
2” (51mm)*** 2”
(51mm)***
Clearance to an inside combustible corner wall or protruding combustible obstructions (vent chase,
etc.).
H3’(0.9m) 3’ (0.9m)**** Clearance to each side of the center line extended above the meter / regulator assembly to a
maximum vertical distance of 15’ (4.6m).
I3’ (0.9m) 3’ (0.9m)**** Clearance to a service regulator vent outlet.
J12” (305mm) 9” (229mm) Clearance to a non-mechanical air supply inlet to the building or a combustion air inlet to any other
appliance.
K6’ (1.8m) 3’ (0.9m) † Clearance to a mechanical air supply inlet.
L7’ (2.1m) ‡ 7’ (2.1m) **** Clearance above a paved sidewalk or paved driveway located on public property.
M12”
(305mm)††
12”
(305mm)**** Clearance under a veranda, porch or deck.
N16” (406mm) 16” (406mm) Clearance above the roof.
O2’ (0.6m)†* 2’ (0.6m) †* Clearance from an adjacent wall including neighbouring buildings.
P8’ (2.4m) 8’(2.4m) Roof must be non-combustible without openings.
Q3’ (0.9m) 3’ (0.9m) See chart for wider wall dimensions.
R6’ (1.8m) 6’ (1.8m) See chart for deeper wall dimensions. The terminal shall not be installed on any wall that has an
opening between the terminal and the open side of the structure.
S12” (305mm) 12” (305mm) Clearance under a covered balcony
ΔThe terminal shall not be located less than 6 feet under a window that opens on a horizontal plane in a structure with three walls and a roof.
* Recommended to prevent condensation on windows and thermal breakage
** It is recommended to use a heat shield and to maximize the distance to vinyl clad soffits.
*** The periscope requires a minimum 18 inches clearance from an inside corner.
**** This is a recommended distance. For additional requirements check local codes.
† 3 feet above if within 10 feet horizontally.
‡ A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
†† Permitted only if the veranda, porch, or deck is fully open on a minimum of two sides beneath the floor.
†* Recommended to prevent recirculation of exhaust products. For additional requirements check local codes.
††* Permitted only if the balcony is fully open on a minimum of one side.
12.1D
NOTE: Clearances are in accordance with local installation codes and the requirements of the gas supplier.
COVERED BALCONY APPLICATIONS ††*
QMIN RMAX MAX
R
= 3 feet
(0.9m) = 2 x IHHW
(4.6m)
QACTUAL
R
QS
GP

11
W415-1371 / 09.15.14
EN
13.1A
TOP EXIT
Horizontal Termination Vertical Termination
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Vertical rise is equal
to or greater than
the horizontal run
Vertical rise is less
than horizontal run
Horizontal run +
vertical rise to
maximum of 40 feet
(12m)
Horizontal run +
vertical rise to
maximum of
24.75 feet (7.5m)
Horizontal run +
vertical rise to Horizontal run +
vertical rise to
4.2 times the
vertical rise equal to
or greater than the
horizontal run
3 times the vertical
rise equal to or
greater than the
horizontal run
maximum of 40 feet
(12m) maximum of 40 feet
(12m)
14.1
For the following symbols used in the venting calculations and examples are:
> - greater than
> - equal to or greater than
< - less than
< - equal to or less than
HT- total of both horizontal vent lengths (Hr) and offsets (Ho) in feet
HR- combined horizontal vent lengths in feet
HO- offset factor: .03 (total degrees of offset - 90°*) in feet
VT- combined vertical vent lengths in feet
15.1A
FEET INCHES MILLIMETERS
1° 0.03 0.5 12.7
15° 0.45 6.0 152.4
30° 0.9 11.0 279.4
45° 1.35 16.0 406.4
90°* 2.7 32.0 812.8
* The first 90° offset has a zero value and is shown in the formula as - 90°
3.4 VENT APPLICATION FLOW CHART
3.5 DEFINITIONS
3.6 ELBOW VENT LENGTH VALUES

12
W415-1371 / 09.15.14
EN
16.1B
Simple venting configuration (only one 90° elbow)
(HT) < (VT)
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: HT< VT
Formula 2: HT+ VT< 40 feet (12.2m)
Example:
V1= 3 FT (0.9m)
V2= 8 FT (2.4m)
VT= V1+ V2= 3 FT (0.9m ) + 8 FT (2.4m) = 11 FT (3.4m)
H1= 2.5 FT (0.8m)
H2= 2 FT (0.6m)
HR= H1+ H2= 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m)
HO= .03 (three 90° elbows - 90°) = .03 (270° - 90°) = 5.4 FT (1.7m)
HT= HR+ HO= 4.5 FT (1.4m) + 5.4 FT (1.6m) = 9.9 FT (3m)
HT+ VT= 9.9 FT (3m) + 11 FT (3.4m) = 20.9 FT (6.4m)
Formula 1: HT< VT
9.9 FT (3m) <11 FT (3.4m)
Formula 2: HT+ VT< 40 FT (12.2m)
20.9 FT (6.4m) < 40 FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
See graph to determine the required vertical
rise VTfor the required horizontal run HT.
The shaded area within the lines represents
acceptable values for HTand VT
02.5
(0.8) 5
(1.5) 7.5
(2.3) 10
(3.1) 12.5
(3.8) 15
(4.6)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
17.5
(5.3) 20
(6.1)
39 (11.9)
REQUIRED
VERTICAL
RISE IN FEET
(METERS)VT
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS) HT
90°
90°
90°
V1
V2
H1
H2
3.7 HORIZONTAL TERMINATION
2 (0.6)
18"

13
W415-1371 / 09.15.14
EN
(HT) > (VT)
Simple venting configuration (only one 90° elbow) See graph to determine the required vertical rise VTfor the
required horizontal run HT.
REQUIRED
VERTICAL RISE
IN INCHES
(MILLIMETERS)
VT
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERES) HT
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: HT< 4.2 VT
Formula 2: HT+ VT < 24.75 feet (7.5m)
Example:
V
1 = VT = 6 FT (1.8m)
H1 = 3 FT (0.9m)
H2 = 5 FT (1.5m)
HR = H1 + H2 = 3FT (0.9m) + 5FT (1.5m) = 8 FT (2.4m)
HO = .03 (two 90° elbows - 90°) = .03 (180° - 90°) = 2.7FT (0.8m)
HT =HR + HO = 8FT (2.4m) + 2.7FT (0.8m) = 10.7FT (3.3m)
HT + VT = 10.7FT (3.3m) + 6FT (1.8m) = 16.7FT (5.1m)
Formula 1: HT < 4.2 VT
4.2 VT =4.2FT (1.3m) x 6FT (1.8m) = 25.2FT (7.7m)
10.7FT (3.3m) < 25.2FT (7.7m)
Formula 2: HT + VT < 24.75 FT (7.5m)
16.7FT (5.1m) < 24.75 (7.5m)
Since both formulas are met, this vent configuration is acceptable.
05
(1.5) 15
(4.6) 20 (6.1)
100 (2540)
50 (1270)
150 (3810)
12.5
(3.8)
19 1/2
(495.3)
57 (1447.8)
147
(3733.8)
2
(0.6)
The shaded area within the lines represents acceptable
values for HT and VT
90°
V1
H1H2
90°
Example:
V
1 = 4 FT (1.2m)
V
2 = 1.5 FT (0.5m)
V
T = V1 + V2 = 4FT (1.2m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
H1 = 2 FT (0.6m)
H2 = 1 FT (0.3m)
H3 = 1 FT (0.3m)
H4 = 1.5 FT (0.5m)
HR = H1 + H2 + H3 + H4= 2FT (0.6m) + 1FT (0.3m) + 1FT (0.3m) + 1.5FT (0.5m) = 5.5 FT (1.7m)
HO = .03 (four 90° elbows - 90°) = .03 (360° - 90°) = 8.1 FT (2.5m)
HT =HR + HO = 5.5 FT (1.7m) + 8.1 FT (2.5m) = 13.6 FT (4.2m)
HT + VT = 13.6 FT (4.2m) + 5.5 FT (1.7m) = 19.1 FT (5.8m)
Formula 1: HT < 4.2 VT
4.2 VT =4.2 FT (1.3m) x 5.5 FT(1.7m) = 23.1 FT (7m)
13.6 FT (4.2m) < 23.1 FT (7m)
Formula 2: HT + VT < 24.75 FT (7.5m)
19.1FT (5.8m) < 24.75 FT (7.5m)
Since both formulas are met, this vent configuration is acceptable.
90°
90°
90° 90°
H1
H2
V1
V2
H3
H4
10
(3.1) 19.5
(5.9)
16.1_2A
24 (7.3)
18
(5.5)

14
W415-1371 / 09.15.14
EN (HT) < (VT)
Simple venting configurations. See graph to determine the required vertical rise VTfor the
required horizontal run HT.
REQUIRED
VERTICAL
RISE IN FEET
(METERS) VT
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT
For vent configurations requiring one or more 90° elbows the following formulas apply:
Formula 1: HT< VT
Formula 2: HT+ VT < 40 feet (12.2m)
Example:
V1 = 5 FT (1.5m)
V2 = 6 FT (1.8m)
V3 = 10 FT (3.1m)
VT = V1 + V2 + V3 = 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21FT (6.4m)
H1 = 8 FT (2.4m)
H2 = 2.5 FT (0.8m)
HR = H1 + H2 = 8FT (2.4m) + 2.5FT (0.8m) = 10.5 FT (3.2m)
HO = .03 (four 90° elbows - 90°)
= .03 (360° - 90°) = 8.1 FT (2.5m)
HT =HR + HO = 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m)
HT + VT = 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)
Formula 1: HT < VT
18.6FT (5.7m) < 21FT (6.4m)
Formula 2: HT + VT < 40 FT (12.19m)
39.6FT (12.1m) < 40FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
90°
V1
V2
H1
H2
The shaded area within the lines represents acceptable
values for HT and VT
90°
90°
90°
05
(1.5) 10
(3.1) 15
(4.6) 20
(6.1)
40 (12.2)
10 (3.1)
20 (6.1)
30 (9.1)
3 (0.9)
V3
18.1A
3.8 VERTICAL TERMINATION

15
W415-1371 / 09.15.14
EN
(HT) > (VT)
Simple venting configurations. See graph to determine the required vertical rise VTfor the
required horizontal run HT.
REQUIRED
VERTICAL
RISE IN FEET
(METERS) VT
HORIZONTAL VENT RUN PLUS OFFSET IN FEET (METERS) HT
For vent configurations requiring more than two 90° elbows the following formulas apply:
Formula 1: HT< 3VT
Formula 2: HT+ VT < 40 feet (12.2m)
Example:
V1 = 2 FT (0.6m)
V2 = 1 FT (0.3m)
V3 = 1.5 FT (0.5m)
VT = V1+V2+V3= 2FT (0.6m) + 1FT (0.3m) + 1.5FT (0.5m) = 4.5FT (1.4m)
H1 = 6 FT (1.8m)
H2 = 2 FT (0.6m)
HR = H1 + H2 = 6FT (1.8m) + 2FT (0.6m) = 8 FT (2.4m)
HO = .03 (four 90° elbows - 90°)
= .03 (360° - 90°) = 8.1 FT (2.5m)
HT =HR + HO = 8FT (2.4m) + 8.1FT (2.5m) = 16.1FT (4.9m)
HT + VT = 16.1FT (4.9m) + 4.5FT (1.4m) = 20.6 FT (6.3m)
Formula 1: HT < 3VT
3VT = 3FT (0.9m) x 4.5FT (1.4m) = 13.5FT (4.1m)
16.1FT (4.9m) > 13.5FT (4.1m)
Since this formula is not met, this vent configuration is unacceptable.
Formula 2: HT + VT < 40 feet (12.2m)
20.6FT (6.3m) < 40 (12.2m)
Since only formula 2 is met, this vent configuration is unacceptable and a new appliance location or vent configuration will
need to be established to satisfy both formulas.
The shaded area within the lines represents acceptable
values for HT and VT
05
(1.5) 10
(3.1) 15
(4.6) 20
(6.1)
10 (3.1)
20 (6.1)
3 (0.9)
25
(7.6) 30
(9.1)
19 (5.8)
90°
V1V2
H1
H2
90°
90°
90°
V3
18.1_2B
18
(5.5)
2 (0.6)

16
W415-1371 / 09.15.14
EN
For optimum performance it is recommended that all horizontal runs have a minimum of 1/4"(6.4mm) rise
per foot (0.3m) using flexible venting. For safe and proper operation of the appliance, follow the venting
instructions exactly.
For clearance to combustible materials from the vent pipe, see “FRAMING” section.
4.0 INSTALLATION
4.1 WALL AND CEILING PROTECTION
!
WARNING
ENSURE TO UNPACK ALL LOOSE MATERIALS FROM INSIDE THE FIREBOX PRIOR TO HOOKING UP
THE GAS AND ELECTRICAL SUPPLY.
IF YOUR APPLIANCE IS SUPPLIED WITH A REMOTE ENSURE THE REMOTE RECEIVER IS IN THE
“OFF” POSITION PRIOR TO HOOKING UP THE GAS AND ELECTRICAL SUPPLY TO THE APPLIANCE.
FOR SAFE AND PROPER OPERATION OF THE APPLIANCE, FOLLOW THE VENTING INSTRUCTIONS
EXACTLY.
ALL INNER EXHAUST AND OUTER INTAKE VENT PIPE JOINTS MAY BE SEALED USING EITHER RED
RTV HIGH TEMP SILICONE SEALANT W573-0002 (NOT SUPPLIED) OR BLACK HIGH TEMP MILL PAC
W573-0007 (NOT SUPPLIED) WITH THE EXCEPTION OF THE APPLIANCE EXHAUST FLUE COLLAR
WHICH MUST BE SEALED USING MILL PAC.
IF USING PIPE CLAMPS TO CONNECT VENT COMPONENTS, 3 SCREWS MUST ALSO BE USED TO
ENSURE THE CONNECTION CANNOT SLIP OFF.
DO NOT CLAMP THE FLEXIBLE VENT PIPE.
RISK OF FIRE, EXPLOSION OR ASPHYXIATION. IMPROPER SUPPORT OF THE ENTIRE VENTING
SYSTEM MAY ALLOW VENT TO SAG AND SEPARATE. USE VENT RUN SUPPORTS AND CONNECT
VENT SECTIONS PER INSTALLATION INSTRUCTIONS.
RISK OF FIRE, DO NOT ALLOW LOOSE MATERIALS OR INSULATION TO TOUCH THE VENT PIPE.
REMOVE INSULATION TO ALLOW FOR THE INSTALLATION OF THE ATTIC SHIELD AND TO
MAINTAIN CLEARANCES TO COMBUSTIBLES.
68.2B
!
WARNING
DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF
MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.
ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.
INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR
OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.
70.1

17
W415-1371 / 09.15.14
EN
This application occurs when venting through a roof. Installation kits for
various roof pitches are available from your authorized dealer / distributor. See
accessories to order specific kits required.
A. Determine the air terminal location, cut and frame a square opening as
illustrated in the ceiling and the roof to provide the minimum 1“ (25mm)
clearance between the vent pipe and any combustible material. Try to center
the vent pipe location midway between two joists to prevent having to cut
them. Use a plumb bob to line up the center of the openings. A vent pipe
shield will prevent any materials such as insulation, from filling up the 1”
(25mm) air space around the pipe. Nail headers between the joist for
extra support.
B. Apply a bead of caulking (not supplied) to the framework or to the Wolf
Steel vent pipe shield plate or equivalent (in the case of a finished ceiling),
and secure over the opening in the ceiling. A firestop must be placed on the
bottom of each framed opening in a roof or ceiling that the venting system passes
through. Apply a bead of caulking all around and place a firestop spacer over
the vent shield to restrict cold air from being drawn into the room or around the
fireplace. Ensure that both spacer and shield maintain the required clearance to
combustibles. Once the vent pipe is installed in its final position, apply sealant between the
pipe and the firestop assembly.
C. In the attic, slide the vent pipe collar down to cover up the open end of the shield and
tighten. This will prevent any materials, such as insulation, from filling up the 1” (25mm) air
space around the pipe.
21.1
CAULKING
VENT PIPE
SHIELD
FIRESTOP
UNDERSIDE OF
JOIST
VENT
PIPE
COLLAR
VENT
PIPE
SHIELD
This application occurs when venting through an exterior wall.
Having determined the correct height for the air terminal
location, cut and frame a hole in the exterior wall as
illustrated to accommodate the firestop assembly.
Dry fit the firestop assembly before proceeding to
ensure the brackets on the rear surface fit to the
inside surface of the horizontal framing.
The vent shield is telescopic and must be adjusted
to shield the full depth of the combustible wall
penetration. The length of the vent shield may be cut
shorter for combustible walls that are less than 6" (152mm)
thick.
A. Apply a bead of caulking (not supplied) around the corner edge of
the inside surface of the firestop assembly, fit the firestop
assembly to the hole and secure using the 4 screws (supplied in
your manual baggie).
B. Once the vent pipe is installed in its final position, apply high temperature sealant W573-0007 (not
supplied) between the pipe and the firestop.
DETERMINE
THE
CORRECT
HEIGHT
CAULKING
FIRESTOP
SPACER
VENT
SHIELD
FINISHING
MATERIAL
!
WARNING
THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.
TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE
RETURN FLANGE OF THE MOUNTING PLATE.
4.1.1 HORIZONTAL INSTALLATION
4.1.2 VERTICAL INSTALLATION

18
W415-1371 / 09.15.14
EN
A. Stretch the inner flex pipe to the required
length needed for the finished wall surface.
Apply a heavy bead of high temperature
sealant W573-0007 Mill Pac (not supplied) to
the inner sleeve of the air terminal. Slip the
vent pipe a minimum of 2” (50.8mm) over the
inner sleeve of the air terminal and secure
with 3 #8 screws.
B. Using the outer flex pipe, slide over the outer
combustion air sleeve of the air terminal
and secure with 3 #8 screws. Seal using
high temperature sealant W573-0002 (not
supplied).
C. Insert the vent pipes through the firestop
maintaining the required clearance to
combustibles. Holding the air terminal (lettering
in an upright, readable position), secure to the
exterior wall and make weather tight by sealing
with caulking (not supplied).
D. If more vent pipe needs to be used to
reach the fireplace, couple them together
as illustrated. The vent system must be
supported approximately every 3 feet (0.9mm)
for both vertical and horizontal runs. Use
noncombustible strapping to maintain the
minimum 1” (25.4mm) clearance to combustibles.
The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth
of its return flange. 23.3B
HI-TEMP
SEALANT
#8 X 1/2” SELF DRILLING
SCREWS & WASHERS
INNER COUPLER
OUTER COUPLER
OUTER
FLEX PIPE INNER
FLEX PIPE
OUTER
FLEX PIPE
CAULKING
SCREWS
#10x2" PIPE
OUTER FLEX
SEALANT
2" (50.8mm) OVERLAP
HI-TEMP
INNER FLEX
PIPE
4.2 USING FLEXIBLE VENT COMPONENTS
For safe and proper operation of the appliance, follow the venting
instructions exactly.
All inner flex pipe and outer flex pipe joints may be sealed using high
temperature sealant W573-0002 (not supplied) or the high temperature
sealant W573-0007 Mill Pac (not supplied). However, the high temperature
sealant W573-0007 Mill Pac (not supplied) must be used on the joint
connecting the inner flex pipe and the exhaust flue collar.
Use only approved flexible vent pipe kits marked:
“Wolf Steel Approved Venting” as identified
by the stamp only on the outer flex pipe.
22.1
ELBOW
SPACERS
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
!
WARNING
4.2.1 HORIZONTAL AIR TERMINAL INSTALLATION

19
W415-1371 / 09.15.14
EN
A. Fasten the roof support to the roof using the screws provided. The
roof support is optional. In this case the venting is to be adequately
supported using either an alternate method suitable to the
authority having jurisdiction or the optional roof support.
B. Stretch the inner flex pipe to the required length. Slip the
inner flex pipe a minimum of 2” (51mm) over the inner pipe
of the air terminal connector and secure with 6 #8 screws.
Seal using a heavy bead of high temperature sealant
W573-0007 (not supplied).
C. Repeat using the outer flex pipe, using a heavy bead of
high temperature sealant W573-0002 (not supplied).
D. Thread the air terminal connector / vent pipe assembly down
through the roof. The air terminal must be positioned vertically
and plumb. Attach the air terminal connector to the roof support,
ensuring that the top of the air terminal is 16” (406mm) above the
highest point that it penetrates the roof.
E. Remove nails from the shingles, above and to the sides of the
air terminal connector. Place the flashing over the air terminal
connector leaving a min. 3/4” (19mm) of the air terminal connector
showing above the top of the flashing. Slide the flashing
underneath the sides and upper edge of the shingles. Ensure that
the air terminal connector is properly centred within the flashing,
giving a 3/4” (19mm) margin all around. Fasten to the roof.
Do not nail through the lower portion of the flashing. Make
weather-tight by sealing with caulking. Where possible, cover
the sides and top edges of the flashing with roofing material.
F. Aligning the seams of the terminal and air terminal connector,
place the terminal over the air terminal connector making
sure the vent pipe goes into the hole in the terminal. Secure
with the three screws provided.
G. Apply a heavy bead of weatherproof caulking 2” (51mm)
above the flashing. Install the storm collar around the air
terminal and slide down to the caulking. Tighten to ensure
that a weather-tight seal between the air terminal and the
collar is achieved.
H. If more vent pipe needs to be used to reach the fireplace see “HORIZONTAL AIR TERMINAL
INSTALLATION” section. 24.2A
STORM COLLAR
FLASHING
CAULKING
WEATHER
SEALANT
2” (51mm) AIR INLET
BASE
ROOF SUPPORT
INNER FLEX PIPE
INNER PIPE
HIGH
TEMPERATURE
SEALANT
AIR
TERMINAL
CONNECTOR
OUTER FLEX PIPE
MAINTAIN A MINIMUM 2” (51mm) SPACE BETWEEN THE AIR INLET BASE AND THE STORM COLLAR.
!
WARNING
4.2.2 VERTICAL AIR TERMINAL INSTALLATION

20
W415-1371 / 09.15.14
EN
This appliance is also certified to be installed as an OEM (Original Equipment Manufacturer) installation
in a manufactured home (U.S. only) or mobile home and must be installed in accordance with the
manufacturer’s instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR,
Part 3280, in the United States or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This
appliance is only for use with the type(s) of gas indicated on the rating plate.
29.1A
This Mobile/Manufactured Home Listed appliance comes factory equipped with a means to secure the unit. Built
in appliances are equipped with 1/4” (6.4mm) diameter holes located in the front left and right corners of the
base. Use #10 hex head screws, inserted through the holes in the base to secure. For free standing products
contact your local authorized dealer / distributor for the appropriate securing kit. For mobile home installations, the
appliance must be fastened in place. It is recommended that the appliance be secured in all installations. Always
turn off the pilot and the fuel supply at the source, prior to moving the mobile home. After moving the mobile home
and prior to lighting the appliance, ensure that the logs are positioned correctly.
This appliance is certified to be installed in an aftermarket permanently located, manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not
convertible for use with other gases, unless a certified kit is used.
A
conversion kit is supplied with the mobile home appliance.
Conversion Kits
This appliance is field convertible between Natural Gas (NG) and Propane (LP).
To convert from one gas to another consult your Authorized dealer/distributor.
A. Install the inner flex pipe to the appliance. Secure with 3 screws
and flat washers. Seal the joint and screw holes using the high
temperature sealant W573-0007 (not supplied).
B. Install the outer flex pipe to the appliance. Attach and seal the
joints using the high temperature sealant Mill-Pac.
28.1B
2” (50.8mm)
OVERLAP
HIGH TEMP
SEALANT
#8 X 1/2”
SELF
DRILLING
SCREWS
4.2.3 APPLIANCE VENT CONNECTION
4.3 MOBILE HOME INSTALLATION
This manual suits for next models
1
Table of contents
Languages:
Other Napoleon Gas Fireplace manuals