White Mountain Hearth VFP24FP2(0,1,2,3)L(N,P)-1 Quick start guide

INSTALLATION INSTRUCTIONS
AND
OWNER'S MANUAL
The Vail Vent-Free Gas Fireplaces
This appliance may be installed in an aftermarket,
permanently located, manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with the type of gas in-
dicated on the rating plate. This appliance is not con-
vertible for use with other gases.
WARNING: If the information in these instructions
are not followed exactly, a re or explosion may
result causing property damage, personal injury or
loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
re department.
— Installation and service must be performed by a
qualied installer, service agency or the gas sup-
plier.
UNVENTED GAS FIREPLACE
HYDRAULIC THERMOSTAT
MODELS:
VFP24FP2(0,1,2,3)L(N,P)-1
MILLIVOLT MODELS:
VFP24FP3(0,1,2,3)L(N,P)-1
VFP24FP3(0,1,2,3)L10(N,P)-1 (10,000 BTU UNIT)
INTERMITTENT PILOT MODELS:
VFP24FP7(0,1,2,3)L(N,P)-1
VFP24FP7(0,1,2,3)L10(N,P)-1 (10,000 BTU UNIT)
Installer: Leave this manual with the appliance.
Consumer: Retain this manual for future reference.
This is an unvented gas-red heater. It uses air (oxy-
gen) from the room in which it is installed. Provisions
for adequate combustion and ventilation air must be
provided. Refer to page 6.
WARNING: If not installed, operated and maintained
in accordance with the manufacturer's instructions,
this product could expose you to substances in fuel
or from fuel combustion which can cause death or
serious illness.
WATER VAPOR: A BY-PRODUCT OF UNVENTED
ROOM HEATERS
Water vapor is a by-product of gas combustion. An
unvented room heater produces approximately one
ounce (30ml) of water for every 1,000 BTU's (.3KW's)
of gas input per hour. Refer to page 6.
Page 1

30411-12-1115Page 2
TABLE OF CONTENTS
IMPORTANT SAFETY INFORMATION........................................................................................................................ 3
SAFETY INFORMATION FOR USERS OF LP-GAS ................................................................................................... 4
INTRODUCTION.......................................................................................................................................................... 5
SPECIFICATIONS........................................................................................................................................................ 6
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS ...................................................................... 6
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR ................................................................... 6-7
GAS SUPPLY............................................................................................................................................................... 8
CLEARANCES............................................................................................................................................................. 9
COMBUSTIBLE MATERIAL......................................................................................................................................... 9
INSTALLATION OF FIREPLACE INTO MANTEL ...................................................................................................... 10
BUILT-IN FIREPLACE INSTALLATION.......................................................................................................................11
PLACEMENT OF GLOWING EMBERS (ROCK WOOL)........................................................................................... 12
OPERATION INSTRUCTIONS/FLAME APPEARANCE ............................................................................................ 12
MILLIVOLT CONTROL LIGHTING INSTRUCTIONS................................................................................................. 13
10,000 BTU MILLIVOLT CONTROL VALVE LIGHTING INSTRUCTIONS ................................................................ 14
HYDRAULIC THERMOSTAT MODELS LIGHTING INSTRUCTIONS ....................................................................... 15
INTERMITTENT PILOT LIGHTING INSTRUCTIONS................................................................................................ 16
LOG IDENTIFICATION...............................................................................................................................................17
LOG PLACEMENT................................................................................................................................................ 18-22
PILOT FLAME CHARACTERISTICS .................................................................................................................... 23-25
MAIN BURNER AND THERMOSTAT OPERATION................................................................................................... 25
MILLIVOLT WIRING................................................................................................................................................... 26
MILLIVOLT TROUBLESHOOTING ............................................................................................................................ 27
INTERMITTANT CONTROL SYSTEM OPERATING INSTRUCTIONS ..................................................................... 28
INTERMITTANT CONTROL SYSTEM WIRING DIAGRAM....................................................................................... 29
INTERMITTENT CONTROL SYSTEM TROUBLESHOOTING............................................................................. 30-32
PARTS LIST .......................................................................................................................................................... 33-34
PARTS VIEW ............................................................................................................................................................. 35
OPTIONAL BRICK LINER INSTALLATION INSTRUCTIONS.................................................................................... 36
OPTIONAL BLOWER INSTALLATION INSTRUCTIONS...................................................................................... 37-40
PARTS LIST AND PARTS VIEW FOR OPTIONAL TRIM KITS ................................................................................. 41
MASTER PARTS DISTRIBUTOR LIST...................................................................................................................... 42
HOW TO ORDER REPAIR PARTS............................................................................................................................ 42
APPLIANCE SERVICE HISTORY.............................................................................................................................. 43
WARRANTY............................................................................................................................................................... 44
SECTION PAGE

30411-12-1115 Page 3
THIS IS A HEATING APPLIANCE
IMPORTANT SAFETY INFORMATION
DANGER: Indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING: Indicates a hazardous situation which, if not avoided,
could result in death or serious injury.
CAUTION: Indicates a hazardous situation which, if not avoided,
could result in minor or moderate injury.
NOTICE: Addresses practices not related to personal injury.
• An unvented room heater having an input rating of more than
6,000 Btu per hour shall not be installed in a bathroom
• An unvented roomheater havinganinputrating of morethan 10,000
Btu per hour shall not be installed in a bedroom or bathroom.
• Due to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
• Children and adults should be alerted to the hazard of high surface
temperature and should stay away to avoid burns or clothing
ignition.
• Young children should be carefully supervised when they are in
the same room with the appliance.
• Do not place clothing or other ammable material on or near the
appliance.
• Avoid the use of scented air fresheners (plug in type air
fresheners, etc. ) while the log set is in operation. Air fresheners
produce a residue in the air similar to candles and may produce
a soot like substance.
• Avoid the use of scented or decorative candles while the log
set is in operation. Candles produce a residue in the air that
creates a soot like substance. Burning candles while the log
set is operating magnies the problem. It should be noted that
candles, in general, produce soot. The amount of time burned
and the quantity of candles burned will determine the amount
of soot produced and deposited.
• Installation and repair should be done by a QUALIFIED SERVICE
PERSON. This appliance should be inspected before use and at
least annually by a professional service person. More frequent
cleaning may be required due to excessive lint from carpeting,
bedding materials, etc. It is imperative that control compartments,
burners and circulating air passageways of the appliance be
kept clean.
• DO NOT use this room heater if any part has been under water.
Immediately call a qualied service technician to inspect the
room heater and to replace any part of the control system and
any gas control which has been under water.
• You must operate heater with replace screen in place.
• Do not place trash, logs or other articles on the log set during
operation.
• During manufacturing, fabricating and shipping, various
components of this appliance are treated with certain oils, lms
or bonding agents. These bonding agents are not harmful but
may produce annoying smoke and smells as they are burned
off during initial operation of the appliance. This is a normal
temporary occurrence. A window should be opened during the
initial bake out period.
• Correct installation of the ceramic ber logs, proper location of
the heater and annual cleaning are necessary to avoid potential
problems with sooting. Sooting, resulting from improper
installation or operation, can settle on surfaces outside the
replace. See instructions for proper installation.
• WARNING: Do not allow fans to blow directly into the
replace. Avoid any drafts that alter burner ame patterns.
• WARNING: Do not use a blower insert, heat exchanger insert
or other accessory not approved for use with this heater.
• WARNING! This replace needs fresh air for ventilation to
run properly. This replace has an ODS (oxygen depletion
sensor) which will shut down the heater if adequate fresh air is
not available. See troubleshooting section in the instructions.
• WARNING: DO NOT operate this appliance unless all
components including logs, burners, and controls are in good
working condition. Never operate this appliance if any log or
twig is broken, or out of their intended position. Refer to the
Log set placement instructions for correct log and twig
positioning.
Replacement components are available through your local
dealer as indicated in the How to Order Repair Parts section of
the appliance manual.
• Keep appliance area clear and free from combustible materials,
gasoline and other ammable vapors and liquids.
• WARNING: Failure to keep the primary air opening(s) of the
burner(s) clean may result in sooting and property damage.
WARNING
When used without adequate combustion and ventilation air,
heater may give off CARBON MONOXIDE, an odorless, poison-
ous gas.
Do not install heater until all necessary provisions are
made for combustion and ventilation air. Consult the writ-
ten instructions provided with the heater for information
concerning combustion and ventilation air. In the absence
of instructions, refer to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation, or
applicable local codes.
This heater is equipped with a PILOT LIGHT SAFETY SYS-
TEM designed to turn off the heater if not enough fresh air
is available.
DO NOT TAMPER WITH PILOT LIGHT SAFETY SYSTEM!
If heater shuts off, do not relight until you provide fresh air.
If heater keeps shutting off, have it serviced. Keep burner and
control compartment clean.
CARBON MONOXIDE POISONING MAY LEAD TO DEATH.
Early signs of carbon monoxide poisoning resemble the u,
with headache, dizziness and/or nausea. If you have these
signs, heater may not be working properly. Get fresh air at
once! Have heater serviced.
Some people — pregnant women, persons with heart or lung
disease, anemia, those under the inuence of alcohol , those
at high altitudes — are more affected by carbon monoxide
than others.
The pilot light safety system senses the depletion of oxygen
at its location. If this heater is installed in a structure having a
high vertical dimension, the possibility exists that the oxygen
supply at the higher levels will be less than that at the heater.
In this type of application, a fan to circulate the structure air will
minimize this effect. The use of this fan will also improve the
comfort level in the structure. When a fan is used to circulate
air, it should be located so that the air ow is not directed at
the burner.

30411-12-1115Page 4
SAFETY INFORMATION FOR USERS OF LP-GAS
Propane (LP-Gas) is a ammable gas which can cause res
and explosions. In its natural state, propane is odorless and
colorless. You may not know all the following safety precautions
which can protect both you and your family from an accident.
Read them carefully now, then review them point by point with
the members of your household. Someday when there may not
be a minute to lose, everyone’s safety will depend on knowing
exactly what to do. If, after reading the following information,
you feel you still need more information, please contact your
gas supplier.
LP-GAS WARNING ODOR
If a gas leak happens, you should be able to smell the gas
because of the odorant put in the LP-Gas.
That's your signal to go into immediate action!
• Do not operate electric switches, light matches, use your phone.
Do not do anything that could ignite the gas.
• Get everyone out of the building, vehicle, trailer, or area. Do
that IMMEDIATELY.
• Close all gas tank or cylinder supply valves.
• LP-Gas is heavier than air and may settle in low areas such
as basements. When you have reason to suspect a gas leak,
keep out of basements and other low areas. Stay out until
reghters declare them to be safe.
• Use your neighbor’s phone and call a trained LP-Gas service
person and the re department. Even though you may not
continue to smell gas, do not turn on the gas again. Do not
re-enter the building, vehicle, trailer, or area.
• Finally, let the service man and reghters check for escaped
gas. Have them air out the area before you return. Properly
trained LP-Gas service people should repair the leak, then
check and relight the gas appliance for you.
NO ODOR DETECTED - ODOR FADE
Some people cannot smell well. Some people cannot smell
the odor of the chemical put into the gas. You must nd out if
you can smell the odorant in propane. Smoking can decrease
your ability to smell. Being around an odor for a time can affect your
sensitivity or ability to detect that odor. Sometimes other odors in
the area mask the gas odor. People may not smell the gas odor or
their minds are on something else. Thinking about smelling a gas
odor can make it easier to smell.
The odorant in LP-gas is colorless, and it can fade under some
circumstances. For example, if there is an underground leak, the
movement of the gas through soil can lter the odorant. Odorants in
LP-Gas also are subject to oxidation. This fading can occur if there
is rust inside the storage tank or in iron gas pipes.
The odorant in escaped gas can adsorb or absorb onto or into
walls, masonry and other materials and fabrics in a room. That will
take some of the odorant out of the gas, reducing its odor intensity.
LP-Gas may stratify in a closed area, and the odor intensity could
vary at different levels. Since it is heavier than air, there may be
more odor at lower levels. Always be sensitive to the slightest gas
odor. If you detect any odor, treat it as a serious leak. Immediately
go into action as instructed earlier.
SOME POINTS TO REMEMBER
• Learn to recognize the odor of LP-gas. Your local LP-Gas
Dealer can give you a “Scratch and Sniff” pamphlet. Use it to
nd out what the propane odor smells like. If you suspect that
your LP-Gas has a weak or abnormal odor, call your LP-Gas
Dealer.
• If you are not qualied, do not light pilot lights, perform service,
or make adjustments to appliances on the LP-Gas system. If
you are qualied, consciously think about the odor of LP-Gas
prior to and while lighting pilot lights or performing service or
making adjustments.
• Sometimes a basement or a closed-up house has a musty
smell that can cover up the LP-Gas odor. Do not try to light
pilot lights, perform service, or make adjustments in an area
where the conditions are such that you may not detect the odor
if there has been a leak of LP-Gas.
• Odor fade, due to oxidation by rust or adsorption on walls of
new cylinders and tanks, is possible. Therefore, people should
be particularly alert and careful when new tanks or cylinders
are placed in service. Odor fade can occur in new tanks, or
reinstalled old tanks, if they are lled and allowed to set too
long before relling. Cylinders and tanks which have been out
of service for a time may develop internal rust which will cause
odor fade. If such conditions are suspected to exist, a periodic
sniff test of the gas is advisable. If you have any question
about the gas odor, call your LP-gas dealer. Aperiodic
sniff test of the LP-gas is a good safety measure under
any condition.
• If, at any time, you do not smell the LP-Gas odorant and you
think you should, assume you have a leak. Then take the same
immediate action recommended above for the occasion when
you do detect the odorized LP-Gas.
• If you experience a complete “gas out,” (the container is under
no vapor pressure), turn the tank valve off immediately. If the
container valve is left on, the container may draw in some air
through openings such as pilot light orices. If this occurs, some
new internal rusting could occur. If the valve is left open, then
treat the container as a new tank. Always be sure your con-
tainer is under vapor pressure by turning it off at the container
before it goes completely empty or having it relled before it is
completely empty.

30411-12-1115 Page 5
INTRODUCTION
Instructions to Installer
1. Installer must leave instruction manual with owner after
installation.
2. Installer must have owner ll out and mail warranty card supplied
with unvented room heater.
3. Installer should show owner how to start and operate unvented
room heater.
Always consult your local Building Department regarding regula-
tions, codes or ordinances which apply to the installation of an
unvented room heater.
This appliance may be installed in an aftermarket* manufactured
(mobile) home, where not prohibited by state or local codes.
*Aftermarket: Completion of sale, not for purpose of resale, from
the manufacturer.
This appliance is only for use with the type of gas indicated on the
rating plate. This appliance is not convertible for use with other gases.
Well Head Gas Installations
Some natural gas utilities use "well head" gas. This may affect the
Btu output of the unit. Contact the gas company for the heating value.
Contact the manufacturer or your gas company before changing
spud/orice size.
WARNING
ANY CHANGE TO THIS HEATER OR ITS CONTROLS CAN
BE DANGEROUS.
Improper installation or use of the heater can cause seri-
ous injury or death from re, burns, explosion or carbon
monoxide poisoning.
Operation
This unvented replace requires no outside venting. This unvented
replace is designed for vent-free operation with ue damper closed.
State and local codes in some areas prohibit the use of unvented
replace.
Millivolt Controls
The valve regulator controls the burner pressure which should be
checked at the pressure test point. Turn captured screw counter
clockwise 2 or 3 turns and then place tubing to pressure gauge over
test point (Use test point “A” closest to control knob). After taking
pressure reading, be sure and turn captured screw clockwise rmly
to re-seal. Do not over torque. Check for gas leaks.
Millivolt System,
When you ignite the pilot, the thermocouple produces millivolts
(electrical current) which energizes the magnet in the gas valve.After
30 seconds to 1 minute time period you can release the gas control
knob and the pilot will stay ON. Allow your pilot ame to operate
an additional one to two minutes before you turn the gas control
knob from the PILOT position to the ON position. This time period
allows the millivolts (electrical current) to build-up to a sufcient
level allowing the gas control to operate properly.
WARNING
This appliance is equipped for (natural gas or propane) gas. Field
conversion is not permitted.
General Information
This series is design certied in accordance with American National
Standard Z21.11.2 by the Canadian Standards Association as an
Unvented Room Heater and should be installed according to these
instructions.
Any alteration of the original design, installed other than as
shown in these instructions or use with a type of gas not
shown on the rating plate is the responsibility of the person
and company making the change.
Important
All correspondence should refer to complete Model Number, Serial
Number and type of gas.
Attention: During initial use of log you will detect an odor as
the log is cured. Also, during the curing process the ceramic
log will burn with a yellow ame.
Notice: During initial ring of this unit, its paint will bake out, and
smoke will occur. To prevent triggering of smoke alarms, ventilate
the room in which the unit is installed.
Installation on Rugs and Tile
If this appliance is installed directly on carpeting, tile or other
combustible material other than wood ooring the appliance shall
be installed on a metal or wood panel extending the full width and
depth of the appliance.
The base referred to above does not mean the re-proof base as
used on wood stoves. The protection is for rugs that are extremely
thick and light colored tile.
Solid-fuels shall not be burned in a masonry or UL 127 factory-
built replace in which an unvented room heater is installed.
Qualied Installing Agency
Installation and replacement of gas piping, gas utilization equipment
or accessories and repair and servicing of equipment shall be per-
formed only by a qualied agency. The term "qualied agency" means
any individual, rm, corporation or company which either in person
or through a representative is engaged in and is responsible for (a)
the installation or replacement of gas piping or (b) the connection,
installation, repair or servicing of equipment, who is experienced in
such work, familiar with all precautions required and has complied
with all the requirements of the authority having jurisdiction.
State of Massachusetts: The installation must be made by a
licensed plumber or gas tter in the Commonwealth of Mas-
sachusetts.
Sellers of unvented propane or natural gas-red supplemental
room heaters shall provide to each purchaser a copy of 527 CMR
30 upon sale of the unit.
In the State of Massachusetts, unvented propane and natural
gas-red space heaters shall be prohibited in bedrooms and
bathrooms.
The installation must conform with local codes or, in the absence
of local codes, with the National Fuel Gas Code, ANSI Z223.1.*
*Available from theAmerican National Standards Institute, Inc. 1430
Broadway, New York, N.Y. 10018.
High Altitudes
For altitudes/elevations above 2,000 feet (610m), ratings should be
reduced at the rate of 4 percent for each 1,000 feet (305m) above
sea level. Contact the manufacturer or your gas company before
changing spud/orice size.
WARNING
Failure to keep the primary air opening(s) of the burner(s)
clean may result in sooting and property damage.

30411-12-1115Page 6
Water vapor is a by-product of gas combustion. An unvented room
heater produces approximately one ounce (30ml) of water for every
1,000 BTU's (.3KW's) of gas input per hour. .
Unvented room heaters are recommended as supplemental heat (a
room) rather than a primary heat source (an entire house). In most
supplemental heat applications, the water vapor does not create a
problem. In most applications, the water vapor enhances the low
humidity atmosphere experienced during cold weather.
This heater shall not be installed in a conned space or unusu-
ally tight construction unless provisions are provided for adequate
combustion and ventilation air.
A conned space is an area with volume less than 50 cubic feet per
1,000 Btuh of the combined input rates of all appliances drawing
combustion air from that space. Small areas such as equipment
rooms are conned spaces. Furnaces installed in a conned space
which supply heated air to areas outside the space must draw return
air from outside the space through tightly sealed return air ducts. A
conned space must have 2 openings into the space for combus-
tion air. One opening must be within 12 inches of the ceiling and
the other must be within 12 inches of the oor. The required sizing
of these openings is determined by whether inside or outside air is
used to support combustion, the method by which the air is brought
to the space (vertical or horizontal duct) and by the total input rate
of all appliances in the space.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is dened as construction
where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm
or less with openings gasketed or sealed, and
b. Weatherstripping has been added on openable windows and
doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and
oors, between wall-ceiling joints, between wall panels, at
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
SPECIFICATIONS
Model VFP24FP3*L
VFP24FP7*L VFP24FP2*L VFP24FP3*L10
Input Max. 20,000 20,000 10,000
Input Min. 14,000 10,000 10,000
Fireplace Dimensions
Height 26 3/8" 26 3/8" 26 3/8"
Depth 10 7/8" 10 7/8" 10 7/8"
Front Width 22 5/8" 22 5/8" 22 5/8"
Rear Width 17 1/4" 17 1/4" 17 1/4"
Gas Inlet 3/8" 3/8" 3/8"
* Indicates optional accessories that may be installed.
Accessories
FBB6 Automatic Blower
VPP1A-22 Aged Brick Liner
VFF24BR-1 Brass Trim Kit
VFF24SS-1 Stainless Steel Trim Kit
VFF24HP-1 Hammered Pewter Trim Kit
Accessories for Millivolt and Intermittant Models Only
FRBC Battery Operated Remote Control
FRBTC Battery Operated Remote Control w/Thermostat
FREC Electric Remote Control
FWS Wall Switch
TMV Wall Thermostat, Millivolt - Reed Switch
TRW Wireless Remote Wall Thermostat
penetrations for plumbing, electrical, and gas lines, and at
other openings.
If your home meets all of the three criteria above, you must provide
additional fresh air. See “Ventilation Air From Outdoors,” page
7.
Determining if You Have a Conned or Unconned Space
Use this worksheet to determine if you have a conned or unconned
space.
Space: Includes the room in which you will install heater plus any
adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height = cu. ft. (volume of
space)
Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling
height) = 1,280 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills
or openings, add the volume of these rooms to the total volume
of the space.
2. Divide the space volume by 50 cubic feet to determine the
maximum BTU/Hr the space can support.
(volume of space) ÷ 50 cu. ft. = (maximum
BTU/Hr the space can support)
Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6 or
25,600 (maximum BTU/Hr the space can support)
The following steps will help insure that water vapor does not
become a problem.
1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidier may be used to
help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat
source.

30411-12-1115 Page 7
3. Add the BTU/Hr of all fuel burning appliances in the space.
Vent-free heater BTU/Hr
Gas water heater BTU/Hr
Gas furnace BTU/Hr
Vented gas heater BTU/Hr
Gas replace logs BTU/Hr
Other gas appliances* + BTU/Hr
Total = BTU/Hr
Example: Vented gas heater 20,000 BTU/Hr
Vent-free heater + 18,000 BTU/Hr
Total = 38,000 BTU/Hr
*Do not include direct-vent gas appliances. Direct vent draws
combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum BTU/Hr the space can support with the
actual amount of BTU/Hr used.
BTU/Hr (maximum the space can support)
BTU/Hr (actual amount of BTU/Hr used)
Example:
25,600 BTU/Hr (maximum the space can support)
38,000 BTU/Hr (actual amount of BTU/Hr used)
WARNING
If the area in which the heater may be operated is smaller than that
dened as an unconned space or if the building is of unusually
tight construction, provide adequate combustion and ventilation air
by one of the methods described in the National Fuel Gas Code,
ANSI Z223.1, Section 5.3 or applicable local codes.
The space in the above example is a conned space because the
actual BTU/Hr used is more than the maximum BTU/HR the space
can support. You must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an adjoining room. If
the extra space provides an unconned space, remove door
to adjoining room or add ventilation grills between rooms. See
Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See Ventilation Air From
Outdoors.
C. Install a lower BTU/Hr heater, if lower BTU/Hr size makes room
unconned.
If the actual BTU/Hr used is less than the maximum BTU/Hr the
space can support, the space is an unconned space. You will need
no additional fresh air ventilation.
WARNING
You must provide additional ventilation air in a conned
space.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When
ventilating to an adjoining unconned space, you must provide two
permanent openings: one within 12" of the ceiling and one within
12" of the oor on the wall connecting the two spaces (see options
1 and 2, Figure 1). You can also remove door into adjoining room
(see option 3, Figure 1). Each ventilation grill or opening shall have
a minimum free area of one square inch per 1,000 BTU/HR of the
total input rating of the gas equipment in the conned space.
Figure 1
WARNING
Rework worksheet, adding the space of the adjoining
unconned space. The combined spaces must have enough
fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one with 12" of the oor. Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces include attics and
crawl spaces. In most cases for direct communication with the
outdoors or direct communication through a vertical duct a free
area opening of one square inch per 4,000 BTU/HR of heater input
rating for each grill. If a horizontal duct is used, a grill free area or
duct opening shall have a free area opening of one square inch per
2,000 BTU/HR for each grill. Follow the National Fuel Code NFPA
54/ANSI Z223.1, Section 5.3 Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic
if attic has a thermostat-controlled power vent. Heated air entering
the attic will activate the power vent.
Figure 2

30411-12-1115Page 8
GAS SUPPLY
Check all local codes for requirements, especially for the size and
type of gas supply line required.
Recommended Gas Pipe Diameter
Pipe Length Schedule 40 Pipe
Inside Diameter
Tubing, Type L
Outside Diameter
Nat. L.P. Nat. L.P.
0-10 feet
0-3 meters
1/2”
12.7mm
3/8”
9.5mm
1/2”
12.7mm
3/8”
9.5mm
10-40 feet
4-12 meters
1/2”
12.7mm
1/2”
12.7mm
5/8”
15.9mm
1/2”
12.7mm
40-100 feet
13-30 meters
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
1/2”
12.7mm
100-150 feet
31-46 meters
3/4”
19mm
1/2”
12.7mm
7/8”
22.2mm
3/4”
19mm
NOTICE: Never use plastic pipe. Check to conrm whether your
local codes allow copper tubing or galvanized.
NOTICE:Since some municipalities have additional local codes, it
is always best to consult your local authority and installation code.
Installing a New Main Gas Cock
Each appliance should have its own manual gas cock.
A manual main gas cock should be located in the vicinity of the unit.
Where none exists, or where its size or location is not adequate,
contact your local authorized installer for installation or relocation.
Compounds used on threaded joints of gas piping shall be resistant
to the action of liqueed petroleum gases. The gas lines must be
checked for leaks by the installer. This should be done with a soap
solution watching for bubbles on all exposed connections, and if
unexposed, a pressure test should be made.
Never use an exposed ame to check for leaks. Appliance must
be disconnected from piping at inlet of control valve and pipe
capped or plugged for pressure test. Never pressure test with
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas
line upstream of the gas control to aid in servicing. It is required by
the National Fuel Gas Code that a drip line be installed near the gas
inlet. This should consist of a vertical length of pipe tee connected
into the gas line that is capped on the bottom in which condensation
and foreign particles may collect.
The use of the following gas connectors is recommended:
— ANS Z21.24Appliance Connectors of Corrugated Metal Tubing
and Fittings
— ANS Z21.45Assembled FlexibleAppliance Connectors of Other
Than All-Metal Construction
The above connectors may be used if acceptable by the author-
ity having jurisdiction. The state of Massachusetts requires that a
exible appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1. To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T.
plugged tapping, accessible for test gauge connection, must
be placed immediately upstream of the gas supply connection
to the appliance.
2. The appliance and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of
1/2 psig (3.5 kPa).
3. The appliance must be isolated from the gas supply piping
system by closing its individual manual shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig (3.5 kPa).
Figure 3
Attention! If one of the above procedures results in pressures in
excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve,
it will result in a hazardous condition.
Checking Manifold Pressure
Millivolt and Intermittant Models Natural gas will have a manifold
pressure of approximately 3.5" w.c. (.871kPa) for maximum input or
1.7" w.c. (.423kPa) for minimum input at the pressure regulator outlet
with the inlet pressure to the pressure regulator from a minimum
of 5.0" w.c. (1.120kPa) for the purpose of input adjustment to a
maximum of 10.5" w.c. (2.614kPa).
Hydraulic Thermostat Models Natural gas will have a manifold
pressure of approximately 6.0" w.c. (1.49kPa) at the pressure
regulator outlet with the inlet pressure to the pressure regulator
from a minimum of 7.0" w.c. (1.74kPa) for the purpose of input
adjustment to a maximum of 10.5" w.c. (2.615kPa).
Millivolt and Intermittant Models Propane gas will have a manifold
pressure approximately 10.0"w.c. (2.49kPa) for maximum input or
6.3"w.c. (1.568kPa) for minimum input at the pressure regulator outlet
with the inlet pressure to the pressure regulator from a minimum
of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a
maximum of 13.0"w.c. (3.237kPa).
Hydraulic Thermostat Models Propane gas will have a manifold
pressure approximately 10.0"w.c. (2.49kPa) at the pressure regulator
outlet with the inlet pressure to the pressure regulator from a minimum
of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a
maximum of 13.0"w.c. (3.237kPa).

30411-12-1115 Page 9
CLEARANCES
COMBUSTIBLE MATERIAL
Do not attach combustible material to the mantel of your replace.
This is a re hazard.
Figure 6
No greeting cards, stockings or ornamentation of any type should be
placed on or attached to the replace. This is a heating appliance.
The ow of heat can ignite combustibles.
Figure 7
Minimum Wall and Ceiling Clearances
30”
(762mm)
4”
(101mm)
Figure 4
This fireplace can be installed with zero clearance to
combustible material.
When facing the front of the appliance the minimum clearances to
combustible construction (material) are the following:
1. Clearances from the right side or left side of the replace opening
to any combustible wall or material should not be less than 4
inches.
2. Clearances from the top of the replace opening to the ceiling
should not be less than 30 inches.
Mantel Clearances for Built-in Installation
Figure 5

30411-12-1115Page 10
INSTALLATION OF FIREPLACE INTO MANTEL
1. Position base approximately 5" from wall surface.
2. Attach nailing ange to replace top with two 10 x 1/2" screws.
3. Place replace on top of base.
4. Gas line connections must be made at this time. When facing
the replace the gas supply will enter on right-hand side. See
"Gas Supply" Page 8.
5. Place right mantel side against base. Insert dowels in breastboard
into right mantel side. Breastboard will rest on replace
top and in front of nailing ange.
Attention: Placing the breastboard in front of nailing ange will
secure the replace.
6. Place left mantel side against base. Insert dowels in breastboard
into left mantel side.
7. Use four pre-drilled screw holes on back of breastboard to
secure breastboard to mantel sides with four Phillips wood
screws.
8. Place mantel top onto mantel.
9. Installation of replace into mantel is completed.
Installation of Trim
1. Lower bottom louver.
2. Remove screen from replace.
3. Remove top louver from replace (two Phillips screws).
4. Attach right and lift trim to replace. Use two Phillips screws
for each side.
5. Attach trim top to replace with two Phillips screws.
6. Reattach top louver to replace using two Phillips screws.
7. Reattach screen to replace.
8. Raise bottom louver.
Figure 8
Installing Fireplace in Mantel
Figure 9

30411-12-1115 Page 11
BUILT-IN FIREPLACE INSTALLATION
Built-In Fireplace Installation
Built-in installation of this replace involves installing replace into
a framed-in enclosure. This makes the front of replace ush with
wall. If installing a mantel above the replace, you must follow the
clearances shown in Figure 5, page 9. Follow the instructions below
to install the replace in this manner.
Frame in rough opening. Use dimensions shown in Figure 10 for a
conventional rough opening. Use dimensions shown in Figure 11
for corner rough opening. Be sure to provide gas line for replace
and electrical power for FBB6 optional blower assembly.
1. Attach two nailing anges to rebox sides with two 10 x 1/2"
screws for each nailing ange.
2. Gas line connections must be made at this time. When facing
the appliance the gas supply will enter on right-hand side. See
"Gas Supply" Page 8.
3. Insert replace into enclosure.
4. Attach nailing anges to framing with a screw or nail.
5. Finished wall surface will be ush to the leading edge of replace
top and sides.
6. Installation of built-in replace is completed.
Installation of Trim
1. Lower bottom louver.
2. Remove screen from replace.
3. Remove top louver from replace.
4. Attach right and lift trim to replace. Use two Phillips screws
for each side.
5. Attach trim top to replace with two Phillips screws.
6. Reattach top louver to replace using two Phillips screws.
7. Reattach screen to replace.
8. Raise bottom louver.
Rough Opening for Installing in Wall
FLUSH
INSTALLATION
PROJECTED
INSTALLATION
1” TO 6” FROM BACK
25mm TO 152mm
ELECTRICAL
RECEPTACLE
26 3/4”
(680mm)
4” (102mm)
GAS SUPPLY
23 1/4” (591mm)
11 1/4”
(286mm)
Figure 10
Rough Opening for Installing in Corner
23 "(584mm)
27 9/16" (700mm)
19 1/2"
(495mm)
39 "(991mm)
Figure 11
Figure 12

30411-12-1115Page 12
Provided with the log set is a small bag of glowing embers (rock
wool) to be placed between logs on the at metal surface of the
burner.
Placement of the embers (rock wool) is very individual and light
coverage of the areas indicated will provide your best effects. We
recommend separation of the rock wool by hand and make your
coverage as light and uffy as possible.
Place just enough embers (rock wool) on the burner to obtain the
glow and a gold yellow ame.
A thin layer of rock wool should be placed under open space
between the right and left middle logs.
Do not place rock wool over large ports in rear portion of burner.
Do not place rock wool in the area of the pilot assembly.
Replacement of loose material (glowing embers) must be purchased
from Empire Comfort Systems, Inc. Application of excess loose
material (glowing embers) may adversely affect performance of
the heater.
WARNING
All previously applied loose material must be removed prior to
reapplication.
Refer to Parts List, Pages 33-34 to order loose material (rock wool).
Replacement Loose Material (Glowing Embers)
15998 Supplied Rock Wool
PE-20-1 Optional Platinum Bright Embers Kit
NOTICE: A single layer of embers is to be used when applying
Platinum Bright Embers (alone or in combination with production
embers) to the burner.
Flames from the pilot (rear right back side of the pan burner) as
well as the main ame should be visually checked as the log set
is installed.
In normal operation at full rate after 10 to 15 minutes, the ame
appearance should be sets of yellow ames.
NOTICE: all ames will be random by design, ame height will go
up and down.
Glowing embers (rock wool) can cover the pan burner in between
the front and middle logs, but very little is necessary to cover this
area. Excess ember material causes the yellow ame to become
orange and stringy. Apply just enough to obtain slow glow and a
gold, yellow ame.
Avoid any drafts that alter burner ame patterns. Do not allow fans to
blow directly into replace. Do not place a blower inside the burner
area of the rebox. Ceiling fans may create drafts that alter ame
patterns. Sooting and improper burning will result.
During manufacturing, fabricating and shipping, various components
of this appliance are treated with certain oils, lms or bonding agents.
These chemicals are not harmful, but may produce smoke and
smells as they burn off during the initial operation of the appliance,
possibly causing headaches or eye or lung irritation. This is a normal
and temporary occurrence.
The initial break-in operation should last 2-3 hours with the burner
at the highest setting. Provide maximum ventilation by opening
windows or doors to allow odors to dissipate. Any odors remaining
after this initial break-in will be slight and will disappear with
continued use.
This appliance must not be used with glass doors in the closed
position. This can lead to pilot outages and severe sooting outside
the replace.
PERIODIC CLEANING – Refer to parts diagram for location of
items discussed below.
• Do not use cleaning uid to clean logs or any part of heater.
• Logs - brush with soft bristle brush or vacuum with brush
attachment.
• Remove loose particles and dust from the burner areas,
controls, piezo covers and grate. Don’t remove ceramic media
from inside burner box.
• Inspect and clean burner air intake hole. Remove lint or particles
with brush. Failure to keep air intake hole clean will result in
sooting and poor combustion.
ANNUAL CLEANING/INSPECTION – Refer to parts diagram for
location of items discussed below.
• Inspect and clean burner air intake hole. Remove lint or particles
with vacuum or brush. Failure to keep air intake hole clean will
result in sooting and poor combustion.
• Inspect and clean all burner ports.
• Inspect ODS pilot for operation and accumulation of lint at air
intake holes.
• Verify ame pattern and log placement for proper operation.
• Verify smooth and responsive ignition of main burner.
• Check level of ceramic media in burner. Burner should be full,
up to the level of openings in burner top.
PLACEMENT OF GLOWING EMBERS (ROCK WOOL)
OPERATION INSTRUCTIONS/FLAME APPEARANCE

30411-12-1115 Page 13
WARNING: If you do not follow these instructions exactly, a re or explosion may
result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these instructions
exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it; call a qualied service
technician. Force or attempted repair may result in a
re or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
LIGHTING INSTRUCTIONS
1. Open bottom louver assembly (if applicable).
2. Set REMOTE/OFF/ON switch to OFF.
3. Turn off all electric power to the appliance if service is to be
performed (if applicable).
4. Push in gas control knob slightly and turn clockwise
to "OFF." Do not force.
5. Close bottom louver assembly (if applicable).
1. STOP! Read the safety information label.
2. Open bottom louver assembly.
3. Set REMOTE/OFF/ON switch to
"OFF."
4. Turn off all electric power to the
appliance (if applicable).
5. Push in gas control knob slightly
and turn clockwise to
"OFF." NOTE: Knob cannot be
turned from "PILOT" to "OFF" un-
less knob is pushed in slightly. Do not force.
6. Wait ten minutes to clear out any gas. Then
smell for gas, including near the oor. If you
smell gas, STOP! Follow "B" in the safety
information above. If you do not
smell gas, go to the next step.
7. Find pilot - Follow metal tube from
gas control. The pilot is behind
the burner on the right side.
8. Turn gas control knob counterclockwise to
"PILOT."
9. Push in control knob all the way and hold in. Repeatedly push
the Piezo Ignitor Button until the pilot is lit. Continue to hold
the control knob in for about one minute after the pilot is lit.
Release knob, and it will pop back up. Pilot should remain lit.
If it goes out, repeat steps 5 through 9.
• If knob does not pop up when released, STOP and IM-
MEDIATELY call a qualied service technician or gas
supplier.
• If the pilot will not stay lit after several tries, turn the gas
control knob to "OFF" and call your service technician or
gas supplier.
10. Turn gas control knob counterclockwise to "ON."
11. Set REMOTE/OFF/ON switch to desired setting.
12. Turn on all electric power to the appliance (if applicable).
13. Close bottom louver assembly.
GAS CONTROL KNOB
SHOWN IN "OFF" POSITION.
THERMOCOUPLE
(NATURAL)
ELECTRODE
PILOT
THERMOPILE
REMOTE
OFF
ON
THERMOCOUPLE
(LPG)
GAS CONTROL KNOB
SHOWN IN "OFF" POSITION.
THERMOCOUPLE
(NATURAL)
ELECTRODE
PILOT
THERMOPILE
REMOTE
OFF
ON
THERMOCOUPLE
(LPG)
GAS CONTROL KNOB
SHOWN IN "OFF" POSITION.
THERMOCOUPLE
(NATURAL)
ELECTRODE
PILOT
THERMOPILE
REMOTE
OFF
ON
THERMOCOUPLE
(LPG)
MILLIVOLT CONTROL LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
TO TURN OFF GAS TO APPLIANCE

30411-12-1115Page 14
A. This appliance has a pilot which must be lighted by hand.
When lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it; call a qualied service
technician. Force or attempted repair may result in a re
or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
1. Open bottom louver assembly (if applicable).
2. Set REMOTE/OFF/ON switch to OFF.
3. Turn off all electric power to the appliance if service is
to be performed (if applicable).
4. Push in gas control knob slightly and turn clockwise
to "OFF." Do not force.
5. Close bottom louver assembly (if applicable).
1. STOP! Read the safety information above.
2. Open bottom louver assembly,
(if applicable).
3. Set REMOTE/OFF/ON switch
to "OFF."
4. Turn off all electric power to
the appliance (if applicable).
5. Push in gas control knob
slightly and turn clockwise
to "OFF."
6. Wait ten minutes to clear out any gas.
Then smell for gas, including near the
oor. If you smell gas, STOP!
Follow "B" in the safety infor-
mation above. If you do not
smell gas, go to the next step.
7. Find pilot - Follow metal tube
from gas control. The pilot is
located next to the burner, near
the right side.
8. Turn gas control knob counter-
clockwise to "PILOT."
9. Push in control knob all the way and hold in. Repeat-
edly push the Piezo Ignitor Button until the pilot is lit.
Continue to hold the control knob in for about one minute
after the pilot is lit. Release knob, and it will pop back
up. Pilot should remain lit. If it goes out, repeat steps 5
through 9.
• If knob does not pop up when released, STOP and
IMMEDIATELY call a qualied service technician or
gas supplier.
• If the pilot will not stay lit after several tries, turn
the gas control knob to "OFF" and call your service
technician or gas supplier.
10. Turn gas control knob counterclockwise to
"ON."
11. Set REMOTE/OFF/ON switch to desired setting.
12. Turn on all electric power to the appliance (if applicable).
13. Close bottom louver assembly (if applicable).
OFF
PILOT
ON
GAS CONTROL KNOB
SHOWNIN "OFF" POSITION.
GAS CONTROL KNOB
SHOWN IN "OFF" POSITION.
THERMOCOUPLE
(NATURAL)
ELECTRODE
PILOT
THERMOPILE
REMOTE
OFF
ON
THERMOCOUPLE
(LPG)
GAS CONTROL KNOB
SHOWN IN "OFF" POSITION.
THERMOCOUPLE
(NATURAL)
ELECTRODE
PILOT
THERMOPILE
REMOTE
OFF
ON
THERMOCOUPLE
(LPG)
10,000 BTU MILLIVOLT CONTROL VALVE LIGHTING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE LIGHTING
LIGHTING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE
WARNING: If you do not follow these instructions exactly, a re or explosion may
result causing property damage, personal injury or loss of life.

30411-12-1115 Page 15
WARNING: If you do not follow these instructions exactly, a re or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by
hand. When lighting the pilot, follow these instructions
exactly.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the oor because some
gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch;
Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re
department.
C. Use only your hand to push in or turn the gas control
knob. Never use tools. If the knob will not push in
or turn by hand, don't try to repair it; call a qualied
service technician. Force or attempted repair may
result in a re or explosion.
D. Do not use this appliance if any part has been under
water. Immediately call a qualied service technician
to inspect the appliance and to replace any part of the
control system and any gas control which has been
under water.
3. Push in gas control knob slightly and turn clock-
wise to "OFF". Do not force.
1. Set thermostat (gas control knob) to lowest setting.
2. Turn off all electric power to appliance if service is to
be performed (if applicable).
1. STOP! Read the safety information above.
2. Set thermostat (gas control knob) to lowest setting.
3. Turn off all electric power to the appliance (if applicable).
4. Push in gas control knob slightly and turn clockwise
to "OFF." Do not force.
5. Wait ten minutes to clear out any gas. Then smell for gas,
including near oor. If you smell gas, STOP! Follow "B" in the
safety information on other side. If you do not smell gas, Go
to the Next step.
6. Find pilot - the pilot is located in front of rear log.
7. Turn manual gas control knob counterclockwise to
"PILOT."
8. Push in manual gas control knob all the way and hold in. Re-
peatedly push the piezo ignitor button until pilot is lit (or use a
match to light). Continue to hold the control knob in for about
one minute after the pilot is lit. Release knob and it will pop
back up. Pilot should remain lit. If it goes out, repeat steps 4
through 8.
• If knob does not pop up when released, stop and immedi-
ately call a qualied service technician or gas supplier.
• If the pilot will not stay lit after several tries, turn the gas
control knob to "OFF" and call a qualied service techni-
cian or gas supplier.
9. Attention! Gas control has an INTERLOCK latching device.
When the pilot is initially lit and the safety magnet is energized
(pilot stays "ON") the INTERLOCK latching device becomes
operative. If the gas control is turned to the "OFF" position or
gas ow to the appliance is shut off, the pilot cannot be re-
lighted until the safety magnet is de-energized (approximately
60 seconds). There will be an audible "click" when the safety
magnet in the gas control is de-energized. Pilot can now be
relighted. Repeat steps 4 through 8.
10. Turn the gas control knob counterclockwise to "HIGH
(5)."
11. Turn on all electric power to the appliance (if applicable).
12. Set the thermostat (gas control knob to desired setting from
"HIGH (5)" to "LOW (1)."
HYDRAULIC THERMOSTAT MODELS LIGHTING INSTRUCTIONS
PIEZO IGNITOR
FOR YOUR SAFETY READ BEFORE LIGHTING
LIGHTING INSTRUCTIONS
TO TURN OFF GAS TO APPLIANCE

30411-12-1115Page 16
TO TURN OFF GAS TO FIREPLACE
1. STOP! Read the safety information above.
2. Turn OFF electric power to the appliance.
3. Remove front surround panel assembly or bottom louver if
included.
4. Turn gas cock counterclockwise to “On” position.
5. Wait ten minutes to clear out any gas. Then smell for gas,
including near the oor. If you smell gas, STOP! Follow “B” in
the safety information above on this page. If you do not smell
gas, go to the next step.
6. Turn ON electric power to the appliance.
7. Find pilot - Follow metal tube from gas control. The pilot is
behind the burner on the right side.
8. Turn main ame to on. If the pilot does not light within 60
seconds, stop and go to Step 5.
9. Refer to remote control instructions for detailed information,
control features, and operation. Note: There is a CPI/IPI switch
behind the right side panel that allows for a continuous standing
pilot mode or an intermittent pilot mode. See appliance manual
for location of this switch. If the pilot or burner does not stay
lit (in the standing pilot mode), stop and immediately call a
qualied service technician or gas supplier.
10. If the burner or pilot does not operate properly after several
tries, turn the gas cock clockwise to “OFF” and call
your service technician or gas supplier.
11. Replace the front surround assembly or close bottom louver
assembly.
12. Operation of the gas valve is controlled by a manual on/
off switch or a hand held remote control. Refer to remote
instructions for detailed operation information.
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING: If you do not follow these instructions exactly, a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance has a pilot which must be lighted by hand. When
lighting the pilot, follow these instructions exactly.
B. Before lighting smell all around the appliance area for gas. Be
sure to smell next to the oor because some gas is heavier
than air and will settle on the oor.
What To Do If You Smell Gas
• Do not try to light any appliance.
• Do not touch any electrical switch;
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the re depart-
ment.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don't try to repair it; call a qualied service technician. Force
or attempted repair may result in a re or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system and
any gas control which has been under water.
LIGHTING INSTRUCTIONS
1. Set REMOTE/OFF/ON switch to OFF.
2. Turn off all electric power to the appliance if service is to be
performed (if applicable).
3. Lower bottom louver assembly.
4. Push in gas control knob slightly and turn clockwise
to "OFF." Do not force.
5. Close bottom louver assembly.
INTERMITTENT PILOT LIGHTING INSTRUCTIONS
OFF ON
GAS COCK
PILOT
ELECTRODE
FLAME
SENSOR

30411-12-1115 Page 17
VFP24 LOG IDENTIFICATION
Log
Description Part Number Front View Top View
Log A R7506
Log B R7504
Log C R7505

30411-12-1115Page 18
Before you begin: Do not, handle these logs with your bare hands!
Always wear gloves to prevent skin irritation. After handling logs,
wash your hands gently with soap and water.
All Logs
The positioning of the logs is critical to the safe and clean operation
of this heater. Sooting and other problems may result if the logs are
not properly and rmly positioned in the appliance.
The following Warning applies when log set is installed onto an
unvented gas burner assembly.
Note: Replacement Glowing Embers must be purchased from an
authorized distributor.
Attention: When ordering parts, it is very important that part num-
ber and description of part coincide.
USE ONLY MANUFACTURER'S REPLACEMENT PARTS. USE
OF ANY OTHER PARTS COULD CAUSE INJURY OR DEATH.
LOG PLACEMENT
Glowing Ember Placement
WARNING
All previously applied Glowing Embers must be removed
prior to reapplication.
Applying Glowing Embers as shown in the image below.
Note: Application of excess Glowing Embers may adversely af-
fect performance of the replace.
WARNING
Failure to position the parts in accordance with this diagram
or failure to use only parts specically approved with this
appliance may result in property damage or personal injury.
2
1
3
WARNING
This appliance is equipped for natural or propane gas. Field
conversion is not permitted.
INDEX
NUMBER
PART
NUMBER
DESCRIPTION
1 R-7506 LOG A
2 R-7504 LOG B
3 R-7505 LOG C

30411-12-1115 Page 19
1. Place Log A between rear log support and burner pan. See image below
LOG PLACEMENT

30411-12-1115Page 20
2. Place Log B onto the two left, front pins on the burner pan.
LOG PLACEMENT
This manual suits for next models
3
Table of contents