Enviro Berkeley-Nova User manual

1PB
OWNER’S MANUAL
50-3259
WARNING: If the information in this manual is not followed exactly, a
re or explosion may result causing property damage, personal injury
or loss of life. Installation and service must be performed by a qualied
installer, service agency or the gas supplier.
Version Française: www.enviro.com/fr.html
4001609
WARRANTY REGISTRATION
enviro.com/warranty
Berkeley-Nova
FREESTANDING GAS FIREPLACE

2
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other ammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Leave the building immeadiately.
• Immeadiately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
- Installation and service must be performed by a qualied
installer, service agency or the gas supplier.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or
gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code
requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed;
only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon
monoxide detector is required in all rooms containing gas red direct vent appliances. The replace
damper must be removed or welded in the open position prior to installation of a replace insert.
Safety Precautions
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
This appliance may be installed in an after-market permanently located,
manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certied kit is used.
Only doors certied with the appliance shall be used

32
Safety Precautions
FOR SAFE INSTALLATION ANDOPERATION OF YOUR “ENVIRO” HEATER,
PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas- red appliances must be installed in
accordance with their instructions. Carefully read all the
instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for a
permit prior to commencing the installation.
• NOTE: Failure to follow these instructions could cause
a malfunction of the replace, which could result in death,
serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your
re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a quali ed
service person. The appliance should be inspected before
the rst use and, at least, annually by a quali ed service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative the control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• Due to high temperatures, the appliance should be
located out of high traf c areas and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when in
the same room as the appliance. Toddlers, young children
and others may be susceptible to accidental contact
burns. A physical barrier is required if there are at risk
individuals in the house. To restrict access to a replace
or stove install an adjustable safety gate to keep toddlers,
young children and other at risk individuals out of the
room and away from hot surfaces. Any safety screen,
guard, or barrier removed for servicing an appliance must
be replaced prior to operating the appliance.
• Clothing or other ammable materials should not be
placed on or near the appliance.
• A barrier designed to reduce the risk of burns from the
hot veiwing glass is provided with this appliance and shall
be installed for the protection of children and other at-risk
individuals. If the barrier becomes damaged, the barrier
shall be replaced with the manufacturer’s barrier for this
appliance
FOR YOUR SAFETY
• Installation and service must be performed by a quali ed
installer, service agency or gas supplier.
• This installation must conform to local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1.
• To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
•To prevent injury, if the pilot or pilot and burners
have gone out on their own, open the glass door and
wait 5 minutes to air out before attempting to re-
light the stove.
• Always keep the area around these appliances clear of
combustible material, gasoline and other ammable liquids
and vapours.
• These appliances should not be used as a drying rack for
clothing or for hanging Christmas stockings/decorations.
• Due to the paint curing on the stove, a faint odor and slight
smoking will likely be noticed when the stove is rst used.
Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another
room or inside the building. Make sure the speci ed vent
pipe is used, properly sized and of adequate height to
provide suf cient draft. Inspect the venting system annually
for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts speci cally approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or quali ed service person.
• Never use solid fuels such as wood, paper, cardboard, coal,
or any ammable liquids, etc., in this appliance.
• Do not use this appliance if any part has been under water.
Immediately call a quali ed service technician to inspect the
appliance and to replace any part of the control system or
any gas control which has been under water.
• Do not abuse the glass by striking it or slamming the door
shut.
• If the Berkeley unit is pulled out of its installation, and
the vent-air intake system is disconnected for any reason,
ensure that the vent-air intake pipes are reconnected and
re-sealed in accordance to the instructions noted in initial
inStallation - direct vent
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and shall
individuals.

4
Table of Contents
Safety Precautions........................................................................................................2
Table of Contents.........................................................................................................4
Codes And Approvals....................................................................................................5
Specications.............................................................................................................6
Dimensions.....................................................................................................6
Rating Label Location.........................................................................................6
Operating Instructions..................................................................................................7
Lighting Instructions..........................................................................................7
Pilot Light.........................................................................................................8
Air Shutter.........................................................................................................8
Remote Controls................................................................................................8
Burner Lighting.................................................................................................9
Blower Speed .................................................................................................10
Normal Sounds During Operation......................................................................10
Maintenance And Service..............................................................................................10
Routine Maintenance.......................................................................................10
Cleaning Decorative Surfaces..........................................................................10
Cleaning the Glass...........................................................................................11
Cleaning the Firebox........................................................................................11
Replacing the Glass..........................................................................................11
Flashout Guard................................................................................................11
Cast Door Removal..........................................................................................12
Glass Door Removal.........................................................................................12
Burner Removal...............................................................................................13
Fuel Conversion...............................................................................................14
Initial Installation.......................................................................................................17
Preparation for Installation...............................................................................17
Clearance to Combustibles................................................................................17
Direct Vent......................................................................................................18
Venting Clearances..........................................................................................18
Approved Venting Parts.....................................................................................19
Horizontal Termination - Minimum Vent..............................................................20
Vent Termination Restrictions............................................................................21
Allowable Vent Congurations...........................................................................22
Air Restrictor Settings......................................................................................23
Horizontal Termination.....................................................................................24
Vertical Termination ........................................................................................25
B-Vent Drafthood Adaptor (50-3229).................................................................28
Gas Line Connection and Testing.......................................................................31
Electrical Requirements ...................................................................................32
Secondary Installation................................................................................................33
Log Set Installation.........................................................................................33
Safety Screen Replacement..............................................................................36
Trouble Shooting........................................................................................................37
Parts List....................................................................................................................38
Rating Label...............................................................................................................41
Notes.............................................................................................................................42
Warranty.................................................................................................................43
Installation Data Sheet...............................................................................................44

54
DIRECT VENT ONLY: This type is identied by the sufx DV. This appliance draws all of its air for
combustion from outside the dwelling, through a specially designed vent pipe system.
This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above
sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
• This appliance has been tested by INTERTEK and found to comply with the established VENTED
GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (Berkeley; NG/LPG)
TESTED TO: ANSI Z21.88-2014/CSA 2.33-2014 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 (R2014) GAS FIRED APPLIANCES FOR HIGH ALTITUDES
CSA P.4.1-15 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This ENVIRO Berkeley Fireplace:
• Has been certied for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall
thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)
Codes And Approvals
• Must be installed in accordance with local codes. If none exist, use current
installation code CAN/CGA B149.1 in Canada or ANSI Z223.1/NFPA 54 in
the USA.
• Must be properly connected to an approved venting system and not connected
to a chimney ue serving a separate solid-fuel burning appliance.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned
on for the rst time, it should be turned onto high without the fan on
for the rst 4 hours. This will cure the paint, logs, gasket material and
other products used in the manufacturing process. It is advisable to open a
window or door, as the unit will start to smoke and can irritate some people.
After the unit has gone through the rst burn, turn the unit off including
the pilot, let the unit get cold then remove the glass door and clean it with
a good gas replace glass cleaner, available at your local ENVIRO dealer.

6
Specifications
Dimensions:
Figure 1. Berkeley Dimensions
Rating LabeL & Lighting instRuctions Location:
The rating label and lighting instructions are located on a plate hanging on the back of of the unit.
29 5/16" [75.5 cm]
4 5/8"
[11.7 cm]
30 1/4"
[76.8 cm]
31 3/8"
[79.7 cm]
22 15/16"
[58.3 cm]

76
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.
Lighting anD tuRning off instRuctions:
Figure 2. Lighting Instruction Label
4. Turn the gas control knob clockwise to the “OFF” position.
5. Close the front control panel.
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to this appliance.
4. Open the front control panel.
5. Turn off the gas control knob clockwise to the “OFF” position.
6. Open door. Wait fIve (5) minutes to clear out any gas. Close door.
Then smell for gas, including near the floor. If you smell gas, STOP!
Follow “B” in the saftey information above on this label. If you don’t
smell gas, go to the next step.
7. Find pilot-located near the center rear of the firebox. Turn the gas
control knob counter-clockwise to “PILOT”. Push the gas
control in fully and hold, keep knob depressed for about 30 seconds
after the pilot is lit. Release knob. If pilot goes out, repeat steps 4
through 5.
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life
A. This appliance has a pilot which must be lighted by hand. When
lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas.
Be sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance. Do not touch any electrical switch; do
not use any phone in your building. Immediately call your gas supplier
from a neighbor's phone. Follow the gas supplier’s instructions. If you
cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don’t try to repair it. Call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.
LIGHTING INSTRUCTIONS
WARNING: This gas valve has a lockout device, which will not allow the
pilot burner to be relit until the thermocouple has cooled.
-If the knob does not pop up when released, stop and immediately call your
service technician or gas supplier.
-If the pilot will not stay lit after several tries, turn the gas control knob
clockwise
to “OFF” and call your service technician or gas supplier.
8. Turn the gas control knob counter clockwise to the “ON” position.
Flip the burner switch to “ON” then turn the “HI/LOW” knob to the
desired setting.
9. Close the front control panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Open the front control panel and flip burner switch to “OFF” C-12454

8
1. Turn off the gas to the replace. If not recently done, remove the
glass and let the unit air out for at least ve (5) minutes to
clear out any gas. Turn on gas to the heater.
2. Start the pilot by pressing the gas control knob (Figure 5) and turning it
to PILOT. While pushing the gas control knob in, press the piezo ignitor
several times until the pilot light starts. Hold the gas control knob in for
30 seconds. Check that the pilot has fully engulfed the thermocouple
assembly (see Figure 3).
aiR shutteRs:
Behind the valve access door is the air shutter adjustment levers on the right hand side of the venturi
box (see Figure 4) above the control panel. The air shutters allow the amount of air coming into the
replace to be adjusted in order to accommodate different climates and venting arrangements. The left
shutter adjusts the rear burner and the right shutter adjusts the front burner. Start the pilot and then the
burner. Make sure the pilot ame is burning normally and none of the burner ports are plugged. Let the
replace burn for roughly fteen minutes and then examine the ames, compare the ames to Figure 47
on page 35.
The ideal ame will be blue at the base and light orange above. The ames should be of medium height.
If the ames look like this, no venturi adjustment is needed. If the ames are fairly short and mostly blue,
the replace is getting too much air. Therefore, the air shutter should be closed (pushed in) slightly until
the correct ames are achieved. Flames that are very orange, with tall, dark, stringy tips, are not getting
enough air. Open (pull out) the venturi until the ames clean up. If the shut is opened, or closed all the
way, and the correct ames cannot be attained, turn off the gas and contact the dealer.
Warning: Incorrect shutter adjustment may lead to improper combustion, which is a safety hazard.
Contact the dealer if there is any concern about the venturi adjustment.
Figure 4. Air shutter adjustment lever.
Thermopile Thermocouple
Figure 3. Pilot Flame
Operating Instructions
PiLot Light:
Remote contRoLs:
This replace can use an optional remote control or wall thermostat. If either of these are to be used
to control the replace for the majority of the time, leave the burner switch (Figure 7) in the remote/
thermostat position. Consult the instructions included with the remote/wall thermostat for operation
guidelines.
Less Air More Air
Front Burner
Rear Burner

98
The Berkeley gas valve and control panel (Figures 5 & 6) are located behind the valve access door at the
front of the stove (Figure 4). To light the burner correctly follow the steps below:
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
A) Make sure the pilot is lit (see Pilot liGHt section) .
B) Turn gas control knob COUNTER CLOCKWISE to ON.
C) Flip the burner switch, located at the top right rear of
the Berkeley, to ON (see Figure 7)
D) Turn the HI/LO knob to the desired ame height.
NOTE: Check that all burner holes are lit.
TO TURN GAS FIREPLACE OFF:
Flip switch to OFF to turn off burners only.
If the replace is to be turned off for the season, or for
servicing, turn the gas shut off valve to OFF located at the
bottom right on the backside of the Berkeley. DO NOT
FORCE IT. If the unit is going to be serviced, turn off the
electrical power to the unit as well.
NOTE: When the unit is turned on for the rst time, it
should be turned onto high, with the fan OFF, for the rst
two to four hours. This will cure the paint, logs, gasket
material, and other products used in the manufacturing
process. It is advised that a door or window be opened
as the unit will start to smoke, which can irritate some
people. After the unit has gone through the rst burn,
Figure 6. Control Panel
buRneR Lighting:
Piezo Ignitor
Fan Control
turn the unit OFF, including the pilot, and let the unit get completely cold. Then remove the glass and
clean it with a good gas replace glass cleaner, available at your local Enviro dealer. See “Maintenance
and Service; GlaSS door reMoval” and “Maintenance and Service; cleaninG tHe GlaSS.”
Figure 7. Burner Switch
Burner Switch
O
L
I
T
P
TP TH TP TH
IN OUT
H
I
L
O
N
O
F
O
F
L
I
P
T
O
Hi/Low
Knob
Gas Control
Knob
Figure 5. Gas Valve Controls

10
Operating Instructions
bLoweR sPeeD:
The blower will come on only when the replace is up to temperature (approximately 15 minutes). The
speed of the fan can be changed by turning the fan control knob. The blower will continue to operate
automatically after the unit has been shut off (approximately 25 minutes).To turn the blower off, turn
the knob COUNTER CLOCKWISE until it “clicks” off (Figure 6).
It is advisable not to operate the blower below 1/3 speed as it puts a strain on the windings of the blower
and running the blower at lower speeds could also cause premature fan failure.
noRmaL sounDs DuRing oPeRation:
Table 1: Normal Sounds
Component Sound & Reason
Berkeley Creaking when heating up or cooling down.
Burner Light pop or poof when turned off; this is more common with LP units.
Temperature Sensor Clinking when it senses to turn the blower on or off.
Pilot Flame Quiet whisper while the pilot ame in on.
Blower / Fan Air movement that increase and decreases with the speed of the blower. The
blower is pushing the heat from the replace into the room.
Gas Control Valve Dull click when turning on or off, this is the valve opening and closing.
Maintenance And Service
Routine maintenance:
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not
blocked by anything. The pilot ame should be blue with little or no yellow on the tips.
Warning: Clearances must be sufcient to allow access for maintenance and service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied agency.
cLeaning DecoRative suRfaces:
Painted, powder coated, or porcelain enameled surfaces should be wiped with a damp cloth periodically.
Never clean the face when it is hot. Do not use other cleaners as they may leave a residue, which can
become permanently etched into the surface.

1110
Maintenance And Service
cLeaning the gLass:
When the replace has cooled, remove the face of the replace along with the glass. See Maintenance
and Service - GlaSS door reMoval. Check the gasket material on the back of the glass, making sure that
it is attached and intact.
During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all
replaces. However, this condensation can allow dust and lint to cling to the glass surface. Initial paint
curing of the appliance can leave a slight lm behind the glass, a temporary problem. The glass will need
cleaning about two weeks after installation. Use a mild glass cleaner and a soft cloth. Abrasive
cleaners will damage the glass and painted surfaces. Depending on the amount of use, the glass
should require cleaning no more than two or three times a season. Do not clean the glass when it is
hot.
cLeaning the fiRebox:
Remove the logs carefully, as they are very fragile. Carefully clean any dust off the logs and remove
any lint from the burner and pilot. At this time, inspect the ceramic burner for cracking. If a problem is
suspected, contact the dealer. Check the logs for deterioration or large amounts of soot; a small amount
on the bottom side of the logs is normal. Replace the logs as shown in the Secondary inStallation - loG
Set inStallation section. If any logs are damaged, contact your nearest ENVIRO dealer.
RePLacing the gLass:
The glass in the replace is a high temperature ceramic. If the glass is damaged in any way, a factory
replacement is required (see PartS liSt). Wear gloves when handling damaged glass door assembly
to prevent personal injury. Do not operate with the glass front removed, cracked or broken. Removal
and replacement of the glass from the door must be done by a licensed or qualied service person.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
Remove the door (see page 12). The replacement glass will come with a new gasket installed. Remove
any silicone remnants from the door. Apply high temperature silicone to the two vertical faces of the
door and install the new piece of glass with gasket (be sure to maintain edge clearances). Apply even
pressure to the glass to allow the silicone to adhere to the gasket material.
fLashout guaRD:
This unit is equipped with a ashout guard that automatically stands up to serve as protection if a delayed
ignition were ever to occur. The ashout guard should always be in the down position (Figure 8) during
regular operation of the stove. If the guard is for some reason left in the up position (Figure 9) it will
effect the volume of convective air discharging from the front of the stove and must be reset to the down
position.
Guard Down Guard Up
Figure 8: Flashout Guard Down (Default) Figure 9: Flashout Guard Up

12
Maintenance And Service
cast DooR RemovaL:
Figure 11. Top latches for glass door (cast top and door removed)
Figure 12. Bottom Alignment Slot for glass door.
Door Latch Mechanisms
Alignment Slot
*Parts removed
for clarity*
In order to install the log set, and
for regular cleaning, the glass door
must be removed. The cabinet
front must rst be removed, as
outlined in the section above,
before accessing the door latches.
There are two (2) door latch
mechanisms on top the glass door
as shown in Figure 11. Each latch
can be pulled straight out and up
by hand. When the top latches are
unhooked, the door can be lifted
up out of the alignment slot at the
bottom of the rebox, shown in
Figure 12.
To replace the glass door, simply
reverse the above procedure.
Warning: Do not touch or attempt
to remove the glass door if the
replace is not completely cold.
WARNING: Never operate the
replace with the glass door
removed.
gLass DooR RemovaL:
Cast Top
Cast Door
The cast door on the Berkeley needs to be
removed whenever access to the rebox is
required. First the Berkeley must be turned
off and allowed to fully cool. Next, remove
the Cast Top as shown in Figure 10 by simply
lifting up. Lay the cat top down on a towel or
blanket to prevent scratching of the nish.
The cast door, with safety screen attached,
can now be removed be rst pulling the
bottom out then lifting up to unhook the
top. Lay the door face down on a towel or
blanket to prevent scratching of the nish.
To re-install the cast door simply reverse the
procedure.
Figure 10. Cast Door Removal

1312
Maintenance And Service
buRneR RemovaL:
The burner may need to be removed for a few reasons, including cleaning under the burner, converting
the unit to a different gas type, or to replace the burner altogether. Proceed only when the unit has
completely cooled down.
Figure 13. Removing Burner.
1. Remove the cabinet front, and glass door as outlined
in the Maintenance and Service - GlaSS door reMoval.
2. Remove the log set as shown in Secondary inStallation
- loG Set inStallaion
3. Place your hands in the air slots in the burners, as
shown in gure 14, then pull forward and lift up to
dis-engage the venturi tubes.
4. Continue to lift up and rotate the burner approx. 45
degrees, as shown in Figure 15, and remove it from
the rebox. Take care not to damage the edges of
the ceramic burner as it is fragile.
To re-install the burner follow steps 1-4 in reverse. When placing the burner back in the unit make sure
it is properly seated and up against the intake plenum at the rear of the rebox. When installed correctly
the burner will have no side to side movement.
Figure 14. Burner Removal - Correct Hand
Placement Figure 15. Burner Removal - Rotate 45 degrees

14
Conversion Kit Installation:
1. Turn control knob on the gas valve to the “OFF” position and shut the gas supply off at the shut-off
valve upstream of the unit. CAUTION: The gas supply must be shut off prior to disconnecting the
electrical power and before proceeding with the conversion. Allow the valve and unit to cool down
to room temperature.
2. Remove the glass door as shown in the Maintenance and Service - GlaSS door reMoval.
3. Carefully remove the log set.
4. Remove the burner as shown in the Maintenance and Service - Burner reMoval.
5. Convert the burner orices:
a) Remove the main burner orices with a 3/8” socket.
b) Put a bead of pipe-thread sealant or approved Teon tape on the orice threads before installing
into the brass elbow.
c) Install the new orices from the kit (Left = #56 , Right = #55).
6. Convert the pilot injector:
a) Using a 7/16” wrench, turn the pilot head a ¼ turn counter-clockwise.
b) Push the slider, with your nger or at head screwdriver.
-Natural gas is marked NAT.
-Propane gas is marked LP with an indicating hole between L and P.
c) Turn the pilot head a ¼ turn clockwise; back to its original position.
fueL conveRsion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualied service agency in accordance
with the manufacturer’s instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed
exactly, a re, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualied service agency is responsible for
the proper installation of this kit. The installation is not proper or complete until the
operation of the converted appliance is checked as specied in the manufacturer’s
instructions supplied with the kit.
Kit Parts List for all Berkeley-Nova models:
2 - Orice (NG: #45 & #44) or (LP: 2 x #55 , 1 x #56)
1 - Installation instruction sheet
1 - Conversion label
Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are
missing, contact your dealer, distributor or courier company to have them replaced before starting this
installation.
Maintenance And Service

1514
Maintenance And Service
7. Convert the SIT gas valve:
a) Remove the black protection cap from the HI/LO knob by hand shown in Figure 16.
b) Insert a 5/32” or 4 mm Allen wrench into the hexagonal key-way of the screw (see Figure 17), rotate
it counter-clockwise until it is free and extract it.
c) Check that the screw is clean and if necessary remove dirt.
d) Flip the screw (refer to Figure 18).
e) Using the Allen wrench as shown in Figure 17, rotate the screw clockwise until a torque of 9 inch lbs.
WARNING! Do not over tighten the screw. It is recommended that you grip the wrench by the short
side.
f) Verify that if the conversion is from NG to LPG, the screw must be re-assembled with the red o-ring
visible (refer to Figure 19). If the conversion is from LPG to NG, the red o-ring of the screw must be
not visible.
g) Re-attach the black protection cap that was removed in step a (Figure 16).
Loosen
Tighten
Figure 17: Removing valve
screw.
Figure 16: Removing
valve cap.
Figure 18: Flip valve
screw.
Red o-ring
is not visible
Red o-ring
is visible
LPG Configuration
Figure 19: O-ring on valve screw.

16
Maintenance And Service
Figure 20: Pilot assembly
beside the burner.
8. Reinstall the burner, re grate, log set, and glass door. Also refer to Secondary inStallation - loG Set
inStallation in your Owner’s Manual. When re-installing the burner, ensure that the burner to pilot
hood and shield relationship is similar to what is shown in Figure 20.
9. Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the
unit.
10. Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap
and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by
using an approved pipe thread sealant or approved Teon tape. NEVER USE AN OPEN FLAME WHEN
TESTING FOR LEAKS.
11. Reconnect the electrical power to the unit.
12. Relight the pilot and conrm the ame
properly covers both the thermocouple
and thermopile (see Figure 3, page 8).
Should the pilot require adjustment,
turn the adjustment screw (gure 38,
page 31) clockwise to decrease or
counterclockwise to increase until the
correct ame is achieved.
13. Relight the main burner in both the
“HI” and “LO” positions to verify
proper burner ignition, operation
and proper ame appearance (gure
47, page 35). Conrm the inlet and
manifold pressures are within the
acceptable ranges as directed in
section intial intallation - GaS line
connection and teStinG. If the Berkeley has been installed at an altitude higher than 2000ft
(610m) it is required to de-rate the unit accordingly and use the supplied #56 orice on
the left (LP only):
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
14. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the unit
has been converted to a different fuel type.

1716
Initial Installation
QUALIFIED INSTALLERS ONLY
intRoDuction:
This section of the owner’s manual is for the use of qualied technicians only. Fireplace placement,
hearths, and venting terminations will be covered, as well as the gas and electrical systems. There are
several installation safety guidelines that must be adhered to. Please carefully read the safety precautions
at the front of this manual.
PRePaRation foR instaLLation:
• Remove the packaging from the appliance, and check to make sure there is no damage. If damage is
found, please report it to both the carrier and your dealer as soon as possible.
• Before beginning, carefully check the glass door and the log set
• Locate a position where the ue system of the stove can be properly installed without damaging the
integrity of the building; e.g. cutting a wall or ceiling joist.
• Check stove and ue system clearance requirements.
• Locate the stove where it can be accessed by a gas supply line.
• Locate the stove in a large and open room that is centrally located in the house. This will optimize heat
circulation and comfort.
• As the Berkeley is equipped with a convection fan, ensure that an electrical outlet is within 6 ft (1.8 m)
of the stove.
• The ow of combustion and ventilation air must not be obstructed.
B
A
Front
Back Wall
Side Wall
C
C
Front
Adjancent Wall
Adjacent Wall
A. Sidewall to unit 12” (30.5 cm)
B. Backwall to unit 5.0” (12.7 cm)
C. Corner to unit 7.43 (18.9 cm)
D. Ceiling to unit 27.5” (69.8 cm)
E. Floor (hard wood & linoleum) 0”
Note: When installing on a carpeted
surface a hearth pad must be used.
minimum aLcove Dimensions:
Width 52.0” (132.1 cm)
Height 57.25” (145.4 cm)
Depth (Max.) 42” (106.68 cm)
D
A
Ceiling
Side Wall
Warning: Clearances must be sufcient
to allow access for maintenance and
service.
cLeaRance to combustibLes:
Figure 21: Clearance to Combustibles
Figure 22: Clearance to Combustibles

18
Initial Installation
QUALIFIED INSTALLERS ONLY
venting cLeaRances:
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a
horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 1½” (38 mm) on the
sides and bottom. When combustible materials are directly above a 90° elbow, 3” (76 mm) of clearance
are necessary.
Table 2. Vent Pipe Minimum Clearances.
Vertical Pipe to
the Side Walls
Horizontal Pipe to
the Sides & Bottom
Above an Elbow
Above the Unit
Above an Elbow
Not Above the Unit
Above Horizontal
Vent Pipe
Wall Frame 8”
(203mm) or less
Hard
Pipe 1”
(25.4 mm)
1½”
(38.1 mm)
3”
(76.2 mm)
3”
(76.2 mm)
2”
(51 mm)
10”x10”
(25x25cm)
A 10” (254 mm) x 10” (254 mm) frame (see Figure 23) will assure the proper support and spacing for
the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used for
passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.
Framing
Joists/Studs
10”
10”
The conguration of the venting pipes depends on the locations
of walls, ceilings, and studs. However, the pipes cannot be of
arbitrary length and arrangement. Because the length of the
vertical and horizontal sections dramatically affects the burning
efciency of the replace, certain guidelines have been set in
initial inStallation - allowaBle vent confiGurationS. Venting
terminals can not be recessed into a wall or siding.
WARNING: This gas appliance must not be connected
to a chimney ue serving a separate solid-burning
appliances.
Figure 23. Vent Framing For Wall or Ceiling.
DiRect vent:
WARNING: This appliance has been designed to draw room air for proper heat circulation
from the bottom of the unit, and out the top front. Blocking or modifying these openings in
any way can create hazardous situations.
The vent length for the Berkeley must be between 36” (91 cm) and 44ft (13.4 m). This model is vented
with co-axial 4” intake, 6 5/8” exhaust aluminum or stainless steel approved rigid vent leading into a vertical
or horizontal termination cap. The ue collar of this model will t inside of a standard 4” x 6 5/8” vent and
must be either correctly interlocked or fastened, with three screws directly to the vent.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been properly
sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must be installed
in the correct location on top of the Berkeley.

1918
Initial Installation
QUALIFIED INSTALLERS ONLY
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a DirectVent Pro starting
collar in conjunction with EXCELDirect venting systems. Use of this system with the DirectVent Pro starting
collar is deemed acceptable and does not affect the Intertek listing of the appliance.
Table 4: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
DirectVent Pro EXCELDirect Description
46DVA-06 DL6 6” Pipe Length
46DVA-09 DL9 9” Pipe Length
46DVA-12 DL1 12” Pipe Length
46DVA-18 18” Pipe Length
46DVA-24 DL2 24” Pipe Length
46DVA-36 DL3 36” Pipe Length
46DVA-48 DL4 48” Pipe Length
46DVA-60 60” Pipe Length
DLA30 16 1/2” - 29”, Adjustable
46DVA-24TA 17” - 24”, Adjustable
46DVA-E45 4DE45 45° elbow
46DVA-E90 4DE90 90° elbow
46DVA-VSS VSS Vinyl siding standoff/sheild
46DVA-WT 4WT Wall thimble
46DVA-SC SC Storm collar
46DVA-WFS 4CS Fire stop
46DVA-WS WS Wall strap/support/band
46DVA-F6 4FA Flashing, 0/12 to 7/12 roof pitch
46DVA-F7 4FB Flashing, 8/12 to 12/12 roof pitch
46DVA-FF 4F Flat ashing
46DVA-VCH SVT High wind vertical termination
46DVA-HC HT High wind horizontal termination
46DVA-KHC 4HTK Horizontal termination kit
46DVA-KCA Chimney Conversion Kit A (USA Only)
46DVA-KCA Chimney Conversion Kit B (USA Only)
46DVA-KCA Chimney Conversion Kit C (USA Only)
The Berkeley replace has been tested and certied for use with M&G DuraVent DirectVent Pro and ICC
EXCELDirect venting systems. Refer to the table below for part numbers of commonly used parts for both
venting systems. For more venting parts please visit the respective manufacturers’ website.
WARNING: Do not mix parts from different vent manufacturers’ systems.
aPPRoveD venting PaRts:
Table 3: Approved Vent Manufacturers
Manufacturer Trade Name Nominal Sizes
ICC EXCELDirect 4” - 6 5/8”
M&G DuraVent DirectVent Pro 4” - 6 5/8”

20
Initial Installation
QUALIFIED INSTALLERS ONLY
hoRizontaL teRmination - minimum vent Length:
Refer to the gure for below for the minimum allowable venting setup for the Berkeley. A termination
guard (50-3266) is required when the termination is within 7’ (2.13m) of grade.
Figure 24. Minimum Vent Length
Approved horizontal termination
Approved through
wall thimble
24” (61 cm)
Minimum
Length
12” (30.5cm)
Maximum Length
Termination
Guard*
(50-3266)
*Only required when within
7’ (2.13m) of grade
5” (12.7cm)
Minimum Clearance
Exterior Wall
52” (132cm)
Minimum
Length
Table of contents
Other Enviro Gas Fireplace manuals