NI 9467 Operating Instructions and Specifications 4 ni.com
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as Ex nA IIC T4 equipment
under DEMKO Certificate No. 07 ATEX 0626664X. Each module
is marked II 3G and is suitable for use in Zone 2 hazardous
locations, in ambient temperatures of –40 °C ≤Ta ≤70 °C. If you
are using the NI 9467 in Gas Group IIC hazardous locations, you
must use the device in an NI chassis that has been evaluated as
Ex nC IIC T4, EEx nC IIC T4, Ex nA IIC T4, or Ex nL IIC T4
equipment.
Electromagnetic Compatibility Guidelines
This product was tested and complies with the regulatory
requirements and limits for electromagnetic compatibility (EMC)
stated in the product specifications. These requirements and limits
provide reasonable protection against harmful interference when
the product is operated in the intended operational electromagnetic
environment.
This product is intended for use in industrial locations. However,
harmful interference may occur in some installations, when the
product is connected to a peripheral device or test object, or if the
product is used in residential or commercial areas. To minimize
interference with radio and television reception and prevent