7
Description
Input terminals
1(+)signalloop(4…20mA)
2(-)signalloop
3Not used, can be used as a spare terminal
Voltagedropin4..20mAinputloopismax4.8V.This
corresponds 240ohmloopresistance.Whenalarms
areused(optional)voltagedropismax7.3V.Inputis
securedforreversedpolarityandovercurrenttolerance
is 100 mA.
Alarm connections, only with model 202
4,5 Lowlevelalarm,displayis lowerthanalarmlevel
6,7Highlevelalarm,displayishigherthanalarmlevel
Solid state realays,SSR: max. 250 V ±DC/AC,
150 mA, 12 ohm. Isolation between input loop 4 kV.
Alarms can be taken into use by removing jumper
inside the case. Voltage drop will increase to 7,3 V.
Measuring mode
Thisisnormaloperatingmode.Scaledinputsignalis
in display. LED indicators functions are:
A1 = Low level indicator
A2 = High level indicator
Conf = Unit in configuration or calibration mode
Measuring mode can be changed to Configuration
modebypressingsimutaneously▲★-keys.IfAccess
code is used it must be entered when display shows
Code, enter selected button combination.
Configuration mode
Undo, Save ➤➤
➤➤
➤
Exit from configuration mode. SAVE saves new
configurationandUndo exitswithoutsaving.
AL L, AL H ➤➤
➤➤
➤
Alarmlevels(L=low,H=high).Bothalarmscannotbe
energizedatthesametime.Thereforelowlevelcannot
havehighervaluethanhighalarmandviceversa.
Ifinputsignalisunder3mArelayswillbede-energized.
(Normalopen'NO'relaysneedsenergytobeclosed).
ALHy ➤➤
➤➤
➤
Alarmhysteresisisnumberofdigitsbelowandabove
selected alarm level (both sides have same value).
Normallyalarmrelaysareenegizedwhendisplayvalue
goestoalarmlevelandde-energizedwhenitgoesover
hysteresisvalue.
Alarms can also have manual reset when hysteresis
value is set larger than measuring range (full span).
Manual reset is done with ▼-key from front panel.
An example of Manual reset / hold function:
High level alarm is 100 °C and low level -5 °C. When
inputis over100°C,LED A2lits(relay A2energized)
anditdon'tgooffeveniftheinputgoesbelow100°C.
It must be resetted manually with front panel key ▼.
Alarmwillberesettedalsoifinputgoesbelowselected
lowlevel(-5°C).Thatisbecausebothrelayscannotbe
energizedatthesametime.IfYoudonotwanttouse
this bossibility given by the other alarm, select it's
value larger that the scaled range (not in use).
Alarmsoff
Negativehysteresisvaluedisablesalarmfunction.
Dec ➤➤
➤➤
➤
Decimal selection 0..3, i.e. 0.9, 0.99 or 0.999
Lo, Hi ➤➤
➤➤
➤
Lo andHi scalesdisplaytoinput signal 4..20 mA. Lo
valueisselectedforinput4mAandcorrespondinglyHi
value is for 20 mA input.
e.g. 4..20 mA = display Lo -100.. Hi +200
Filt➤➤
➤➤
➤
Display Filter. This fucntion stabiles display value
whenwidemeasuringrangeisused.
Filtervaluecanbesetbetween1(min)..0.010(max).
1.000 = no filter
0.200=normal filter
e.g. 0.2 =(1/5) one new measurement and 4 old
values or
0.1 = (1/10) one new + 9 old values (slower)
Alarms are controlled with the filtered value (filter
affects to alarms reaction time).
Inte ➤➤
➤➤
➤
Display intesity (brightness). You can change the
intensity with ▲▼-buttons. Hold ▼-key to decrease
intensityandviceversa.
Inmeasuringmodeintensitydecreasesautomatically
when input is under 6 mA.
TrF ➤➤
➤➤
➤
Transferfunctionselection.
Lin= normal fnction
Sqrt= square root function
Squarerootfunctionenablesevennegativeinput.This
is usefull in cases where e.g. flow goes backwards.
CFCo ➤➤
➤➤
➤
Access code for configuration mode. Access code is
formed with ▲▼★➤-keys. Code is formed with six
pushesoffrontpanelbuttons.Notinusewhencodeis
set to (★★★★★★) (factory default).
Ifconfigurationaccesscodeisforgotten,allthesettings
canbereturnedtofactorydefaults(notcalibration)by
holdingdownbuttons★and➤whileconnectinginput
signal 4..20 mA.