© 2018 nVent 89056971
- 4 -
INSTALLATION INSTRUCTION
1. Inspect air conditioner
2. Slide rails must be used to support rear portion of the air conditioner. For rail location dimensions
and mounting opening cutout dimensions, refer to on page 5. NOTE: The air conditioner
must be mounted level +/- 1° in all directions to ensure proper drainage of condensate from the
condensate evaporator.
3. Seal around the enclosure cutout openings with the adhesive-backed gasket tape shipped with the
air conditioner. The gasket may be applied to either the enclosure or the air condition.
4. Remove and discard plastic plug from outlet of condensate drain tube. The drain tube must
be routed to the exterior of the enclosure. NOTE: Be sure that no portion of the drain system is
submerged or elevated above the exit point of the air conditioner. Also, the external drain line
MUST NOT form a trap at any point in the line. A trap is formed when the end of the drain tube is
submerged in a collection bucket, or when any portion of the drain line rises above the level of
another portion of the drain line. This is true even if the rise in the line is below the level of the exit
point of the air conditioner. It is recommended that the drain line slope downward continuously
from the exit of the air conditioner at a minimum rate 1° per foot of linear run.
5. Mount air conditioner in enclosure and allow to remain in upright position for at least ve minutes
before starting.
6. Refer to the nameplate for electrical current requirements. Connect the power cord to a properly
grounded power supply.
7. Unit may be equipped with an optional automatic temperature controller that is preset at the
factory for your convenience and should not require adjustment. If adjustment is required for
operation, refer to Components List on page 3.
DIMENSION DRAWING
CONDENSATE
OVERFLOW
EXHAUST AIR
FLOW
AMBIENT
AIR OUT
COOL AIR
OUT
AMBIENT
AIR IN
ENCLOSUIRE
AIR IN
TOP VIEW
DETAIL “A”
SEE DETAIL “A”
FRONT VIEW
SIDE VIEW
BOTTOM VIEW
SERVICE CORD 6
FOOT STANDARD INCLUDING
.125 INCH
SCREW
HEADS
MAINTENANCE
The LOBOY 14 series air conditioner is designed to be maintenance free, with the exception of the condenser
air inlet lter. To ensure reliable continuous operation, the inlet lter inside the front of the LOBOY 14 should be
removed and cleaned or replaced periodically.
Clean by flushing the lter with warm water and allow it to dry thoroughly. Recoat the lter with RP Super Filter
Coat adhesive or the equivalent. Reinstall cleaned or new lter.
CUTOUT DIMENSIONS
Cutout Notes:
1. Entire weitht of air conditioner is not
intended to be supported by the
mounting anges. Slide rails should be
provided.
2. Cutout dimensions for standard
product only.