All inputs and outputs
on I/O Modules provide
field isolaon.
Please wire accordingly.
TYPE POWER CONSUMPTION
RADIO 35 mA @ 12 Vdc AVG (10% Duty Cycle)
DIGITAL 26 mA @ 12 Vdc MAX
4-20 mA 83 mA @ 12 Vdc MAX
0-10 V 58 mA @ 12 Vdc MAX
Always disconnect power
when aaching or detaching
I/O Module(s) to or from
DataRail to avoid damage.
2. Power Consumpon
1. Isolaon vs Non-Isolaon
If isolaon is required, then separate
power sources are required for
Radio Module and I/O Module(s).
If isolaon is not required, a jumper
is required to make common with
Radio Module’s power supply to
to one of I/O Module’s COM pin.
+-
9-30 V
Jumper required if using
a single power source.
©2019 OleumTech Corporaon. OleumTech and WIO are registered trademarks of OleumTech Corporaon. Other trademarks are the property of their respecve owners.
Specificaons, design, and product descripons subject to change without noce. Doc ID: AD-1089-001_A
WIO® System Wiring Diagrams for Radio Kit RM1K
A P PL I C A TI O N D R A W I NG