7
2.7- INSTALLATION OF ACCESSORIES
WARNING
Electrical shock hazard.
Turn OFF electrical power at the fuse box or service panel
before making any electrical connection and ensure that a
proper ground connection is made before connecting line
voltage.
Failure to do so can result in death or bodily injury.
2.7.1- Humidifier and electronic air cleaner
This unit is equipped with a 120 VAC terminal for the connection
of accessories up to a maximum of 2 amps. A humidifier and an
electronic air cleaner can be wired to terminals L1 and N of the
unit. Refer to the wiring diagrams in this manual (Figure 12 and
Figure 13). A field supplied 24 VAC transformer can be installed
for accessories using 24 VAC. A separate power source must
be used if the accessories draw more than 2 amps.
Some accessories require control relays. A location has been
set aside in the unit for the installation of relays: a 24 VAC (part
number OFE-L01H009). In addition, a 24 VAC relay can be
wired between terminals W1 and C to be activated during a call
for heat. Refer to the wiring diagrams for the location of the relay
RACC on the control panel and in accessory instructions.
2.7.2- Use of a heat pump
When using a heat pump, a thermostat with dual fuel option or
a fossil fuel kit is required that prevents the operation of the
electric elements and the heat pump at the same time. Refer to
the instructions provided with the thermostat or the “Fossil Fuel
kit”for the proper wiring of the furnace and the heat pump.
The simultaneous operation of the electric elements and the
heat pump will cause overheating of either unit. The safety
controls of the appliances will shut down the elements or heat
pump, since they are not designed to function in this fashion.
3-OPERATION
3.1- START-UP
Before starting up the unit, be sure to check that the following
items are in compliance:
1. The electrical installation and ventilation are conform;
2. The blower access door is in place and the blower rail
locking screws are well tightened;
3. The blower speed adjustments for heating and air
conditioning are appropriate and according to the
specifications in this manual;
4. The thermostat of the room is in heating mode and is set
higher than the ambient temperature.
5. The breakers on front panel are set on the “ON” position
To start the unit, turn the main electrical switch on.
3.2- USE OF MANUAL FURNACE CONTROLS ON
ADVANTAGE FURNACE
When there is a demand for heat, the pilot light (L-1) comes on.
Refer to the wiring diagram.
When the “HI/LO” switch is put into the “LO” position, it will shut
down approximately half the elements.
However, it is important to put the switch back to the “HI”
position during the winter months to ensure adequate
heating.
Also, this switch must remain in the “HI” position when a 2-stage
or outdoor thermostat is used to control the electric elements of
the second stage. Refer to the diagram in Section 2.5-.
The “ON/OFF VENT/FAN” switch engages the blower in the
continuous low speed mode. This will filter the air and provide
for better air distribution in the building.
The 15 A circuit breaker is there to protect the motor and the
control circuit conductors. If the unit does not function, press the
circuit breaker button to see if it may have disengaged due to a
power surge. If the breaker has to be pressed again, the unit
must be checked by a qualified service technician.
Figure 10 : Advantage furnace controls
3.3- OPERATING SEQUENCE
3.3.1- Heating mode
1. The thermostat closes the R-W1 circuit (24 VAC), thereby
sending a 24 VAC signal to the blower relay and the
sequencer board. The board will then activate all the first
stage relays with a delay of 3 seconds between each
element. The motor relay will be activated, which will start
the blower on the first stage heating speed.
2. The thermostat closes the R-W2 circuit (24 VAC), thereby
sending a 24 VAC signal to the blower relay and the
sequencer board. The board will then activate all the first
and second stage relays with a delay of 3 seconds between
each element. The motor relay will be activated, which will
start the blower on the second stage maximum heating
speed.