Pacific Power Source ASX series User manual

ASX SERIES
AC POWER SOURCE
OPERATION
MANUAL
PACIFIC
POWER SOURCE
<
Schulz-Electronic GmbH
Dr.-Rudolf-Eberle-Straße 2
D-76534 Baden-Baden
Fon +49.7223.9636.30
Fax +49.7223.9636.90
vertrieb@schulz-electronic.de
www.schulz-electronic.de
Advanced Test Equipment Rentals
www.atecorp.com 800-404-ATEC (2832)
®
E
s
t
a
b
l
i
s
h
e
d
1
9
8
1


ASX-SERIES
OPERATION MANUAL
FOR THE
MODELS
115-ASX, 120-ASX
140-ASX, 160-ASX
315-ASX, 320-ASX
345-ASX, 360-ASX
3120-ASX
PPS PART NO. 140050
THIS MANUAL ASSIGNED TO MODEL:
S/N:
THE INFORMATION CONTAINED
IN THIS MANUAL IS PROPRIETARY TO
PACIFIC POWER SOURCE.
AND MAY NOT BE COPIED OR REPRINTED
WITHOUT ITS EXPRESSED WRITTEN CONSENT.
PACIFIC POWER SOURCE, INC.
17692 Fitch Irvine, CA 92614
FIFTH EDITION
COPYRIGHT (C) PPS MARCH, 2010

CERTIFICATION
PACIFIC POWER SOURCE CERTIFIES THAT THIS INSTRUMENT WAS
THOROUGHLY TESTED AND INSPECTED AND FOUND TO MEET OR
EXCEED ITS PUBLISHED SPECIFICATIONS WHEN IT WAS SHIPPED
FROM THE FACTORY.
LIMITED WARRANTY
Pacific Power Source (PPS) warrants each unit to be free from defects in
material and workmanship. For the period of two (2) years from the date of
shipment to the purchaser, PPS will either repair or replace, at its sole
discretion, any unit returned to its factory in Irvine, California. This warranty
does not cover batteries. It does not cover damage arising from misuse of the
unit or attempted field modifications or repairs. This warranty specifically
excludes damage to other equipment connected to this unit.
Upon notice from the purchaser within (30) days of shipment of units found to
be defective in material or workmanship, PPS will pay all shipping charges for
the repair or replacement. If notice is received more than thirty (30) days from
shipment, all shipping charges shall be paid by the purchaser. Units returned
on debit memos will not be accepted and will be returned without repair.
This warranty is exclusive of all other warranties, express or implied.

TABLE OF CONTENTS
PAGE
i
1 GENERAL............................................................................................................................................1
1.1 USING THIS MANUAL.................................................................................................................1
1.2 SAFETY NOTICES.......................................................................................................................2
1.3 GENERAL PRODUCT DESCRIPTION ........................................................................................4
2 SPECIFICATIONS ...............................................................................................................................7
2.1 ELECTRICAL SPECIFICATIONS ................................................................................................7
2.1.1 INPUT POWER REQUIREMENTS.......................................................................................7
2.1.2 OUTPUT POWER...............................................................................................................12
2.1.3 OUTPUT POWER FACTOR...............................................................................................22
2.1.4 OUTPUT FREQUENCY......................................................................................................22
2.1.5 OUTPUT DISTORTION ......................................................................................................22
2.1.6 OUTPUT LOAD REGULATION..........................................................................................22
2.1.7 INPUT LINE REGULATION................................................................................................22
2.1.8 OUTPUT BANDWIDTH ......................................................................................................23
2.1.9 LOAD TRANSIENT RESPONSE........................................................................................23
2.1.10 OUTPUT DC OFFSET .........................................................................................................23
2.1.11 OUTPUT PROTECTION ......................................................................................................23
2.1.12 OUTPUT CONTROL CHARACTERISTICS.........................................................................23
2.1.13 OUTPUT ISOLATION ..........................................................................................................23
2.2 MECHANICAL SPECIFICATIONS.............................................................................................24
2.2.1 DIMENSIONS......................................................................................................................24
2.2.2 INPUT POWER CONNECTION..........................................................................................27
2.2.3 OUTPUT POWER CONNECTION......................................................................................33
2.2.4 CHASSIS SLIDE MOUNTS................................................................................................33
2.3 ENVIRONMENTAL SPECIFICATIONS......................................................................................33
2.3.1 TEMPERATURE RANGE...................................................................................................33
2.3.2 COOLING............................................................................................................................33
2.3.3 THERMAL PROTECTION..................................................................................................33
3 INSTALLATION..................................................................................................................................34
3.1 CHASSIS PLACEMENT...............................................................................................................34
3.2 OUTPUT VOLTAGE RANGE CONFIGURATIONS ......................................................................36
3.2.1 OUTPUT VOLTAGE RANGE CONFIGURATION, MODEL 115-ASX ..................................37
3.2.2 OUTPUT VOLTAGE RANGE, MODELS 120-ASX AND 320-ASX.......................................39
3.2.3 OUTPUT VOLTAGE RANGE CONFIGURATION, MODEL 315-ASX ..................................39
3.2.4 OUTPUT VOLTAGE RANGE CONFIGURATION, MODELS 140-ASX, 160-ASX, 345-ASX,
AND 360-ASX......................................................................................................................41
3.2.5 OUTPUT VOLTAGE RANGE CONFIGURATION, MODEL 3120-ASX ................................43
3.3 INPUT POWER CONNECTION...................................................................................................45
3.3.1 INPUT VOLTAGE CONFIGURATION, MODEL 115-ASX....................................................45
3.3.2 INPUT VOLTAGE CONFIGURATION, MODELS 120-ASX AND 320-ASX..........................47
3.3.3 INPUT VOLTAGE CONFIGURATION, MODEL 315-ASX....................................................49
3.3.5 INPUT VOLTAGE CONFIGURATION, MODEL 3120-ASX..................................................53
3.3.6 INPUT POWER WIRING REQUIREMENTS.........................................................................55
3.4 OUTPUT POWER CONNECTION...............................................................................................57
3.4.1 SINGLE PHASE OUTPUT...................................................................................................57
3.4.2 SPLIT PHASE OUTPUT......................................................................................................60
3.4.3 THREE PHASE OUTPUT....................................................................................................63
3.4.4 TRANSFORMER OUTPUTS - SPECIAL CONSIDERATIONS.............................................66

TABLE OF CONTENTS
PAGE
ii
3.5 CONNECTION OF SYSTEM CONTROL UNIT (SCU)..................................................................67
3.6 REMOTE INTERFACE ................................................................................................................69
3.7 AUX I/O INSTALLATION.............................................................................................................69
3.8 EXTERNAL SENSE CONNECTION ............................................................................................70
4 OPERATION.......................................................................................................................................73
4.1 FRONT PANEL CONTROLS.......................................................................................................73
4.2 INITIAL POWER-UP....................................................................................................................75
4.3 ROUTINE POWER-UP ................................................................................................................76
4.4 SYSTEM TURN-OFF ...................................................................................................................77
4.5 SYSTEM SHUTDOWN ................................................................................................................77
4.5.1 SHUTDOWN CONDITIONS......................................................................................................77
4.5.2 RESETTING SHUTDOWN FAULTS.........................................................................................78
4.6 OUTPUT VOLTAGE FORMS.......................................................................................................78
4.6.1 SYSTEM ARCHITECTURE......................................................................................................79
5 MAINTENANCE..................................................................................................................................81
5.1 MAINTENANCE INTERVAL........................................................................................................81
5.2 MAINTENANCE REQUIREMENTS .............................................................................................81
5.2.1 MODELS 115, 120, 315, AND 320-ASX...............................................................................81
5.2.2 MODELS 140, 160, 345, 360, AND 3120-ASX.....................................................................81
6 CALIBRATION....................................................................................................................................82
6.1 CALIBRATION INTERVAL..........................................................................................................82
6.2 TEST EQUIPMENT REQUIREMENTS ........................................................................................82
6.3.1 CALIBRATE CONTROLLER..............................................................................................83
6.3.2 POWER SOURCE LOAD TEST.........................................................................................84
7 SERVICE............................................................................................................................................85
7.1 SERVICE PROCEDURE.............................................................................................................85
7.2 ROSTER OF SYSTEM LEVEL FACTORY PART NUMBERS ..................................................85
7.3 SUB-ASSEMBLY AND CHASSIS COMPONENT PART NUMBERS.......................................86
7.3.1 FACTORY PART NUMBERS, MODEL 115-ASX (PART NUMBER 143139) ...................86
7.3.2 FACTORY PART NUMBERS, MODEL 120-ASX (PART NUMBER 143148) ...................86
7.3.3 FACTORY PART NUMBERS, MODEL 140-ASX (PART NUMBER 143013) ...................87
7.3.4 FACTORY PART NUMBERS, MODEL 160-ASX (PART NUMBER 143014)......................87
7.3.5 FACTORY PART NUMBERS, MODEL 315-ASX (PART NUMBER 143145) ...................88
7.3.7 FACTORY PART NUMBERS, MODEL 345-ASX (PART NUMBER 143016) ...................89
7.3.8 FACTORY PART NUMBERS, MODEL 360-ASX (PART NUMBER 143017)......................89
7.3.9 FACTORY PART NUMBERS, MODEL 3120-ASX (PART NUMBER 143008)....................90
INDEX .........................................................................................................................................................91
9 MODIFICATIONS AND CHANGE NOTICES ......................................................................................93

LIST OF ILLUSTRATIONS
PAGE
iii
FIGURE1.3 ASX-SERIES POWER SOURCE - FRONT VIEW.......................................................6
FIGURE 2.1.2 (A) MODEL 115-ASX OUTPUT DERATING CURVES ................................................... 13
FIGURE 2.1.2 (B) MODEL 120-ASX OUTPUT DERATING CURVES.................................................... 14
FIGURE 2.1.2 (C) MODEL 140-ASX OUTPUT DERATING CURVES ................................................... 15
FIGURE 2.1.2 (D) MODEL 160-ASX OUTPUT DERATING CURVES ................................................... 16
FIGURE 2.1.2 (E) MODEL 315-ASX OUTPUT DERATING CURVES....................................................17
FIGURE 2.1.2 (F) MODEL 320-ASX OUTPUT DERATING CURVES....................................................18
FIGURE 2.1.2 (G) MODEL 345-ASX OUTPUT DERATING CURVES...................................................19
FIGURE 2.1.2 (H) MODEL 360-ASX OUTPUT DERATING CURVES ................................................... 20
FIGURE 2.1.2 (I) MODEL 3120-ASX OUTPUT DERATING CURVES................................................. 21
FIGURE 2.2.1 OUTLINE DRAWING, MODELS 115, 120, 315, & 320-ASX ....................................28
FIGURE 2.2.2 OUTLINE DRAWING, MODELS 140,160,345,360-ASX ...........................................29
FIGURE 2.2.3 OUTLINE DRAWING, MODEL 3120-ASX .................................................................30
FIGURE 2.2.4 OUTLINE DRAWING, MODELS 140,160,345 & 360-ASX MAGNETICS MODULE .31
FIGURE 2.2.5 OUTLINE DRAWING, MODEL 3120-ASX MAGNETICS MODULE ..........................32
FIGURE 3.2.1 MODEL 115-ASX OUTPUT VOLTAGE RANGE CONFIGURATION..........................38
FIGURE 3.2.2 MODEL 315-ASX OUTPUT VOLTAGE RANGE CONFIGURATION ..........................40
FIGURE 3.2.3 MODELS 140, 160, 345, & 360-ASX OUTPUT VOLTAGE RANGE
CONFIGURATION……………………………..…..………………..……….……………….42
FIGURE 3.2.4 MODEL 3120-ASX OUTPUT VOLTAGE RANGE CONFIGURATION.........................44
FIGURE 3.3.1 MODEL 115-ASX INPUT VOLTAGE CONFIGURATION.............................................46
FIGURE 3.3.2 MODELS 120-ASX AND 320-ASX INPUT VOLTAGE CONFIGURATION..................48
FIGURE 3.3.3 MODEL 315-ASX INPUT VOLTAGE CONFIGURATION............................................50
FIGURE 3.3.4 MODELS 140, 160, 345, AND 360-ASX INPUT VOLTAGE CONFIGURATION.......... 52
FIGURE 3.3.5 MODEL 3120-ASX INPUT VOLTAGE CONFIGURATION...........................................54
FIGURE 3.3.6 3120-ASX INPUT WIRING DIAGRAM..........................................................................56
FIGURE 3.4.1.1 MODELS 115,120,140,160,315,320,345, & 360-ASX SINGLE PHASE OUTPUT
CONNECTION..............................................................................................................58
FIGURE 3.4.1.2 3120-ASX SINGLE PHASE OUTPUT CONNECTION..................................................59
FIGURE 3.4.2.1 SPLIT PHASE OUTPUT CONNECTION.......................................................................61
FIGURE 3.4.2.2 SPLIT PHASE OUTPUT CONNECTION.......................................................................62
FIGURE 3.4.3.1 THREE PHASE OUTPUT CONNECTION ....................................................................64
FIGURE 3.4.3.2 THREE PHASE OUTPUT CONNECTION ....................................................................65
FIGURE 3.5.1 SCU CONNECTION...................................................................................................... 68
FIGURE 3.8.1 MODELS 115, 120, 140, 160, 315, 320, 345, & 360-ASX EXTERNAL SENSE
CONNECTION...............................................................................................................71
FIGURE 3.8.2 MODEL 3120-ASX EXTERNAL SENSE CONNECTION...............................................72
FIGURE 4.1 FRONT PANEL CONTROLS .........................................................................................74
FIGURE 4.6.1 ASX-SERIES SYSTEM ARCHITECTURE .....................................................................80


1
SECTION 1
GENERAL
1 GENERAL
This manual provides information required to use an ASX-Series AC Power Source. Operation
of the ASX series models: 115-ASX, 120-ASX, 140-ASX, 160-ASX, 315-ASX, 320-ASX,
345-ASX, 360-ASX, and 3120-ASX is described in this document. This is a general Operations
Manual. Installation, operation, and calibration are the subjects covered.
The ASX products are typically configured with a modular controller. This allows for the creation
of systems with various control characteristics and specifications. For detailed control
description and control and metering specifications, see the UPC controller manual supplied with
the unit.
1.1 USING THIS MANUAL
This manual provides instructions for installation and use of the ASX-Series Power Source
equipment. For this reason, it is very important that the user reads sections 1 GENERAL
information, 3 INSTALLATION, and 4 OPERATION, prior to using this equipment. A thorough
understanding of these sections is required to safely and properly operate this equipment.
Section 2 lists the specifications of the equipment. Knowledge of this information is required to
gain maximum use of this equipment for a given application. The user is encouraged to read this
section in order to gain a deeper understanding of the capabilities of the ASX-Series Power
Source.
Sections 5 and 6 list MAINTENANCE and CALIBRATION requirements of this equipment. Refer
to these sections when either maintenance or calibration is required.
Section 7 describes SERVICE methodology and provides system, sub-assembly, and
component part numbers to aid the operator in making factory authorized field repairs.
Section 9 contains product change notices, errata, and data relative to customer specified
modifications. Read Section 9 before operating the equipment. This is especially true when
modifications (MODs) have been installed, since these can change system operation.
If questions arise while reading this manual, the user is encouraged to call the Pacific Power
Source. Pacific maintains a toll-free number which is 1-800-854-2433 (1-800-472-8465 inside
California).

SECTION 1 GENERAL
2
1.2 SAFETY NOTICES
The ASX-Series equipment is capable of transferring very large amounts of electrical energy
very quickly. This basic quality is fundamental to a high-performance power source. The
warnings and cautions listed below should be observed at all times.
WARNINGS are conditions which are hazardous to user personnel. All warnings throughout this
manual will be formatted as shown below. A condition which is hazardous to both personnel and
equipment will be issued as a warning.
CAUTION statements indicate a dangerous situation which may damage the equipment but is
not a threat to life or limb. Cautions will assume the format shown on page 3. All cautions should
be rigorously observed
WARNING
THIS EQUIPMENT CONTAINS HIGH ENERGY, LOW IMPEDANCE CIRCUITS!! LETHAL POTENTIALS ARE
CONTAINED WITHIN THE CABINET.
CARE MUST BE EXERCISED WHEN SERVICING THIS EQUIPMENT IN ORDER TO PREVENT SERIOUS
OPERATOR INJURY OR EQUIPMENT DAMAGE.
VOLTAGE AT THE TERMINALS RESPONDS INSTANTLY WHEN THE OUTPUT IS ACTIVATED.
OBSERVE THE FOLLOWING WHEN SERVICE, MAINTENANCE, OR CALIBRATION ARE REQUIRED:
1) REMOVE ALL JEWELRY FROM HANDS, ARMS AND NECK WHEN SERVICING THIS EQUIPMENT.
THIS PREVENTS THE POSSIBILITY OF SHORTING THROUGH THE JEWELRY AND CAUSING
BURNS OR ELECTROCUTION OF THE OPERATOR.
2) WEAR SAFETY GLASSES WHEN SERVICING THIS EQUIPMENT TO PREVENT EYE INJURY DUE
TO FLYING PARTICLES CAUSED BY ACCIDENTAL SHORT CIRCUIT CONDITIONS.
3) DO NOT REMOVE ANY PANEL OR COVER WITHOUT FIRST REMOVING THE INPUT SERVICE
BY OPENING ALL CIRCUIT BREAKERS.
4) SERVICE OTHER THAN EXTERNAL CLEANING SHOULD BE REFERRED TO PERSONNEL
AUTHORIZED BY THE FACTORY TO SERVICE THIS EQUIPMENT.

SECTION 1 GENERAL
3
1.2 SAFETY NOTICES (cont.)
CAUTION
READ SECTIONS 1, 3, AND 4 OF THIS
MANUAL BEFORE INSTALLING OR
OPERATING THIS EQUIPMENT.
WARNING
IF THIS EQUIPMENT IS NOT USED IN A MANNER SPECIFIED BY THE MANUFACTURER, THE
PROTECTION PROVIDED BY THE EQUIPMENT MAY BE IMPAIRED

SECTION 1 GENERAL
4
1.3 GENERAL PRODUCT DESCRIPTION
The ASX-Series Power Source is high-performance AC power conversion equipment. This
series of equipment features models with power ratings from 1.5 kVA to 12.0 kVA. All systems
are designed to fit into a standard 19 inch instrument rack. The power sources are suitable for
use as frequency converters as well as sophisticated AC test power systems.
ASX power sources are typically configured with an interchangeable controller. Controller
options range from basic manual control (UPC1M and 3M) to sophisticated programmable
controllers (UPC1, UPC3, UPC12 or UPC32). The manual controller allows the user to adjust
voltage and frequency. The programmable controller provides all of the manual control
capability, plus a wide variety of control features including program storage, waveform editing,
and remote interface.
Unique to the Models 120ASX and 320ASX is the ability to operate at 150l-n / 300Vl-l. Unique to
the model 3120ASX is the ability to provide full power in either 1, 2, or 3 phase mode of
operation. The nominal (rated) output voltage range for the ASX-Series is 0-125l-n / 250Vl-l.
Available current at specific voltages, as well as maximum output voltage varies by model. Refer
to section 2.1.2 for further details
Optional output transformers are available to provide higher output voltage ranges. Standard
ratios up to 2.5:1 (312/541V) as well as custom ratios are available.
The ASX-Series consists of the basic models listed below.
1. Model 115-ASX - 1.5 kVA model, capable of 1 Phase operation. Single phase output
voltage range is 0-132l-n. Internal output transformer option available for higher
voltages.
2. Model 120-ASX - 2.0 kVA model, capable of 1 or 2 Phase operation. Single phase
output voltage range is 0-150 VACl-n. Output voltage in 2 Phase Mode is 0-300 VACL1-L2.
Additional ranges available with custom external transformer configurations.
3. Model 140-ASX - 4.0 kVA model, capable of 1 or 2 Phase operation. Single phase
output voltage range is 0-135 VACl-n. Output voltage in 2 phase mode is 0-270VACL1-L2.
External Magnetics Module available for higher output voltage ranges.
4. Model 160-ASX -6.0 kVA model, capable of 1 or 2 Phase operation. Single phase mode
provides 6kVA of power with a 0-132 VACl-n voltage range. 2 phase mode provides
4kVA of power with a 0-270VACL1-L2.voltage range. External Magnetics Module
available for higher output voltage ranges.
5. Model 315-ASX - 1.5 kVA model, capable of 1, 2, or 3 phase operation. Single and three
phase modes provide 1.5kVA of power with a 0-132 VACl-n output voltage range. 2
phase mode provides 1kVA of power with a 0-264Vl1-l2 voltage range. Additional ranges
available with custom external transformer configurations.
6. Model 320-ASX - 2.0 kVA model, capable of 1, 2, or 3 Phase operation. Single and
three phase modes provide 2.0kVA of power with a 0-150 VACl-n output voltage range.
2 phase mode provides 2kVA of power with a 0-300Vl1-l2 voltage range. Additional
ranges available with custom external transformer configurations.

SECTION 1 GENERAL
5
1.3 GENERAL PRODUCT DESCRIPTION (cont.)
7. Model 345-ASX - 4.5 kVA model, capable of 1, 2, or 3 Phase operation. Single and
three phase modes provide 4.5kVA of power with a 0-135 VACl-n output voltage range.
2 phase mode provides 3.0kVA of power with a 0-270l1-l2 voltage range. External
Magnetics Module available for higher output voltage ranges.
8. Model 360-ASX – 6.0 kVA model, capable of 1, 2, or 3 Phase operation. Single and
three phase modes provide 6.0kVA of power with a 0-132 VACl-n output voltage range.
2 phase mode provides 4.0kVA of power with a 0-270l1-l2 voltage range. External
Magnetics Module available for higher output voltage ranges.
9. Model 3120-ASX - 12.0 kVA model, capable of 1, 2, or 3 Phase operation. Single, split,
and three phase modes provide 12kVA of power with a 0-135 VACl-n output voltage
range. 2 phase mode provides the full 12.0kVA of power with a 0-270l1-l2 voltage range.
External Magnetics Module available for higher output voltage ranges.
10. System Control Unit (SCU) - Self-contained chassis assembly which houses a
UPC-Series controller allowing for the controller to be remotely located from the power
source chassis.
External voltage sense is provided on all systems. Systems configured with the programmable
controller also offer Continuous Self Calibration (CSC) output level control.
Output voltage and current metering is provided on all systems. Specifications of the metering
functions vary by controller type. Refer to Section 8 of the UPC-Series Operation Manual for
details relative to the metering functions.

SECTION 1 GENERAL
6
1.3 GENERAL PRODUCT DESCRIPTION (cont.)
FIGURE1.3 ASX-SERIES POWER SOURCE - FRONT VIEW
MODEL 115-ASX
W/ UPC1 CONTROLLER
MODEL 3210-ASX
W/ UPC3 CONTROLLER
INPUT
POWER
OUTPUT
POWER
OUTPUT
COUPLING
OUTPUT
FORM
ON
OFF
DIRECT
TRANSFORMER
1 PHASE
2 PHASE
3 PHASE
ON /
AUTO
OFF
PACIFIC POWER SOURCE INC. IRVINE, CALIFORNIA

7
SECTION 2
SPECIFICATIONS
2 SPECIFICATIONS
This section states the electrical specifications of the ASX-Series Power Source. The
specifications listed apply to all models, except as noted. Some specifications are controller
dependent. These are noted as such.
2.1 ELECTRICAL SPECIFICATIONS
2.1.1 INPUT POWER REQUIREMENTS
This paragraph lists and defines the input voltage forms that are accepted by the various models
within the ASX-Series line of equipment. Each model is listed separately. Refer to the
appropriate model when determining proper input service requirements. The input currents
listed are those for operation at full rated load. Overload conditions will result in higher input
currents that still fall within the recommended input service.
The input power transformer of the ASX-Series Power Source has taps for each of the listed
power forms--one of which is selected by the factory at time of order. Once selected, the unit will
operate at designated voltage, ±10%.
The standard input frequency of 50/60 Hz is offered for all models. 400 Hz ( 360 – 440 Hz) option
is also available. Please call factory for details.
MODEL 115-ASX
INPUT VOLTAGE
The Model 115-ASX accepts one of the following single phase input voltages:
1) 100 VAC ±10%, 47-63 Hz
2) 110 VAC ±10%, 47-63 Hz
3) 120 VAC ±10%, 47-63 Hz
4) 200 VAC ±10%, 47-63 Hz
5) 208 VAC ±10%, 47-63 Hz
6) 220 VAC ±10%, 47-63 Hz
7) 230 VAC ±10%, 47-63 Hz
8) 240 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 115-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 100 VAC 22 Arms 25 A
2) 110 VAC 20 Arms 25 A
3) 120 VAC 18 Arms 25 A
4) 200 VAC 11 Arms 15 A
5) 208 VAC 10 Arms 15 A
6) 220 VAC 10 Arms 15 A
7) 230 VAC 9 Arms 15 A
8) 240 VAC 9 Arms 15 A

SECTION 2 SPECIFICATIONS
8
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 120-ASX
INPUT VOLTAGE
The Model 120-ASX accepts one of the following single phase input voltages:
1) 100 VAC ±10%, 47-63 Hz
2) 110 VAC ±10%, 47-63 Hz
3) 120 VAC ±10%, 47-63 Hz
4) 200 VAC ±10%, 47-63 Hz
5) 208 VAC ±10%, 47-63 Hz
6) 220 VAC ±10%, 47-63 Hz
7) 230 VAC ±10%, 47-63 Hz
8) 240 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 120-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 100 VAC 22 Arms 25 A
2) 110 VAC 20 Arms 25 A
3) 120 VAC 18 Arms 25 A
4) 200 VAC 10 Arms 15 A
5) 208 VAC 10 Arms 15 A
6) 220 VAC 10 Arms 15 A
7) 230 VAC 9 Arms 15 A
8) 240 VAC 9 Arms 15 A
MODEL 140-ASX
INPUT VOLTAGE
The Model 140-ASX accepts one of the following three phase input voltages:
1) 208 VAC Δ±10%, 47-63 Hz
2) 220 VAC Δ±10%, 47-63 Hz
3) 240 VAC Δ±10%, 47-63 Hz
4) 220/380 VAC ±10%, 47-63 Hz
5) 230/400 VAC ±10%, 47-63 Hz
6) 240/416 VAC ±10%, 47-63 Hz
(cost option) 7) 277/480 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 140-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 208 VAC Δ13 Arms 20 A
2) 220 VAC Δ12 Arms 20 A
3) 240 VAC Δ11 Arms 15 A
4) 220/380 VAC 7 Arms 10 A
5) 230/400 VAC 7 Arms 10 A
6) 240/416 VAC 6.5 Arms 10 A
7) 277/480 VAC 5.5 Arms 10 A

SECTION 2 SPECIFICATIONS
9
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 160-ASX
INPUT VOLTAGE
The Model 160-ASX accepts one of the following three phase input voltages:
1) 208 VAC Δ±10%, 47-63 Hz
2) 220 VAC Δ±10%, 47-63 Hz
3) 240 VAC Δ±10%, 47-63 Hz
4) 220/380 VAC ±10%, 47-63 Hz
5) 230/400 VAC ±10%, 47-63 Hz
6) 240/416 VAC ±10%, 47-63 Hz
(cost option) 7) 277/480 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 160-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 208 VAC Δ20 Arms 30 A
2) 220 VAC Δ18 Arms 30 A
3) 240 VAC Δ16 Arms 25 A
4) 220/380 VAC 11 Arms 15 A
5) 230/400 VAC 10 Arms 15 A
6) 240/416 VAC 10 Arms 15 A
7) 277/480 VAC 8 Arms 15 A
MODEL 315-ASX
INPUT VOLTAGE
The Model 315-ASX accepts one of the following single phase input voltages:
1) 100 VAC ±10%, 47-63 Hz
2) 110 VAC ±10%, 47-63 Hz
3) 120 VAC ±10%, 47-63 Hz
4) 200 VAC ±10%, 47-63 Hz
5) 208 VAC ±10%, 47-63 Hz
6) 220 VAC ±10%, 47-63 Hz
7) 230 VAC ±10%, 47-63 Hz
8) 240 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 315-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 100 VAC 22 Arms 25 A
2) 110 VAC 20 Arms 25 A
3) 120 VAC 18 Arms 25 A
4) 200 VAC 11 Arms 15 A
5) 208 VAC 10 Arms 15 A
6) 220 VAC 10 Arms 15 A
7) 230 VAC 9 Arms 15 A
8) 240 VAC 9 Arms 15 A

SECTION 2 SPECIFICATIONS
10
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 320-ASX
INPUT VOLTAGE
The Model 320-ASX accepts one of the following single phase input voltages:
1) 100 VAC ±10%, 47-63 Hz
2) 110 VAC ±10%, 47-63 Hz
3) 120 VAC ±10%, 47-63 Hz
4) 200 VAC ±10%, 47-63 Hz
5) 208 VAC ±10%, 47-63 Hz
6) 220 VAC ±10%, 47-63 Hz
7) 220 VAC ±10%, 47-63 Hz
8) 240 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 320-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 100 VAC 22 Arms 25 A
2) 110 VAC 20 Arms 25 A
3) 120 VAC 18 Arms 25 A
4) 200 VAC 10 Arms 15 A
5) 208 VAC 10 Arms 15 A
6) 220 VAC 10 Arms 15 A
7) 230 VAC 9 Arms 15 A
8) 240 VAC 9 Arms 15 A
MODEL 345-ASX
INPUT VOLTAGE
The Model 345-ASX accepts one of the following three phase input voltages:
1) 208 VAC Δ±10%, 47-63 Hz
2) 220 VAC Δ±10%, 47-63 Hz
3) 240 VAC Δ±10%, 47-63 Hz
4) 220/380 VAC ±10%, 47-63 Hz
5) 230/400 VAC ±10%, 47-63 Hz
6) 240/416 VAC ±10%, 47-63 Hz
(cost option) 7) 277/480 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 345-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT
CURRENT
Service
Recommended
1) 208 VAC Δ15 Arms 25 A
2) 220 VAC Δ14 Arms 25 A
3) 240 VAC Δ12 Arms 20 A
4) 220/380 VAC 8 Arms 15 A
5) 230/400 VAC 8 Arms 15 A
6) 240/416 VAC 7.5 Arms 15 A
7) 277/480 VAC 6 Arms 10 A

SECTION 2 SPECIFICATIONS
11
2.1.1 INPUT POWER REQUIREMENTS (cont.)
MODEL 360-ASX
INPUT VOLTAGE
The Model 360-ASX accepts one of the following three phase input voltages:
1) 208 VAC Δ±10%, 47-63 Hz
2) 220 VAC Δ±10%, 47-63 Hz
3) 240 VAC Δ±10%, 47-63 Hz
4) 220/380 VAC ±10%, 47-63 Hz
5) 230/400 VAC ±10%, 47-63 Hz
6) 240/416 VAC ±10%, 47-63 Hz
(cost option) 7) 277/480 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 360-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT
CURRENT
Service Recommended
1) 208 VAC Δ20 Arms 30 A
2) 220 VAC Δ18 Arms 30 A
3) 240 VAC Δ16 Arms 25 A
4) 220/380 VAC 11 Arms 15 A
5) 230/400 VAC 11 Arms 15 A
6) 240/416 VAC 10 Arms 15 A
7) 277/480 VAC 8 Arms 15 A
MODEL 3120-ASX
INPUT VOLTAGE
The Model 3120-ASX accepts one of the following three phase input voltages:
1) 208 VAC Δ±10%, 47-63 Hz
2) 220 VAC Δ±10%, 47-63 Hz
3) 230 VAC Δ±10%, 47-63 Hz
4) 240 VAC Δ±10%, 47-63 Hz
5) 220/380 VAC ±10%, 47-63 Hz
6) 230/400 VAC ±10%, 47-63 Hz
7) 240/416 VAC ±10%, 47-63 Hz
8) 277/480 VAC ±10%, 47-63 Hz
INPUT CURRENT
The input current required by the Model 3120-ASX at full rated load is stated below.
Recommended input service is also stated.
V
in INPUT CURRENT SERVICE RECOMMENDED
1) 208 VAC Δ40 Arms 60 A
2) 220 VAC Δ36 Arms 50 A
3) 230 VAC Δ36 Arms 50 A
4) 240 VAC Δ32 Arms 50 A
5) 220/380 VAC 22 Arms 30 A
6) 230/400 VAC 21 Arms 30 A
7) 240/416 VAC 20 Arms 30 A
8) 277/480 VAC 16 Arms 20 A

SECTION 2 SPECIFICATIONS
12
2.1.2 OUTPUT POWER
OUTPUT VOLTAGE RANGE
DIRECT-COUPLED
The standard output voltage ranges of the ASX-Series are: 0-132 VACl-n for the Models
115-ASX, 160-ASX, 315-ASX, and 360-ASX; 0-135 VACl-n for the Models 140-ASX, 345-ASX,
and 3120-ASX; and 0-150 VACl-n for the Models 120-ASX and 320-ASX, when operated in the
direct-coupled mode. These voltages are stated for nominal input voltage applied.
TRANSFORMER-COUPLED
The output voltage range of the ASX-Series Power Source varies when operated in the
transformer-coupled mode. Maximum output voltage is determined by the transformer turns
ratio. See list below for maximum output voltage vs. turns ratio.
TURNS RATIO MAXIMUM OUTPUT VOLTAGE (No Load)
1.5:1 198 VACl-n Models 115-ASX, 160-ASX, 315-ASX, and 360-ASX
203 VACl-n Models 140-ASX, 345-ASX, and 3120-ASX
2.0:1 264 VACl-n Models 115-ASX, 160-ASX, 315-ASX, and 360-ASX
270 VACl-n Models 140-ASX, 345-ASX, and 3120-ASX
2.5:1 330 VACl-n Models 115-ASX, 160-ASX, 315-ASX, and 360-ASX
338 VACl-n Models 140-ASX, 345-ASX, and 3120-ASX
OUTPUT CURRENT
FULL-RATED CURRENT
The full-rated output current the ASX-Series Power Source is listed below by model number.
Refer to the derating charts of Figures 2.1.2(A-H) for maximum output current at a specific output
form, voltage, or power factor. Output current ratings are scaled appropriately when using
transformer-coupled outputs. Note that the 315-ASX has reduced ratings when the output
magnetics option is installed (the "T" added to the model number designates the output
magnetics option). All other models retain their full-rated output current with the output
magnetics option installed.
1φ2φ3φ
MODEL I
out, rms I
out, pk I
out, rms I
out, pk I
out, rms I
out, pk
115-ASX 16 A 35 A N/A N/A N/A N/A
120-ASX 20 A 90 A 14 A 45 A N/A N/A
140-ASX 32 A 90 A 16 A 45 A N/A N/A
160-ASX 48 A 120 A 16 A 45 A N/A N/A
315-ASX 12 A 69 A 6 A 23 A 4 A 23 A
315-ASXT 9 A 69 A 6 A 23 A 3 A 23 A
(with output magnetics option)
320-ASX 20 A 69 A 12 A 23 A 7 A 23 A
345-ASX 36 A 100 A 12 A 40 A 16 A 40 A
360-ASX 48 A 120 A 16 A 45 A 16 A 45 A
3120-ASX 96 A 300 A 48 A 150 A 32 A 100 A
OVERLOAD OPERATION
The ASX-Series Power Source will deliver up to 125% of rated RMS output current at 25°C
ambient room temperature, nominal through 10% high input line voltage, and at a power factor
of 0.8. Elevated ambient temperatures, low input line voltage, or power factors between 0.8 and
1.0 will increase the internal dissipation of the power source and can cause overload shutdown
due to over-temperature conditions. Length of time to reach over-temperature varies with the
models and the above parameters.
Table of contents
Other Pacific Power Source AC Power Distribution manuals