Metek MX15 User manual

MX15 Series
AC and DC Power Source
Installation Manual
Contact Information
Telephone: 800 733 5427 (toll free in North America)
858 450 0085 (direct)
Fax: 858 458 0267
Email:
Domestic Sales: domorders.sd@ametek.com
International Sales: intlorders.sd@ametek.com
Web: www.programmablepower.com
March 2011 Document No. 7005-954 Rev. C



Installation Manual
AC Power Source
California Instruments
Models:
MX15-1
MX15-1Pi
MX30/2-1Pi
MX30/2-1Pi-MB
MX45/3-1Pi
MX45/3-1Pi-MB
Rev C, March 2011.

i
About AMETEK
AMETEK Programmable Power, Inc., a Division of AMETEK, Inc., is a global leader in the design
and manufacture of precision, programmable power supplies for R&D, test and measurement,
process control, power bus simulation and power conditioning applications across diverse
industrial segments. From bench top supplies to rack-mounted industrial power subsystems,
AMETEK Programmable Power is the proud manufacturer of Elgar, Sorensen, California
Instruments and Power Ten brand power supplies.
AMETEK, Inc. is a leading global manufacturer of electronic instruments and electromechanical
devices with annualized sales of $2.5 billion. The Company has over 11,000 colleagues working
at more than 80 manufacturing facilities and more than 80 sales and service centers in the United
States and around the world.
Trademarks
AMETEK is a registered trademark of AMETEK, Inc.
Other trademarks, registered trademarks, and product names are the property of their respective
owners and are used herein for identification purposes only.
Notice of Copyright
MX15 Series, AC and DC Power Source, Installation Manual
© 2010 AMETEK Programmable
Power, Inc. All rights reserved.
Exclusion for Documentation
UNLESS SPECIFICALLY AGREED TO IN WRITING, AMETEK PROGRAMMABLE POWER, INC.
(“AMETEK”):
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER
DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR
EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL,
WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH
INFORMATION WILL BE ENTIRELY AT THE USER’S RISK, AND
(c) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH,
ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE
TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED AMETEK CONTENT
IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION, WHICH IS POSTED AT
WWW.PROGRAMMABLEPOWER.COM.
Date and Revision
March 2011 Revision C
Part Number
7005-954
Contact Information
Telephone: 800 733 5427 (toll free in North America)
858 450 0085 (direct)
Fax: 858 458 0267
Email: sales@programmablepower.com
service@programmablepower.com
Web: www.programmablepower.com

ii
This page intentionally left blank.

iii
Important Safety Instructions
Before applying power to the system, verify that your product is configured properly for your
particular application.
WARNING
Hazardous voltages may be present when covers are removed. Qualified
personnel must use extreme caution when servicing this equipment.
Circuit boards, test points, and output voltages also may be floating above
(below) chassis ground.
WARNING
The equipment used contains ESD sensitive ports. When installing
equipment, follow ESD Safety Procedures. Electrostatic discharges might
cause damage to the equipment.
Only qualified personnel who deal with attendant hazards in power supplies, are allowed to perform
installation and servicing.
Ensure that the AC power line ground is connected properly to the Power Rack input connector or
chassis. Similarly, other power ground lines including those to application and maintenance
equipment must be grounded properly for both personnel and equipment safety.
Always ensure that facility AC input power is de-energized prior to connecting or disconnecting any
cable.
In normal operation, the operator does not have access to hazardous voltages within the chassis.
However, depending on the user’s application configuration, HIGH VOLTAGES HAZARDOUS TO
HUMAN SAFETY may be normally generated on the output terminals. The customer/user must
ensure that the output power lines are labeled properly as to the safety hazards and that any
inadvertent contact with hazardous voltages is eliminated.
Guard against risks of electrical shock during open cover checks by not touching any portion of the
electrical circuits. Even when power is off, capacitors may retain an electrical charge. Use safety
glasses during open cover checks to avoid personal injury by any sudden component failure.
Neither AMETEK Programmable Power Inc., San Diego, California, USA, nor any of the subsidiary
sales organizations can accept any responsibility for personnel, material or inconsequential injury,
loss or damage that results from improper use of the equipment and accessories.
SAFETY SYMBOLS

iv
Product Family: MX15 Series
Warranty Period: One Year
WARRANTY TERMS
AMETEK Programmable Power, Inc. (“AMETEK”), provides this written warranty covering the
Product stated above, and if the Buyer discovers and notifies AMETEK in writing of any defect in
material or workmanship within the applicable warranty period stated above, then AMETEK may,
at its option: repair or replace the Product; or issue a credit note for the defective Product; or
provide the Buyer with replacement parts for the Product.
The Buyer will, at its expense, return the defective Product or parts thereof to AMETEK in
accordance with the return procedure specified below. AMETEK will, at its expense, deliver the
repaired or replaced Product or parts to the Buyer. Any warranty of AMETEK will not apply if the
Buyer is in default under the Purchase Order Agreement or where the Product or any part
thereof:
is damaged by misuse, accident, negligence or failure to maintain the same as
specified or required by AMETEK;
is damaged by modifications, alterations or attachments thereto which are not
authorized by AMETEK;
is installed or operated contrary to the instructions of AMETEK;
is opened, modified or disassembled in any way without AMETEK’s consent; or
is used in combination with items, articles or materials not authorized by AMETEK.
The Buyer may not assert any claim that the Products are not in conformity with any warranty
until the Buyer has made all payments to AMETEK provided for in the Purchase Order Agreement.
PRODUCT RETURN PROCEDURE
1. Request a Return Material Authorization (RMA) number from the repair facility (must be
done in the country in which it was purchased):
In the USA, contact the AMETEK Repair Department prior to the return of the
product to AMETEK for repair:
Telephone: 800-733-5427, ext. 2295 or ext. 2463 (toll free North America)
858-450-0085, ext. 2295 or ext. 2463 (direct)
Outside the United States, contact the nearest Authorized Service Center
(ASC). A full listing can be found either through your local distributor or our
website, www.programmablepower.com, by clicking Support and going to the
Service Centers tab.
2. When requesting an RMA, have the following information ready:
Model number
Serial number
Description of the problem
NOTE: Unauthorized returns will not be accepted and will be returned at the shipper’s expense.
NOTE: A returned product found upon inspection by AMETEK, to be in specification is subject to
an evaluation fee and applicable freight charges.

Installation Manual
MX15 Series 5
Table of Contents
1. Introduction..................................................................................................................................... 6
1.1 General Description................................................................................................................................6
1.2 Manual organization and format .............................................................................................................6
2. Unpacking and Installation ............................................................................................................. 7
2.1 Unpacking............................................................................................................................................... 7
2.2 Power Requirements ..............................................................................................................................7
2.3 Mechanical Installation............................................................................................................................ 8
2.4 AC Input Connections and Wiring...........................................................................................................8
2.5 AC On/Off Circuit Breaker on MX15 front panel. .................................................................................. 11
2.6 Output Connections.............................................................................................................................. 13
2.7 Connectors - Rear Panel ...................................................................................................................... 21
2.8 Multiple Cabinet System Configurations............................................................................................... 24
2.9 Clock and Lock Configurations............................................................................................................. 25
2.10Basic Initial Functional Test.................................................................................................................. 27
3. Index............................................................................................................................................. 29
List of Figures
Figure 2-1: The MX15 Power Source.................................................................................................................... 7
Figure 2-2: Location of AC Input Fuse Block, Chassis Ground Connection, and Output Terminal Block..............9
Figure 2-3: MX15 AC Input Connection Diagram................................................................................................ 10
Figure 2-4: Rear Panel........................................................................................................................................ 12
Figure 2-5: External sense cable shield connection to chassis ground............................................................... 13
Figure 2-6: MX45-1 Output Wiring ...................................................................................................................... 15
Figure 2-7: MX30/2 or MX30/2-MB Output Wiring............................................................................................... 16
Figure 2-8: Two MX15's in Clock and Lock mode Output Wiring........................................................................ 17
Figure 2-9: MX45/3 or MX45/3-MB Output Wiring............................................................................................... 18
Figure 2-10: Three MX15's in Clock and Lock mode - Output Wiring ................................................................. 19
Figure 2-11: Ship kit Terminal Block dimensions................................................................................................ 20
Figure 2-12: Multi-Cabinet DIP Switch Location and Setting............................................................................... 24
Figure 2-13: Functional Test Setup..................................................................................................................... 28
List of Tables
Table 2-1: Suggested Input Wiring Sizes for each MX15 Cabinet....................................................................... 11
Table 2-2: Suggested Output Wiring Sizes......................................................................................................... 14
Table 2-3: System Interface Connectors............................................................................................................. 21
Table 2-4: Analog Interface Connector ............................................................................................................... 22
Table 2-5: BNC Connectors................................................................................................................................ 22
Table 2-6: External Sense Connector................................................................................................................. 23
Table 2-7: Clock and Lock Configuration settings............................................................................................... 25
Table 2-8: Clock and Lock Initialization settings ................................................................................................. 26

Installation Manual
MX15 Series 6
1. Introduction
This installation manual is provided in hardcopy format and contains information on the
installation only of MX15 Series power sources with the programmable controller.
All other MX15 Series manuals are provided in Adobe Acrobat PDF format on CD ROM P/N
CIC496. The CD ROM is included in the MX15 Series Ship kit.
1.1 General Description
The MX Series AC and DC power source systems are high efficiency, floor standing AC and DC
power sources that provide a precise output with low distortion. Available voltage ranges are 150
Vac, 300 Vac and 400 Vac in AC mode and 200 Vdc and 400 Vdc in DC mode. All MX15 units
have a single-phase output.
Models with a -1 designation provide full front panel operation but do not include a RS232C or
IEEE-488 remote control interface. An optional RS232C/IEEE-488 control interface can be added
at the time of order however (-P) option. Models with the Pi controller offer several additional
standard features, including the RS232C/IEEE-488 interfaces, arbitrary waveform generation,
and additional measurement functions.
The MX Series units are contained in a compact floor standing enclosure on casters. This allows
the units to be moved around more easily.
Read the installation instructions carefully before attempting to install and operate the MX Series
power systems.
1.2 Manual organization and format
All user documentation for California Instruments power sources is provided on CDROM in
electronic format. (Adobe Portable Document Format) The required Adobe PDF viewer is
supplied on the same CDROM. This Installation manual is provided only in hardcopy form to
ensure that the installation information is available to all MX users and installers.
To request a hardcopy of other MX Series manuals from California Instruments, contact customer
service at support@calinst.com. There will be an additional charge for printed manuals. You can
also print these manuals directly from the included CD ROM.

Installation Manual
MX15 Series 7
2. Unpacking and Installation
2.1 Unpacking
Inspect the unit for any possible shipping damage immediately upon receipt. If damage is
evident, notify the carrier. DO NOT return an instrument to the factory without prior approval. Do
not destroy the packing container until the unit has been inspected for damage in shipment. If
possible, retain the container (wooden crate) in the event the system ever has to be returned to
the factory for either repair or upgrades
WARNING: This power source weighs approximately 600 lbs / 272 Kg. Obtain
adequate help when moving the unit. Make sure the location (floor) in which the MX
Series unit(s) will be installed can support the weight of the unit(s).
2.2 Power Requirements
The MX Series power Source has been designed to operate from a three-phase, three wire (Wye
or Delta) AC input line. A protective earth connection is required as well. (PE).
Available three-phase input settings are 208 VLL (option -208), 230 VLL (option -230), 400 VLL
(option -400), 440 VLL (option –440), or 480 VLL (option -480).
Figure 2-1: The MX15 Power Source
CAUTION: Do not connect 400, 440, or 480V into a unit set for 208 or 230V unit, the
result could be a severely damaged unit. Always check the input rating on the model
number tag before connecting AC input power. Consult factory if input settings have
to be changed.

Installation Manual
MX15 Series 8
2.3 Mechanical Installation
The MX15's are completely self-contained power sources. They are to be used free standing on
a solid surface. The units are fan cooled, drawing air in from the front and exhausting at the rear.
The front and back of each unit must be kept clear of obstruction and a 6” clearance must be
maintained to the rear. Special consideration of overall air flow characteristics and the resultant
internal heat rise must be considered at all times to avoid self heating and over temperature
problems.
2.4 AC Input Connections and Wiring
Three phase Delta or Y AC input voltage of sufficient amperage (consult AC input specifications
for maximum AC current per phase) is required to power the MX Series.
Note: AC power should be routed through a properly sized and rated three-phase
PROTECTIVE CIRCUIT BREAKER or similar branch circuit protection device with
disconnect capability. This will protect building wiring and other circuits from
possible damage or shutdown in case of a system problem. It will also facilitate
removing AC input power to the MX system in case of service or reconfiguration
requirements.
Note: AC input wiring and connections must conform to local electrical safety codes that
apply. Always consult a qualified electrician prior to installation of any MX System.
AC input connections are to be made directly to the input fuse block. The input fuse block is
located on the lower right hand corner of the rear of the MX15 chassis. To access the input fuse
connection block, the protective rear cover needs to be removed first.
CAUTION: Always disconnect any input power completely when removing any
protective cover and allow the internal capacitors to fully discharge (minimum
of 15 mins) before removing any cover. See Figure 2-2 for details.
No wiring for AC input connections is provided with the MX Series and must be provided by the
end user or installer. Input wiring should be entered through the right hand side (when facing the
back of the MX15, see Figure 2-4) wire access opening located at the rear bottom of the MX15
chassis.

Installation Manual
MX15 Series 9
Figure 2-2: Location of AC Input Fuse Block, Chassis Ground Connection, and Output Terminal
Block
Note: To comply with product safety requirements, EARTH GROUND must be connected
to the chassis of the AC power system using the ground stud located above the K1
relay. Use a Green/Yellow ground wire.
The mains source must have a current rating equal to or greater than the input fuses and the
input wiring must be sized to satisfy the applicable electrical codes. The front cover must be re-
installed prior to use and the strain relief provisions located at the rear bottom of the unit must be
used to maintain protection against hazardous conditions.

Installation Manual
MX15 Series 10
Figure 2-3: MX15 AC Input Connection Diagram

Installation Manual
MX15 Series 11
The input power cables and protective circuit breaker used must be large enough to handle the
input current and input voltage of the power source and must conform to local electrical codes.
Consult a qualified electrician prior to installation. Table 2-1 shows the size of the cables that may
be used per MX15 cabinet. Note that wires must be sized to accommodate the worst-case
maximum current that may occur under low line conditions. Local electrical codes may also
require different wire types and sizes. These ratings should also be used when selecting a circuit
breaker or equivalent disconnect device.
Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate
the voltage drop from the following formula:
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
Table 2-1: Suggested Input Wiring Sizes for each MX15 Cabinet
Nominal Line
Voltage
Load Current
@ low line
Wire Gauge (US)
Circular Mils
(Kcmils)
Metric (mm2)
480 V
25 Arms
10 AWG
11.50
5.8
400 V
30 Arms
10 AWG
11.50
5.8
230 V
52 Arms
8 AWG
18.00
9.1
208 V
58 Arms
6 AWG
26.24
13.3
CAUTION: Capacitors in the power source may hold a hazardous electrical charge
even if the power source has been disconnected from the mains supply. Allow
capacitors to discharge to a safe voltage before touching exposed pins of mains
supply connectors.
Power modules need at least 15 Minutes to discharge to safe levels before they can be
removed.
2.5 AC On/Off Circuit Breaker on MX15 front panel.
It is important to understand the purpose and operation of the On/Off circuit breaker of the MX15
located on the upper left side of the front panel. This is a 2A rated breaker that is used to engage
and protect the LV Power supply of the MX15 chassis only. The LV Power supply provides DC
bias power to the entire MX15 system. The AC input power is routed through a set of three AC
line fuses (F1-A, F1-B and F1-C) located in the lower right bottom corner of the MX15 (Looking
from the rear). (See Figure 2-2 for fuse locations). These fuses protect the MX15 amplifier and
the AC input transformer from excessive input currents. The AC input power is connected to the
input transformer through a large three-pole contactor. Removing AC power to the LV Power
Supply by opening the front panel circuit breaker (moving the lever to the down (OFF) position)
will cause this contactor to lose its coil voltage and will result in it opening and disconnecting the
input transformer and amplifier from AC mains input.
Note: If any MX15 system failure has occurred on any part of the MX15 system, AC input
power must be removed immediately and not restored until the system has been
inspected by a qualifier service technician.
Always turn off the On/Off Circuit breaker before re-applying AC input power.

Installation Manual
MX15 Series 12
CAUTION: The AC input fuses can only be checked if the MX15 is completely
de-energized and disconnected from any AC power input.
Note: Under no circumstances should AC input power be applied if one or more of the
AC input line fuses have failed and opened up.
Figure 2-4: Rear Panel

Installation Manual
MX15 Series 13
2.6 Output Connections
2.6.1 Output Wiring
The output terminal block, TB1 is located at the rear of the unit behind the bottom access panel.
See Figure 2-2 for details. The outputs are labeled HI and LO.
The external sense inputs allow the power system output voltages to be monitored directly at the
load and must be connected at TB2 when the sense is programmed for external. The external
sense input does not have to be connected when Internal Sense is programmed. The external
sense wires are to be connected to TB2 on the rear panel and should be run using a twisted
shielded cable. See Figure 2-4 for location of TB2 and Figure 2-5 for shield connection detail.
Note: For External Sense connection, a shielded cable MUST be used with the shield
connected to chassis ground at the Ext. Sense connector. (See Figure 2-5).
External sense is recommended for multi-cabinet systems is the output wiring from the cabinets
to the common output terminal block supplied is not of equal length.
Figure 2-5: External sense cable shield connection to chassis ground
Note: The output of the power source is isolated from the input line and floating with
respect to chassis ground. If needed, either side (HI or LO) may be grounded.
If the EUT changes frequently, you may want to consider using some quick disconnect scheme
external to the MX15 so it will not be necessary to power down the MX15 and remove the front
covers. This can take the form of a panel-mounted socket of sufficient current and voltage rating.
(Not supplied with MX15)
The output power cables must be large enough to prevent a total voltage drop exceeding 1% of
the rated output voltage between the power source and the load. Table 2-2 shows the size of the
cables that may be used. Note that wires must be sized to accommodate the maximum current
that is available. This may be a function of the voltage range. Size the wires for the lowest
available voltage range as the currents will be highest in that range.
Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate
the voltage drop from the following formula:
SHIELD
CONNECTION

Installation Manual
MX15 Series 14
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
Table 2-2: Suggested Output Wiring Sizes
Load Current
Wire Gauge (US)
Circular Mils
(kcmils)
Metric (mm2)
65 AMPS
6 AWG
26.24
13.3
130 AMPS
4 AWG
41.74
21.1
2.6.2 Output Terminal Blocks
The MX15-1 and the MX15-1Pi have one output terminal block. The terminal block is large
enough to accommodate the recommended wire gauge sizes shown in Table 2-2. The terminal
block is located in the lower left corner on the rear of the unit. The rear panel needs to be
removed to access this terminal block.
CAUTION: REMOVE ALL INPUT POWER TO THE MX15 BEFORE
REMOVING THE REAR PANEL.
The correct standard size Allen wrench for connecting output wiring to TB1 is supplied with each
MX15 in the ship kit. Look for a brown envelope. If the correct tools cannot be found, contact
Terminal 2 of TB1 provides the output LO connection, and terminal 1 of TB1 provides the output
HI connection. The location of TB1 is shown in Figure 2-2.

Installation Manual
MX15 Series 15
MX15-1 and MX15-1Pi Output Wiring Diagram
Figure 2-6 shows the required output connections for a MX15-1 or MX15-1Pi.
Always disconnect all input power from the MX15 before removing the rear panel cover that
provides access to the input and output terminal connections.
Figure 2-6: MX15-1 Output Wiring

Installation Manual - Rev C California Instruments
MX15 Series 16
2.6.3 MX30/2 Output Wiring Diagram
Figure 2-7 shows the required output connections for a MX30/2-1Pi or MX30/2-1Pi-MB output configuration (rear-view perspective).
Always disconnect all input power from the MX30/2 before removing the rear panel cover that provides access to the input and output
terminal connections. MX30/2 and MX45/3 systems are shipped with external output terminal blocks that enable the output wiring from
two or three chassis to be combined, providing a single point of connection to the EUT. These blocks are not enclosed however.
Figure 2-7: MX30/2 or MX30/2-MB Output Wiring