philippi BTM2 User manual

Battery/Tank Monitor BTM2
philippi elektrische systeme gmbh www. philippi-online.de
Neckaraue 19 info@philippi-online.de
D-71686 Remseck am Neckar Tel: +49 (0)7146/8744-0
OPERATING INSTRUCTIONS
Battery/Tank Monitor BTM2
Thank you for purchasing the Battery / Tank Monitor BTM2.
This gives you one of the most advanced and accurate battery / tank monitors available on the
market.
Battery monitor:
You can see at a glance:
- the current state of charge
- charge and discharge currents
- the battery voltage
- the remaining operating time until the adjustable capacity alarm of the main battery
- the voltage of up to 2 additional batteries
- the currents of a solar system and the charger (optional)
and have the possibility
- connect a second shunt SHP to measure e.g. the current of the solar system.
- connect a philippi charger ACE to monitor the charging process.
- set an alarm when the capacity of the main battery falls below a threshold
- set an alarm when the voltage falls below or exceeds a threshold.
- connect the monitor to an NMEA 2000 network and display the battery and tank levels on the
plotter.
Tank monitor:
You can see at a glance
- the current fill levels of up to 4 tanks
and have the possibility to
- set an alarm threshold for each tank (full or empty alarm)

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 2
1 General information
1.1 V purpose of use
The battery/tank monitor BTM can only be operated in conjunction with the shunt SHE-348 on
extra-low voltage DC 8-32V. It is designed for use on yachts and may only be operated in enclosed
spaces protected from rain, moisture, dust and condensation. Never use the battery/tank monitor
in locations where there is a risk of explosion from gas or dust. The battery/tank monitor is not
suitable for outdoor installation.
1.2 L Scope of delivery
- Battery/Tank Monitor BTM2
- 3 Plug-in terminals (2x MVSTB 2.5- 3 and 1x 9-pole)
- 2 fuse holder ASH1 with fuse FSS 1A
- These operating instructions
Optional accessories (not included in the scope of delivery):
SHUNT SHE 348 for battery capacity detectionOrder no.: 0 7003 0348
SHUNT SHP 348 for solar power measurement Order no.: 0 7003 0351
Temperature sensor Temp-BT Order no.: 0 5900 3480
Battery charger interface ACE-LIN Order no.: 0 8000 4975
N2K cable for NMEA 2000 connection Order no.: 5 0411 1140
1.3 RECOMMENDED FUEL SENSORS (not included)
To measure the fill level, we recommend the immersion tube sensor of the TGT or TGW series for
fuel and fresh water as well as the ultrasonic sensor UTV for faeces tanks and the flow rate sensor
DFS (fresh water only). For deep tanks up to 200 cm and a very precise measurement, the pressure
sensor TDS200 (water/diesel/faeces) or TDW200 (water/faeces).
However, these sensors are not included in the scope of delivery.
Sensors from other manufacturers can also be connected. The display is configured to the
connected sensors in SETUP. Furthermore, an adjustment to the tank geometry is possible in order
to correctly display the actual tank content.
Please note: only with the DFS
flow sensors is the litre display accurate, as litres are also measured here. With all
other sensors, this is only a conversion of the measured fill level and, depending on the
sensor accuracy, can never be accurate to the litre!
Fresh water:
-Flow sensor (1x) DFS Order no.: 7 0003 0304
-immersion tube sensor TGW 200-800 Order no.: 6 6011 7xxx
-Pressure sensor TDN 200 / TDT 250 Order no.: 6 6025 1208
Petrol:

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 3
-immersion tube sensor TGT 200-800 Order no.: 6 6011 7xxx
Diesel:
-immersion tube sensor TGT 200-800 Order no.: 6 6011 7xxx
-Pressure sensor TDS 200 / TDT 250 Order no.: 6 6026 1206
Grey water/ black water:
-Pressure sensor TDN 200 Order no.: 6 6025 1208
-Ultrasonic tank sensor UTV 20-80 Order no.: 7 0219 35xx
recommended accessories for
ultrasonic sensor:
-Sound guide tube UFT 40 (40cm long) Order no.: 7 0219 9400
-Sound guide tube UFT 80 (80cm long) Order no.: 7 0219 9800
-spacer ring UTS 25 (25mm high) Order no.: 7 0219 9025
-Fuse holder incl. fuse 1A for
measuring leads
ASH1A Order no.: 6 0030 3411
1.3 Warranty
Warranty is granted for a period of two years from the date of purchase. Defects due to
incorrect connection liquids leaking into the unit or oxidation due to condensation liquids leaking
into the unit or oxidation due to condensation
lightning strike excluded
Subsequent costs and natural wear and tear are not covered by the warranty.
When asserting claims under guarantee and warranty, a detailed description of the defect is
essential. Detailed information facilitates and accelerates processing. Please understand that we
cannot accept shipments that are sent to us freight collect.
1.4 Disclaimer
Compliance with the operating instructions as well as the conditions and methods during
installation, operation, use and maintenance of the battery/tank monitor BTM cannot be
monitored by philippi elektrische systeme gmbh. Therefore, we do not accept any responsibility or
liability for losses, damages or costs resulting from incorrect installation and improper operation.
1.5 Quality assurance
During production and assembly, the units undergo several checks and tests. Fabrication,
inspections and tests are carried out according to established protocols. Each unit has its own
serial number. Therefore, never remove the type plate. The assembly and testing of all units is
carried out entirely in our factory.
2 S ich safety instructions

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 4
- No modifications may be made to the unit, otherwise the
CE mark
- The battery/tank monitor may only be connected by qualified electricians. -
Before connecting the battery/tank monitor, disconnect the battery leads.
- Ensure that the polarity of the batteries is correct!
- The power supply line to the monitor and shunt must be fused.
- This appliance is not intended for use by children.
These installation and operating instructions are part of the component delivery.
They must be kept in a safe place - important for later maintenance work - and
passed on to any subsequent owners of the unit.
3. Assembly and installation
3.1 Monitor
Mount the battery monitor in a protected,
dry and clearly visible place so that it can be
read at any time. The required mounting cut-
out is 85x85 mm, the required minimum
depth is 35mm. On the rear side there is a 3-
pole terminal for the power supply of the
monitor and the communication line to the
shunt SHE and SHP. The tank sensors are
connected via the 9-pole terminal. A
potential-free relay contact is available via
the 2-pole terminal.
A software update can be loaded onto the
monitor via a micro-SD card on the back.
The power supply to the monitor can be interrupted at any time without losing battery status data,
as this is stored in the SHE 348 shunt.
Therefore, the shunt SHE 348 should be permanently connected to the battery. If the monitor is
switched off, the shunt SHE goes into sleep mode and the current consumption of the shunt drops
to 2 mA. This is not a particular load on the battery. However, if the battery system remains
without charge for more than 3 months, the shunt should also be disconnected from the battery.
The following figure gives an overview of the connection of the monitor and the shunt SHE 348.

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 5
The LIN bus connection between the monitor and the shunt is made via a 1-wire cable. This can
also be any or an existing cable. For mechanical reasons, the cable cross-section should be min.
1mm² and max. 1.5 mm².

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 6
3.2 Shunt SHE for battery monitoring
Mount the shunt SHE 348 in a protected, dry place as close as possible to the battery. The shunt
must be connected in the MINUS path of the battery.
Install the active shunt SHE 348 as close as possible to the service battery. However, avoid the
shunt making contact with the positive - terminal of the batteries. Connect the side of the shunt
marked B- to the negative terminal of the main battery using a short, thick cable (35-70 mm²).
Connect the negative terminal of up to two starter batteries to the side of the shunt marked V-.
Note: If the main battery consists of several batteries connected in parallel, their common negative
terminal must be connected to the side of the shunt marked B-. The negative cables of the starter
batteries are connected to the other side (V-) of the shunt. We recommend that all negative
connections of the consumers, charging devices and the negative terminals of the starter batteries
are combined on a ground busbar and that a short cable is laid from there to the V- connection of
the shunt.- Connect the measuring lead of the shunt to the positive terminal of the main battery
via an inline fuse holder (1A). This line measures the voltage of the main battery and
simultaneously supplies the shunt with current.
It is important that no other cables are connected between the B- terminal and the
battery MINUS terminal, otherwise not all currents will be detected and the battery
management system will not work. All cables of the vehicle electrical system
including the connection cable to the starter battery must be connected to the V
side of the shunt SHE 348.
After applying the operating voltage to pin +1, the shunt goes into operation and indicates the
operating status via the integrated LED:
- Rapid flashing during firmware update of the shunt SHX
- Flashing every 1 sec. Normal operation
- Flashing every 5 sec. Sleep mode (power saving mode) when monitor off
The following connections are available on the shunt at the 5-pin connector:
Consumers, charging sources, starter
batteries
Monitored battery group

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 7
1: Battery voltage measuring lead (+1) and at the same time power supply for shunt
This line is absolutely necessary for the function of the shunt and should only be disconnected
during winter storage to enable a complete recording of the battery capacity. Due to the very low
current consumption in sleep mode, the shunt does not place any additional load on the battery.
2: Voltage (+2) second battery group
Optional connection of a voltage measurement of a second battery group (starter battery), this is
then displayed as a second battery group on the monitor.
3: T-: Minus temperature sensor (brown wire) T+: Plus temperature sensor (blue wire)
Optional temperature sensor (Temp-BT) for recording the battery temperature. The temperature
sensor should be fixed to the outside of the battery housing. The temperature sensor has no active
influence on the capacity calculation or charging, but is only used for information.
4: LIN bus communication with display
The BLS monitor communicates with the SHE 348 shunt and the ACE charger via this line.
3.3 Shunt SHP for current measurement
Mount the optional shunt SHP for measuring the solar current or similar in a protected, dry
location as close as possible to the battery. The shunt must be connected in the MINUS path of the
solar system.
Connect the negative pole of the solar system to the side of the shunt marked V-.
The following connections are available on the shunt at the 5-pin connector:
1: Battery voltage measuring lead (+1) and at the same time power supply for shunt
This line is absolutely necessary for the function of the shunt and can be disconnected at any time
when the monitor is switched off.
4: LIN bus communication with display
The BTM2 monitor communicates with the SHP shunt via this line. This line can be realised with
any cable, preferably with 1 mm² cross-section.
3.4 Interface ACE-LIN (optional accessory)
To communicate the BTM2 monitor with an ACE series charger, an ACE-LIN interface must be
inserted into the ACE charger. For the models ACE 12/60 and ACE 24/30, the integrated monitor
must be removed and replaced with the interface ACE-LIN.
Removing the front charger cover and preparing the cable gland

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 8
Remove the cover Break out the metal tongue with flat-nose pliers
Inserting the rubber cable grommet Inserting the cover and the cable.
Inserting the interface board ACE-LIN
Make sure that the ACE charger is disconnected from the
AC mains before starting work.
After removing the front cover, the setting of the DIP switches must be adjusted for operation with
the CAE-LIN interface.
The ACE chargers are equipped with DIP switches to adjust the charging
characteristic individually to the batteries. Only if the DIP switches of the
charger are set to ABCD = "1111", the charging characteristic can be adjusted
from the monitor BLS. Then it is also possible to set a user-defined
characteristic curve. Otherwise, the characteristic curve set via the DIP switches
applies.
For the electrical connection of the interface board, the 16-pin connector of the ribbon cable must
be plugged into the matching red connector on the main board of the charger ACE.

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 9
The interface board is held in place by three plastic clips on the housing.
Wiring LIN line to monitor BLS / shunt SHE
The communication connection "LIN" of the interface ACE-LIN is connected to the connection "LIN"
of the shunt SHE 348 and the monitor BLS via a 1-wire connection cable. This can be decided
according to the local installation conditions. The order of the units on the "LIN" line is irrelevant.
Since the "LIN" connection on the ACE-LIN interface is duplicated, it is advisable to lay one LIN line
from the monitor to the charger and the other from the charger to the shunt. The ideal conductor
cross-section for the "LIN" cable is 1mm².
IMPORTANT: The monitor, the shunt and the charger must have the same negative potential, i.e.
be connected to a common negative point (battery negative).

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 10
3.5 Electrical connection tank sensor
Up to four tanks can be monitored
simultaneously.
However, if fewer tanks are monitored, the
first tank sensor is connected starting at
connection TG 1 (e.g. with 2 tank sensors,
only connections TG 1 and TG 2 are used).
Resistance sensor (e.g. TGT/TGW) and active
tank sensor (e.g. pressure probe TDS) can be
connected in mixed form.
The connection is made according to the
adjacent diagram
A flow sensor DFS can only be connected to
DFS (DFS + /Minus/DFS S)!
ATTENTION: If
the power supply (red line) of the ultrasonic
tank sensor is not via the BTM, but directly
via the DC on-board power supply, the supply
line must be protected with a 1A fuse!
The minus lines of the tank sensor must be
connected to the minus (-) terminal to avoid
incorrect measurements.
4. settings on the monitor
To access the settings, press the cogwheel symbol in the main screen at the bottom
centre.
4.1 Password protection (PIN) of the Setup
menu
Afterwards, you will be asked to enter the PIN, which is "1234"
by default.
After successful entry with subsequent confirmation
"OK" takes you to the settings menu.

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 11
The following settings can be made by pressing the respective symbol:
1. Display
2. Battery
3. Charger
4. Energy source
5. Tanks
6. Alarms
4.2 Display
After pressing the "Display" symbol, the adjacent picture appears. The following settings can now
be made or information read off:
- Language DE/FR/GB...
- Brightness max. 20 - 100%
- Brightness AutoON/OFF
- Threshold night mode 3.. 30
- Auto Stand by OFF/x [s/min]
- Change PIN
- Number of tanks1-4
- Tank capacity Unit Litres / Gallons (L/g)
- Home page Battery/Tank
- Raymarine mode (only relevant for NMEA 2000)
- Load factory settings
- Save configuration to SD card (all settings are exported)
- Load configuration from SD card (all settings are imported)
- Display of software and hardware status

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 12
The setting "Threshold night mode" is used to calibrate the light sensor in automatic mode. For
calibration, the light sensor (left centre of the display) must be covered with the finger and the
value in brackets must be read. Add two to this value and enter it by pressing briefly. If the
measured value falls below the set value, the display is dimmed. If the measured value exceeds the
set threshold +10, the display is illuminated normally again.
4.3 Battery management
For proper function, the following data must be set during commissioning:
If the battery was not fully charged at that time, it is mandatory to fully charge it in order to
synchronise the display with the battery charge level.
- Name
- Nominal capacity of the battery (Chap. 5.3)
- Rated voltage of the battery group (Chap. 5.4)
- Battery type (chap. 5.6)
- Ah Efficiency factor (CEF) (Chap. 5.9)
- Peukert exponent (Chap. 5.10)
- Cycle depth (chap. 5.11)
- Shunt Info
- Name Battery 2 / 3
4.3.1 Name
This name is shown in the battery symbol of the display and is used for easier assignment.

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 13
4.3.2 Nominal capacity
The nominal capacity of the battery (1-9999Ah) is set here. To obtain a meaningful accuracy of the
remaining time function as well as the percentage charge display, the capacity of the battery to be
monitored must be set.
Please note that the battery capacity should only be adjusted when the batteries are 100%
charged, as this procedure sets the capacity indicator to 100% and all internal counters to 0.
If the battery was not fully charged at that time, this is mandatory to synchronise the display with
the battery charge level.
4.3.3 Rated voltage
Please set the nominal voltage 12 or 24V / 36V / 48V of the battery group so that the capacity
calculation can be done properly.
4.3.4 Battery type
To adjust the "battery empty" and "battery full" detection, the type of battery used [GEL, NASS,
AGM, Lithium, INDIV] must be entered.
4.3.5 Ah Efficiency (CEF)
Every battery has an Ah efficiency. This means that more ampere-hours must be loaded into the
battery than can be removed. The efficiencies of lead batteries are between 80% and 95%. If the
CEF deteriorates below 70% during operation, this basically means that the battery has reached
the end of its life and needs to be replaced. The factory default setting is 95%. The CEF is
automatically adjusted during operation by means of a sliding average over the last 4 cycles.
4.3.6 Cycle depth
The cycle depth indicates the % value by which a battery must be discharged and charged for a
charge cycle to be counted. For starter batteries a value between 10-20% should be set and for
GEL batteries up to 50% can be set. The value represents the cycle stability of the battery, i.e. how
much the battery can be discharged without reducing its life.
4.3.7 Peukert Factor
The capacity of lead-acid batteries is usually specified for a 20-hour discharge. This means, for
example, that a 100 ampere-hour battery can deliver 5 amps for 20 hours before the battery is
empty. If the discharge current is higher, for example 10 amps, the battery is not able to deliver
the full 100 ampere hours. In this case, the battery voltage drops below the lower limit of 10.8 V
for 12V batteries before the battery has delivered its rated capacity.
This relationship can be captured mathematically with the Peukert equation.
In the residual time function, this equation is used to adjust the residual time at high discharge
rates. Under normal circumstances, the Peukert exponent does not need to be changed.

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 14
Usually, the Peukert exponent is set to 1.27 for lead batteries, if no deviating values are available,
and to 1.02 for lithium systems.
4.3.8 Name2
This name is displayed in the battery symbol of the additional battery and is used for clear
assignment.
4.3.9 Name3
This name is displayed in the battery symbol of the additional battery and is used for clear
assignment.
4.3.10 Shunt type / software version / update
The type of the connected shunt and its software version are displayed. A firmware update can be
uploaded to the shunt via the item "Update software" if a corresponding file (PB99R1) is available
on the SD card. To do this, the shunt must be de-energised (disconnect the green plug on the
shunt) and then press the START button. Within 30 seconds, the shunt must be supplied with
power again (plug in the green connector on the shunt) so that the update process is started. The
successful process is then displayed on the screen.
4.4 Charger
The following settings can be made:
- Charging characteristic
- Charge Control (control of the charging process by the charger or the battery monitor)
- Info on which charger is connected (ACExx) and its software version
- Software version of the ACE-LIN interface
The current charging parameters of the set characteristic curve can be read in the 4 following
fields. If the individual charging characteristic is selected, these settings can be edited:
- Maximum charging voltage (boost)
- Max. Boost duration
- Float charge voltage (float)
- Current threshold in % of the maximum power for switching to trickle charge

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 15
If no philippi ACE series charger is connected or the charger is not supplied with mains voltage, no
settings can be made.
4.5 Alarm
A tank alarm is always indicated by the associated tank symbol flashing. A battery alarm is always
displayed in the battery symbol. In addition, the alarm can be issued/configured as follows:
- optical Display illumination flashes
- Audible internal buzzer
- Relay contact potential-free relay (max. 1A)
The optical and acoustic alarm can always be acknowledged in advance by touching the screen or
can switch off automatically after a definable time.
Alarm options:
Tank alarms:
An alarm threshold can be set individually for each of the 4 tanks. The following settings are
possible:
0 %Alarm off1
..50 %. Empty alarm: if the fill level falls below the set value,
alarm is triggered. The alarm triggering is delayed by 15s.
51... 99 % Full alarm: if the fill level rises above the set value,
the alarm is triggered. The alarm is delayed by 15s.
The alarm is automatically cancelled as soon as the value has changed by 5%.
By briefly pressing the respective line, the acoustic alarm can be switched on or off. By pressing
and holding (> 2s), the respective threshold value can be edited.

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 16
Battery capacity alarms
A message appears on the monitor to charge the battery (battery appears red) if the battery falls
below the set capacity threshold.
The alarm for the alarm capacity is preset to 50%. For an average application, this value is usually
fine; however, the alarm can be adjusted according to the application's requirements.
If the state of charge drops further, 2 different thresholds take effect: Battery reserve (20%) and
battery deep discharge (0%). An alarm is triggered here depending on the configuration.
Battery voltage alarms
If there is a voltage >1V at the shunt on the terminal (+2) for the 2nd battery voltage, this is
reported as another battery. If the battery voltage drops or exceeds the set threshold value for 30
s, an alarm can be generated.
The following settings are possible in the alarm menu:
- Visual alarmLighting flickers (on / off)
- Alarm auto off0-255 sec (Attention 0 = always on)
- Relay auto off 0-255 sec (Attention 0 = always on)
The potential-free relay and the buzzer can be configured for individual alarms. Depending on the
configuration, the alarm switches on for the following alarm states and remains on until all
pending alarms have been cancelled. If an alarm has been acknowledged and a new alarm is
added, the buzzer is activated again.
Battery 1Capacity alarm Adjustable (10 - 80 %)
Battery Empty (20%) determined by battery management
Battery deep discharge (0%) determined by battery management
Overvoltage adjustable (14 - 32 V)
(Over)-temperature adjustable (40 - 60 °C)
Battery 2Undervoltage adjustable (9-24V)
Overvoltage adjustable (14-32V)
Battery 3Undervoltage adjustable (9-24V)
Overvoltage adjustable (14-32V)
The voltage alarms must be adjusted for 24V batteries!
Tank Tank 1 Level adjustable, empty or full alarm
Tank 2 Level adjustable , empty or full alarm
Tank 3 Level adjustable, empty or full alarm
Tank 4 Level adjustable , empty or full alarm

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 17
4.6 SETTINGS IN THE TANK MENU:
The respective tank menu for
the tanks shown is accessed
by pressing the button
(arrow on the right):
In the tank menu, the volume, the tank type, the sensor type can be entered and an adjustment to
the tank geometry can be made.
With the free setting of the resistance range (User R), the ohm values for 0%, 25%, 50%, 75% and
100% are entered in this menu or the tank monitor can adopt the resistance values for these fill
levels at the push of a button.
The same applies to tank sensor with a voltage output (sensor type: User U).
For the sensor type UTV 40/80, the tank depth is entered in this menu.
These settings are saved in the event of a power failure and are available again when the unit is
switched back on.
4.6.1 TANK TYPE E
There are 5 different tank symbols to choose from for each tank:
Water / Diesel / Petrol / Faecal matter (black water) / Grey water
4.6.2 VOLUME
Enter the tank volume. The content is displayed in litres.
4.6.3 SENSOR
Sensor typeTank sensorMeasuring range Geometry adjustment
TGX 10-180 (Ohm) philippi TGT / TGW 10.. 180 Ohm optional240
- 33 (Ohm) 240...33 Ohm UTR not possible! optional
User R 1 - 1000 Ohm 1 - 1000 Ohm necessary
User V (0-10V) philippi UTV (0,5-2,5V) 0.. 10V necessary
UTV 40/80 philippi UTV 40/UTV 80 0,5.. 2,5 Voptional
TDx TDS / TDN / TDT (4 - 20mA) necessary
DFS - (down) philippi DFSFlow sensor not possibleDFS + (up)
philippi DFS flow sensor not possible
TRS / RSW / DSW philippi TRS / RSW / DSWFloat switch not possible

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 18
TIL5 Rod Tuft sensorAdditional hardware TILnot possible
Gobius4 Gobius 4 (1-4V) 4 steps for from MJ 16 not possible
If the tank type does not match the tank sensor type used, either "---" is displayed as the value or
an incorrect value may be displayed.
4.6.3.2 SENSOR TYPE TGX 10 - 180 (OHM)
For this setting you need a tank sensor TGW (fresh water) or TGT (fuel) with a resistance range of
10 - 180 Ohm (10 Ohm = empty / 180 Ohm = full). In the TRIM menu, the characteristic curve of
the tank sensor can be adapted to the tank geometry.
4.6.3.3 SENSOR TYPE 240 - 33 (OHM)
For this setting you need a tank sensor with a resistance range of 240 - 33 Ohm (240 Ohm = empty
/ 33 Ohm = full). In the TRIM menu, the characteristic curve of the tank sensor can be adapted to
the tank geometry.
4.6.3.4 SENSORTYP User R
For this setting you need a passive tank sensor with any resistance range between 1 - 1000 Ohm.
For the levels 0, 25, 50, 75 and 100%, the corresponding resistance values must now be entered in
the TRIM menu.
Tank sensor: This setting option only works with passive resistance tank sensors, not with
capacitive tank sensors or active resistance sensors (e.g. philippi UTR) !
4.6.3.5 SENSOR TYPE USER V (UTV)
With this setting, tank sensors can be displayed with a voltage signal in the range of max. 0 - 10
volts. For the filling levels 0, 25, 50, 75 and 100%, the
corresponding voltage values can be entered in the TRIM menu item.
The default setting ex works
is pre-assigned to the ultrasonic tank transmitter UTV with an output signal 0.5-2.5V.
4.6.3.6 SENSOR TYPE UTV 40 / 80
For this setting you need the following ultrasonic tank sensors:
Tank depth (plus optional distance ring UTS 25) up to 40 cm: UTV 40Tank depth
(plus optional distance ring UTS 25) 40 -80 cm: UTV 80
The tank depth can then be entered in the SETUP menu with centimetre precision for each tank.
After selecting the tank type UTV 40/80, the UTV type, any spacer ring UTS and the tank depth of

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 19
the tank are entered in the submenu.
For tank depths incl. distance ring less than or equal to 40 cm, a UTV 40 is required;
above this, a UTV 80. When using a UTV 40, the adjustable range is always less than
40cm. Only UTV40 or UTV80 ultrasonic tank sensors may be used!
4.6.3.7 SENSORTYP TDx:
For this setting you need a tank sensor with a current output of 4-20mA (e.g. TDS200, TDN200, TDT
250). The calibration is carried out in the TRIM menu, where the corresponding current
measurement values can now be entered or determined for the levels 0, 25, 50, 75 and 100%.
4.6.3.8 SENSOR TYPE DFS -
For this setting you need a philippi DFS flow sensor. The connection is only possible to DFS S. The
following symbol appears under the respective tank in the main menu:
Since this sensor cannot detect whether the tank is being filled, you must enter the fill level
manually. Pressing the assigned button takes you directly to the tank menu where you can set the
fill level accordingly. If water
flows through the flow sensor DFS, this is indicated by the rotating symbol. The DFS with arrow
pointing downwards empties the corresponding tank in the display.
4.6.3.9 SENSOR TYPE DFS +
See 4.6.3.8 - Differently, this setting fills the associated tank. This is useful to record the amount of
fresh water produced when using a watermaker.
A maximum of one (1!) DFS can be connected to the BTM!
4.6.3.10 SENSOR TYPE TRS/RSW/DSW:
For this setting you need a philippi TRS float switch (mounted on top of the tank) or philippi
RSW/DSW (mounted on the side). The tank display remains at 0% until the float switch switches
through - the display then goes to 100%. No series resistor is necessary!
4.6.3.11 SENSOR TYPE GOBIUS4
The voltage output of the Gobius control unit must be connected to a tank input. The level is
displayed in 4 steps. The internal settings of the Gobius system cannot be changed from the BTM.
They must be adjusted via the Gobius display.
4.6.4 Adaptation
To adapt the level indicator to a non-rectangular tank geometry,
you have the option of adjusting the characteristic curve. The

Battery/Tank Monitor BTM2
REV 1A - FEB 2022 - Software Version 1.xPage 20
respective default settings from the selected sensor type can be adapted to the individual
conditions. This is mandatory for the tank types User R, User U, TDS:
Method 1 (tank is filled step by step):
the probe is in the empty tank. In the Setup menu, go to the setting value for 0% and read the
measured value in the middle at the bottom and enter it in the Level 0% field. Then fill the tank to
25% and enter it in the Level 25% field. Proceed in the same way with the values 50%, 75%, 100%.
This method has the advantage that even with an unusual tank shape, the content is reproduced
correctly.
Method 2 (installation e.g. TDS200 with full fuel tank):
the probe is outside the tank. In the setup, go to the setting value for 0% and read the measured
value in the middle at the bottom and enter it in the Level 0% field.
Then install the probe and read the reading in the middle at the bottom and enter it in the Level
100% field. To get the values for 25%, 50% and 75%, you must first divide the difference between
the values 0% and 100% by 4. Add this value to the value at 0% - this way you get the input value
for 25%. By adding correspondingly more, you get the values for 50% and 75%.
You can enter these values at the setting values for 25%, 50% and 75%.
Method 3:
You know the values for 0%, 25%, 50%, 75% and 100%? Then enter these values directly in the
corresponding settings.
4.7 Energy source
The current and the landed capacity are displayed in the lower left part of the main screen. The
following settings are available.
4.7.1 Name
This battery symbol is displayed on the main screen and is used for clear assignment.
4.7.2 Reset counter
The capacity counter can be set to zero again.
4.7.3 Shunt type / software version / update
The software version of the SHP shunt is displayed. A firmware update can be uploaded to the
shunt via the item "Update software" if a corresponding file (PB99R1) is available on the SD card.
To do this, the shunt must be de-energised (disconnect the green plug on the shunt) and then
press the START button. The shunt must then be restarted within 30 seconds (plug in the green
connector at the shunt) so that the update process is started. The successful process is then
displayed on the screen.
Table of contents
Other philippi Monitor manuals