RAD-...-IFS
8 / 213 PHOENIX CONTACT 105542_en_06
1.4 Installation notes
•RAD-2400-IFS and RAD-868-IFS only: Phoenix Contact hereby declares that this
wireless system complies with the basic requirements and other relevant regulations
specified in Directive 2014/53/EC.
•RAD-2400-IFS and RAD-868-IFS only: The category 3 device is suitable for installa-
tion in zone 2 potentially explosive areas. It meets the requirements of EN 60079-
0:2012+A11:2013 and EN 60079-15:2010.
• Installation, operation, and maintenance may only be carried out by qualified electrical
engineers. Follow the installation instructions as described.
• When installing and operating the device, the applicable regulations and safety direc-
tives (including national safety directives), as well as general technical regulations must
be observed. The technical data is provided in the packing slip and on the certificates
(conformity assessment, additional approvals where applicable).
• Opening or modifying the device is prohibited. Do not repair the device yourself; re-
place it with an equivalent device. Repairs may only be carried out by the manufacturer.
The manufacturer is not liable for damage resulting from non-compliance.
• The IP20 degree of protection (IEC 60529/EN 60529) of the device is intended for use
in a clean and dry environment. Do not subject the device to mechanical and/or thermal
stress that exceeds the specified limits.
• To protect the device against mechanical or electrical damage, install it in suitable
housing with an appropriate degree of protection in accordance with IEC 60529.
• The device complies with the EMC regulations for industrial areas (EMC class A).
When used in residential areas, the device may cause radio interference.
• Only specified devices from Phoenix Contact may be connected to the 12-pos.
S-PORT interface.
• The device is not designed for use in atmospheres with a danger of dust explosions.
• If dust is present, the device must be installed in suitable approved housing and the sur-
face temperature of the housing must be taken into consideration.
WARNING: Risk of electric shock
During operation, certain parts of the devices may carry hazardous voltages. Disregarding this warning may
result in serious personal injury and/or damage to equipment.
– Provide a switch/circuit breaker close to the device, which is labeled as the disconnect device for this de-
vice or the entire control cabinet.
– Provide overcurrent protection (I ≤ 6 A) within the installation.
– Disconnect the device from all power sources during maintenance work and configuration (for SELV or
PELV circuits the device can remain connected).
– The device housing provides basic insulation from neighboring devices for 300 Vrms. If several devices
are installed next to each other, this must be taken into consideration and additional insulation may have
to be installed. If the neighboring device is equipped with basic insulation, no additional insulation is re-
quired.