Curves of constant speed
In the cur es I, II, and III the pump operates at constant speed and flow rate aries according to the load loss of
the circuit along the selected cur e.
Form of the ni ht temperature decrease performance
To acti ate the night temperature decrease press the key If turns on the adjacent field, the decrease of
temperature is enabled and the pump automatically changes from normal operation to the night-time
temperature reduction.
The change depends on the temperature of impulsion. The pump automatically switches to night-time
temperature reduction, when the temperature drops in the next hour more than 10 ° - 15 ° C. The display
shows "-C".
The change to normal operation is carried out without delay, as soon as the temperature rises 3 ° C.
Permanent ni ht-time temperature reduction
The night-time temperature reduction could be adjusted permanently. After acti ating the decrease of
temperature, you ha e to press the button again for 5 seconds. After releasing the button in the display
appears "-C".
The pump is stable in operation decrease until:
- do not press the key again
- does not increase the temperature of impulsion.
In these cases turns on the night temperature decreases, as well as after a power failure.
Technical data U Delta 55-XX
Maximum hei ht of support: 6,0 m
Maximal flow: 3200 l/h
Power P1 (W): 3 - 42
Supply tension: 1x230V 50Hz
Protection : IP42
Heat cate ory: F
Room temperature: 0ºC up to 40ºC
Temperature of the fluid: +5 up to 110ºC
Max. pressure of the system: 10 bar
Approved fluids: Hot water VDI2035
Mix water/glycol 1:1