promesstec UMU-FD 2 User manual

promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
User manual
Configuration module/ front display UMU-FD 2
Version 2.1.1

2
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
Inhalt
1. General................................................................................................................ 3
1.1 Information .................................................................................................... 3
1.2 Drawings, shortcut......................................................................................... 3
2. Transport, Packaging, Storage ........................................................................... 5
2.1 Transport....................................................................................................... 5
2.2 Packaging...................................................................................................... 5
2.3 Storage.......................................................................................................... 5
3. Safety instructions............................................................................................... 6
3.1 Intended use of the product........................................................................... 6
3.2 Stuff qualification........................................................................................... 7
3.3 Special hazards............................................................................................. 7
4. Starting and operation......................................................................................... 8
4.1 Before mounting............................................................................................ 8
4.2 Assembly / Installation / Configuration........................................................... 8
5. Configuration module/ front display UMU-FD 2................................................... 8
6. Attaching / detaching the UMU-FD 2................................................................... 9
7. Electrical data.................................................................................................... 10
8. Display structure................................................................................................ 11
8.1 Operation of the function keys..................................................................... 11
8.2 Display orientation....................................................................................... 12
9. Settings –flow chart.......................................................................................... 13
10. Maintenance, dismounting, return, cleaning, disposal ................................... 14
10.1 Maintenance, dismounting ....................................................................... 14
10.2 Return ...................................................................................................... 14
10.3 Liability..................................................................................................... 14
10.4 Cleaning................................................................................................... 14
10.5 Disposal ................................................................................................... 14
10.6 Control of the device ................................................................................ 15
11. Installation....................................................................................................... 15
12. Order code...................................................................................................... 15

3
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
1. General
1.1 Information
-These operating instructions give important information on how to use the mea-
suring instrument. A prerequisite for safe working is compliance with all specified
safety instructions.
-The qualified personnel must have read and understood these operating instruc-
tions before installing and commissioning the sensor.
-These operating instructions are part of the product. Therefore, keep them in a
place that is accessible to all users at all times, close to the place of use.
-The local regulations and safety regulations that apply to the sensor's area of
application must be observed.
-If the serial number on thenameplate is no longer legible (e.g. due to mechanical
damage), traceability is no longer ensured.
-The sensors described in the operating instructions are developed and manu-
factured according to the latest knowledge. All components are subject to strict
quality and environmental criteria during production.
-The manufacturer is not liable if damage occurs as a result of improper use, non-
observance of these operating instructions, use of insufficiently qualified specia-
list personnel and unauthorized modifications to the sensor.
1.2 Drawings, shortcut
Warning!
A non-observance can cause injuries to persons and/or the demoli-
tion of the device. There can be a dangerous to life.
Attention!
A non-observance can cause a faulty operation of the device or lead
to property damage.
Info!
A non-observance can have influence on the operation of the device
or cause unintentional reactions of the device.
Danger!
When not observing the safety instructions, there is a risk of serious
or fatal injuries caused by electrical power.
Configuration module/front display UMU-FD
2

4
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
Warning!
Possibly a dangerous situation can occur, which results in burns be-
cause of hot surfaces or liquids, if not avoided.
Warning!
This device is designed for connection to life-threatening electrical
voltages. Disregarding this warning can lead to severe injuries or me-
chanical destruction. To avoid the risk of electric shock or fire, the sa-
fety rules in the manual must be observed and the instructions follo-
wed. The specification values must not be exceeded and the device
may only be used in accordance with the following description. Read
the manual carefully before using the device. Only qualified persons
(technicians) are allowed to install this device. If the device is not
used as described in this manual, the protective devices of the de-
vice will be impaired.
Warning!
Before the device has been permanently installed, no dangerous
voltage may be connected to it, and the following measures should
only be carried out when the device is de-energized and under ESD-
safe conditions:
-Installation, assembly and disassembly of lines.
-Troubleshooting the device.
Warning!
The front panel of the device must not be opened, as this could da-
mage the contacts for contacting the UMU-FD 2 front display.
The device does not contain any internal DIP switches or program-
ming bridges. The UMU 100 must be mounted on a DIN rail accord-
ing to DIN 60715.
The CE mark is the visible sign that the device complies with the re-
gulations.
Double insulation is the symbol that the device meets special insula-
tion requirements.

5
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
2. Transport, Packaging, Storage
2.1 Transport
Check the instrument for any damage that may have been caused during transpor-
tation. If, report them immediately.
2.2 Packaging
Do not remove packaging until just before mounting. Keep the packaging as it will
provide optimum protection duringtransport (e.g. change in installation site, sending
back).
2.3 Storage
For longer term storage avoid the following influences:
1. Direct sunlight or proximity to hot objects
2. Mechanical vibration, mechanical shock (putting it hard down)
3. Soot, vapour, dust and corrosive gases
If possible store the device in its original package or an equivalent one.

6
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
3. Safety instructions
More important safety instructions can be found in the individual
chapters.
Definitions:
Dangerous voltages are defined as the ranges:75...1500 75...1500 volts DC and
50...1000 volts AC.
Technicians are qualified persons who are trained or instructed to carry out an in-
stallation, operation or possible troubleshooting that is justifiable from a technical as
well as from a safety point of view.
Operating personnel are persons who set or operate the pushbuttons or potentiom-
eters of the product during normal operation and who have been made familiar with
the content of this manual.
Reception and unpacking:
Unpack the device without damaging it and check upon receipt that the device type
corresponds to what you ordered. The packaging should remain with the device until
it is installed in its final location.
3.1 Intended use of the product
Environmental conditions:
Direct sunlight, strong dust formation or heat, mechanical shocks and impacts are to
be avoided; the device must not be exposed to rain or excessive moisture. If neces-
sary, heating that exceeds the specified limits for the ambient temperature must be
prevented with the help of a cooling fan. The device must be installed in pollution
degree 2 or better.

7
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
3.2 Stuff qualification
Improper handling can result in considerable injury and damage to
equipment. The activities described in these operating instructions
may only be carried out by skilled stuff who have the qualifications
described below. Keep unqualified stuff away from hazardous areas.
For installation and starting of the flow-meter the stuff has to be familiar with the
relevant regulations and directives of the country and must have the qualification
required. They must have knowledge on measurement and control technology, have
to be acquainted with electric circuits, are capable of carrying out the work described
and can independently recognize potential hazards. Depending on the operation
conditions of the application they have to have the corresponding knowledge, e.g.
of aggressive media..
3.3 Special hazards
Comply with the country-specific regulations (e.g. standards) and
observe the applicable standards and guidelines for special applica-
tions (e.g. for hazardous media such as acetylene, combustible or
toxic substances as well as for refrigeration systems and compres-
sors).
Failure to comply with the relevant regulations can result in serious
personal injury and damage to property!
A protection from electrostatic discharge (ESD) is required. The pro-
per use of grounded work surfaces and personal wrist straps is re-
quired when working with exposed circuitry (PCB, printed circuit
boards), in order to prevent static discharge from damaging sensitive
electronic components.
There is a danger of death caused by electric current. Upon contact
with life parts, there is a direct danger of death. Electrical instruments
may only be installed and connected by skilled electrical personnel.
Operation using a defective power supply unit (e.g. short circuit from
the mains voltage to the voltage output) can result in life-threatening
voltages at the instrument.
Residual media in dismounted instruments can result in a risk to per-
sonnel, the environment and equipment. Take sufficient precaution-
ary measures. Do not use this instrument in safety or Emergency
Stop devices. Incorrect use of the instrument can result in injury.
Should a failure occur, aggressive media with extremely high tem-
perature and under high pressure or vacuum may be present at the
instrument.

8
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
4. Starting and operation
4.1 Before mounting
Check that a fully assembled transmitter has been delivered.
Examine the device for any transport damage that may have occur-
red. If such damage is present, notify the transport company and
supplier immediately.
Keep the packaging as it offers optimal protection during transport.
Make sure that the housing and the connection contacts are not
damaged.
4.2 Assembly / Installation / Configuration
-The extremely low power consumption allows the units to be mounted side by
side with no air gap between them, even at an ambient temperature of 60°C.
Calibration and adjustment
During the calibration and adjustment, the measurement and the connection of exter-
nal voltages must be carried out in accordance with this manual, and the technician
must use tools and instruments that are safe from the point of view of safety.
Operation in normal mode
The operating personnel may only adjust or operate the device if these are installed
in a reasonable manner in control panels or similar, so that the operation does not
entail any danger to life or material. This means there must be no risk of contact and
the device must be placed in such a way that it is easy to use.
5. Configuration module/ front display UMU-FD 2
•Programming front for universal transmitter UMU 100
•Monitoring of process values and status via the built-in display
•Scroll help texts in 7 languages
Applications
•Communication interface for programming and adjusting the operating parame-
ters of the UMU 100.
•The easy-to-read display can be used to monitor the process signals, to simulate
the output signal and to display sensor errors and internal device errors.
•Can be plugged from one UMU 100 to the next to transfer the data from the first
transmitter to the next.
•If the device is integrated in the process, the display shows the corresponding
process values and the respective process status.

9
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
Technical features
•Easy to read dot matrix LCD display.
•Backup memory for loading and saving device configuration.
•Programming access can be blocked by assigning a password. The password is
stored in the device saved to ensure a high level of protection against unauthorized
configuration changes.
6. Attaching / detaching the UMU-FD 2
1: Insert the two fixing pins of the UMU-FD 2 into the openings on the upper front
panel of the UMU 100.
2: Snap the UMU-FD 2 display into place at the bottom edge.
Remove the UMU-FD 2
3/4: Press the release of the UMU-FD 2 on the underside and carefully remove the
UMU-FD 2.

10
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
Order details
UMU 100 = universal transmitter
UMU-FD 2 = display / programming front
UMU-CJC = CJC-connecting terminal
7. Electrical data
Environmental conditions:
Operating temperatur . . . . . . . . . . . . . . . . . . . . . . . . . -20°C to +60
Storage temperature . . . . . . . . . . . . . . . . . . . . . . . . . .-20°C to +85°C
Relative humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non cond.)
protection class. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP20 after installation
Installation in pollution degree 2 / overvoltage category II
Mechanical specifications:
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . .73,2 x 23,3 x 26,5 mm
Dimensions (HxWxD) with 4000er- / 9000er-unit . . . . . . 109 x 23,5 x 131 mm
Weight approx. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 g
General specifications:
Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6,5...20 V via UMU 100
Power requirement, max.. . . . . . . . . . . . . . . . . . . . . .0,15 WmA

11
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
8. Display structure
By default, the UMU-FD 2 switches to monitoring mode for process monitoring. The
UMU-FD 2 can be switched to configuration or simulation mode using the buttons on
the front panel.
UMU-FD 2
Line 1 shows the scaled process va-
lue
Line 2 shows the selected enginee-
ring unit
Line 3 shows the analog output value
or TAG number
Line 4 shows the relay and communi-
cation status as well as the signal
history
8.1 Operation of the function keys
When using the FD 2 front display to configure a UMU device, you are guided
through all parameters and can select the appropriate settings for the respective ap-
plication. There is a scrolling help text for each menu, which is automatically shown
on the 3rd line of the display.
The configuration can be carried out using 3 function keys:
•With ▲ you can increase the numerical value or select the next parameter.
•With ▼ you can decrease the numerical value or select the previous parame-
ter.
•With OK you can save the selected value and continue to the next menu.
After completing the configuration, the display returns to the normal state (monitor-
ing). If 3 is held down, one can return to the previous menu or to the normal state
without saving the changed values or parameters.
If no key is pressed for 1 minute, the display returns to the normal state without sav-
ing the changed values or parameters.
For more information on the device-specific programming menus, please refer to the
operating instructions for the respective device.

12
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
UMU-FD 2
Relay status (relay energized) When the
icon flashes with 1 or 2, it means a delay in
relay action (configurable on/off delay).
The arrow keys indicate that the process
value is going up/down.
The circle icon confirms the host communi-
cation indicator
8.2 Display orientation
In order to ensure proper operability if the device is installed overhead, the display
can be rotated by 180 degrees using the "ORIEN" menu item.

13
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
9. Settings –flow chart
!!! The display will return to “Monitor” (monitoring mode) from any
menu if no button is pressed for 1 minute.
The menus / texts with a gray background are only displayed as an
aid and do not belong to the respective UMU-FD 2 submenu. The
product-specific menu structure for the UMU 100 device can be
found in the associated product manual

14
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
10. Maintenance, dismounting, return, cleaning, disposal
10.1 Maintenance, dismounting
Residual media in dismounted instruments can result in a risk of
per-sonnel, the environment and equipment. Take sufficient precau-
tionary measures.
There is a risk of burns. Let the instrument cool down sufficiently
before dismounting. During dismounting there is a risk of danger-
ously hot pressure media escaping.
10.2 Return When returning the instrument, use the original packaging or a suit-
able package.
To avoid a damage, use for example antistatic plastic film, shock-
absorbent material, a marking as highly sensitive measuring instru-
ment.
10.3 Liability
To the extent that the instructions in this manual are not followed exactly, the cus-
tomer cannot assert any claims against promesstec GmbH, which could otherwise
exist in accordance with the sales agreements entered into.
10.4 Cleaning
Before cleaning the instrument disconnect the electrical connection.
Clean the instrument with a moist cloth. Electrical connections must
not come into contact with moisture.
10.5 Disposal
Dispose instrument components and packaging materials in accord-
ance with the respective waste treatment and disposal regulations
of the region or country to which the sensor is supplied.

15
promesstec GmbH I Niedersachsenstraße 4 I D- 48465 Schüttorf I Tel.:+49 (0)5923/ 90 229 0 I Fax:+49 (0)5923/ 90 229 29
E-Mail: office@promesstec.com I Internet: www.promesstec.com
10.6 Control of the device
The devices are checked before shipment and sent in perfect condition. If damage
is visible on the device, we recommend a thorough inspection of the transport pack-
aging. In the event of damage, please inform the supplier immediately.
11. Installation
The device may only be connected by technicians who are familiar with and follow
the technical terms, warnings and instructions in the manual.
If you have any doubts about the correct handling of the device, you should contact
promesstec GmbH directly.
The installation and connection of the device must be carried out in accordance with
the applicable regulations of the respective country regarding the installation of elec-
trical equipment, including cable cross-section, (electrical) pre-fusing and positioning.
A description of input/output and supply connections is given on the block diagram
and on the side label.
The following applies to devices that are permanently connected to a dangerous volt-
age: The maximum size of the back-up fuse is 10A and must be easily accessible
and close to the unit, along with a circuit breaker. The circuit breaker should be
marked in such a way that there can be no doubt that it cuts power to the equipment.
12. Order code
Order code: UMU-FD 2 Order example: UMU-FD 2