Integrated Access Controller
Installation Manual
LED
123
456
789
0 #
3000
ProVisual, Inc.
CCTV & Security Distributor
Integrated Access Controller
Installation Manual

Product ConnectionProduct Connection
Installation ManualInstallation Manual
Product ManualProduct Manual
Product MaintenanceProduct Maintenance
Home & Business Security Solutions
Function DebuggingFunction Debugging

Provisual Integrated Access Control Series: AC-930P
Anson Integrated Access Control is characterized by its elegant design and convenient application
and installation, which is especially suitable for office buildings and shops. The device is equipped
with built-in reader and can work both as controller and reader.
Anson Integrated Access control should be installed indoor. Please consider water-proof facility in
case outdoor application is needed.
For detailed information, please refer to Product Manual and Wiring Diagram. Please make sure
installation is correctly completed before turn on the power. When connect any external device, please
turn off the power. This manual is only a general instruction and all products mentioned in this
manual are Anson products.
Product
Manual CCTV & Security Distributor
Home & Business Security Solution
Features
Operation
Instruction
Notice
Product Series

1. If there is no sound when card is presented to the reading area, the reading function maybe
damaged.
2. If there is no sound when press the keys, the keypad maybe damaged.
3. When add card, if the device exits program mode automatically, the memory maybe
damaged.
4. If valid card is read and OK light is on, while relay does not act, the lock control may
malfunction.
5. If relay keeps on in open state, buzzer keeps buzzing, and SW-GND is short or lower than
, the keys maybe damaged.
6. MenCi-GND is short or lower than 3.5V, the door magnet input maybe damaged.
7. Voltage of DATA0, DATA1 and GND should be higher than 3.5V, otherwise exterior reader can
not work properly.
8. When RS485 is applied, voltage between 485+ and 485- is around 5 voltages.
The life of products is related to application environment and application method. Please carefully
follow the product manual and installation manual.
In case of any problem, please contact with our technical support instead of self-repairment.
Please keep the original state of the products when sending back for repair. Please notify us
if you have any special demand, and we will feedback within 48 hours.
ProVisual, Inc.
Technical Support Department
Toll Free: 1(800)593-6955
3.5V
support@securitycameradistributor.com
Product
Maintenance
Product
Maintenance
Common Question
Home & Business Security Solution
CCTV & Security Distributor

AC-930PAC-930P
123
456
789
0 #
150mm
88mm
30mm
设备参数
Product
Manual
485 232
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
Fixing Hole
Jumper
The Back
Fixing Hole
Fixing Hole
The Side
The Front
Working Voltage:DC9-15V
Static Current:≤120mA
Reading Distance: 5-10cm
Card Type: ID card
Working Temperature: -15℃~55℃
Card Capacity: 3000pcs
Input Interface: 1pcs exit button, 1pcs door magnet
Output Interface: 1pcs lock control port (normal open, normal close), 1pcs
door magnet alarm output port (normal close)
Communication Mode:RS232/RS485
Reader Interface: Wiegand 26
Product Parameters
Home & Business Security Solution
CCTV & Security Distributor

AC-930PAC-930P
Installation
Manual
Installation
Manual
1. Remove the two keys first.
2. Unfasten the two screws.
Push up the back cover to open
First open the lower part of
backcover for around 1cm.
Please note that open too
wide may lead to damage to
the device.
3. Open the back cover and connect the
device according to the wiring diagram.
4. Fix the backcover on the wall
Reassemble the device. (according
to 1, 2 and 3 in reversed order.
Home & Business Security Solution
CCTV & Security Distributor

Connect with Electric Bolt
Power Interface
AC-930P Interface
+12V
GND
Connect with Power
+12V
GND
V+
V-
NO
COM
NC
Connect with EM Lock
+
-
+12V
GND
Fail-safe
Fail-secure
+12V
GND
SIGNAL
SIGNAL
+12V
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
*Valid state:door magnet is normal open.
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
*Valid state:door
magnet is normal open.
AC-930P Interface
Power Interface
AC-930P Interface
AC-930P Interface
Power Interface
Connect with Electric Lock
Electric Bolt
Iron Core Cover Plate
Door Magnet
Power Interface
485 232
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
485 232
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
Power
Interface
Reader
Interface
Exit Button
Interface
RS232
Interface
Door Magnet
Alarm Output
Interface
Lock Control
Interface
Door Magnet
Interface
Door bell
Interface
RS485
Interface
AC-930P Interface
AC-930PAC-930P
Home & Business Security Solution
CCTV & Security Distributor
Product
Connection
Product
Connection

COM1
COM2
Exit Button
For this type of connection, the
barrier switch is closed in normal
status. When user presents
card or presses the exit button,
the barrier will be opened, The
opening time depends on the
door-open delay time. It is
recommended to install ultra-red
and ground sensor for protection.
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
+12V
GND
+
-
接读 卡器
262RP
1 2 3
4 5 6
7 8 9
* 0 #
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
Black
Red
Green
White
AC-930P Interface AC-930P Interface
Barrier Interface
(Electric Level Signal)
Common end
Stop
Close
Open
Automatic Door Interface
( Switch Signal)
The automatic door is open when
COM1-COM2 is short circuit.
Connect with Automatic Door
Connect with Barrier
AC-930P Interface AC-930P Interface
Active Boorbell
Connect with Door Bell
Power Interface
AC-930P Interface
AC-930P Interface
Connect with Reader
Alarm Light
Connect with Alarm Device
AC-930PAC-930P
Home & Business Security Solution
CCTV & Security Distributor
Product
Connection
Product
Connection

Connect with RS485
For 485 communication, please follow
the diagram for connection and no other
connection mode should be used.
Converter
485+
485-
12345
DB9-Hole
Computer
Interface
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
12345
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
RS232
485 232
AC-930P Interface
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
RS232\TCP/IP
485 232
Rj45
ASV-TCP/IP
DC9~30V
232
485
Rs232
9~30V+
9~30V-
485+
485-
Rs485
12345
DB9-Hole
Rs 232
Connect with
PC or Router
AC-930P Interface
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
RS485
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
PWD
RxD
TxD
RS485
RS232
RS485-RS232
Convertor
Computer
Interface
T/R+
T/R-
GND
485 232
AC-930P Interface
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
485 232
Rj45
AC-200TCP
DC9~30V
232
485
Rs232
9~30V+
9~30V-
485+
485-
Rs485
Rs 485
RS485\TCP/IP
Connect with
PC or Router
AC-930P Interface
Product
Connection
Product
Connection
AC-930PAC-930P
Home & Business Security Solution
CCTV & Security Distributor

A
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
GND
12V
DAT0
DAT1
SW
GND
MenC1
BELL
BELL
RX
TX
GND
485+
485-
2C
2NO
1NO
1C
1NC
GND
1 2 3
4 5 6
7 8 9
0 #
Invalid Card: If the reader sounds twice after the card is
presented to the reading area for one second, the card is invalid.
Valid Card: If after the card is presented to the reading area for
0.5 seconds, the reader sounds once, green lights on and
delay acts, then the card is valid.
When the buzzer sounds once,
Dial “*”, the orange light flashes; Input“000000”, the orange
light turns on and device enters program mode. This means
the keypad is OK.
1 , 1 1
Adjust the multimeter to , When the power is on,
in normal state, 1C- NC is short circuit while C- NO
is open circuit. When present the valid card or press
the exit button, 1C-1NC turns into open circuit, while 1C-
1NO is short circuit.
1C
1NC
1NO
1C
1NC
1NO
Normal State Door-open State
Test Reading Card
Test the Keypad
Test Output
Test Input
If valid default input is normal open, no input available for the
device when input signal is open-circuit; while input available
when input signal is close-circuit. The status reversed when
valid default input is normal close.The user can decide the
type of default input setup in the software. AC-930P has two
input interfaces: SW-GND is button input; MenCi-GND is door
magnet input. Both of them can be changed in “channel setup”.
Test Reading Card
AC-930P Interface
AC-930P Interface
Home & Business Security Solution
AC-930PAC-930P
CCTV & Security Distributor
Function
Debugging
Function
Debugging

After the exterior device is connected with AC-930P, please
select Tools---Card Register in the software program. Then,
select the exterior device and start to read the card. If you
can find the card number in the list, it means the exterior device
works correctly.
Connect with Exterior Identification Device
1. Select the device
2.Start to read card
3. Get the card
number
Test the LCD
The LCD will display the Provisual and the time, after turn
on the power for . AC-930P
Provisual
200 7- 0 4- 1 6 14:2 0
123
456
789
0 #
Test the Communication
Rs485
AC-930P has two kinds of communication modes: RS232
and RS485. User can chose the communication mode by
setting up the jumper. AC-930P can connect with PC serial port,
and one serial port only connects with one AC-930P.
RS485 signal should be converted to RS232 signal before it
can communicate with PC. RS485 can connect with
multiple devices. After ASI-8930 is connected with PC, user
can detect AC-930P address by detecting serial port (please
refer to the user manual to setup the address). If
“connected” is displayed, the communication is ok. User
can get version and model number of AC-930P by inputting the
address and clicking Auto Detect.
Setup the Jumper
Rs232
Test the time of AC-930P
Time adjustment is shown in the picture on the left. The time of
controller should be in consistent with PC. User can get
updated time for controller by press“Refresh”. If controller
time is incorrect, card record may get lost, validity of card-
read is in doubt, and moreover, valid card may turn into be
invalid.
PC time should be in consistent with controller time;
otherwise the reader may not work properly.
*
Function
Debugging
Function
Debugging
AC-930PAC-930P
Home & Business Security Solution
CCTV & Security Distributor

Urgent Maintenance:
1. When the exterior reader can not read the cards, please
test the voltage of DATA0—GND and DATA1---GND. If the
voltage is less than 3.5V, please weld TVS2, TVS3.
2. When door magnet input fails, please test the voltage
between Menci and GND. If the voltage is less than 3.5V,
please weld TVS5.
3. When exit button input fails, please test the voltage between
SW and GND. If the voltage is less than 3.5V, please weld
TVS4.
PCB
Common Question
1. If there is no sound when card is presented to the reading area, the reading function maybe damaged.
2. If there is no sound when press the keys, the keypad maybe damaged.
3. When add card, if the device exits program mode automatically, the memory maybe damaged.
4. If valid card is read and OK light is on, while relay does not act, the lock control may malfunction.
5. If relay keeps on in open state, buzzer keeps buzzing, and SW-GND is short or lower than , the
keys maybe damaged.
6. MenCi-GND is short or lower than 3.5V, the door magnet input maybe damaged.
7. Voltage of DATA0, DATA1 and GND should be higher than 3.5V, otherwise exterior reader can not work
properly.
8. When RS485 is applied, voltage between 485+ and 485- is around 5 voltages.
9. The LCD have no information to be displayed, after turn on the power for AC-930P. The starting
program maybe damaged.
The life of products is related to application environment and application method. Please carefully follow
the product manual and installation manual.
In case of any problem, please contact with our technical support instead of self-repairment.